– 25 –
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. 4-Way Air Discharge Cassette Type
RAV-SP180UT-UL, RAV-SP240UT-UL
RAV-SP300UT-UL, RAV-SP360UT-UL, RAV-SP420UT-UL
No.
1
2
3
4
5
6
Parts name
Fan motor (for indoor)
Thermo. sensor (TA-sensor)
Heat exchanger sensor (TCJ-sensor)
Heat exchanger sensor (TC-sensor)
Float switch
Drain pump motor
Type
SWF-340U60-2
328 mm
Ø6 mm, 1000 mm
Ø6 mm, 1000 mm
FS-0218-102
MDP-1401
Specifications
Output (Rated) 60 W
10 k
Ω
at 77°F (25°C)
10 k
Ω
at 77°F (25°C)
10 k
Ω
at 77°F (25°C)
—
—
Type
ICF-340U150-1
328 mm
Ø6 mm, 1000 mm
Ø6 mm, 1000 mm
FS-0218-102
MDP-1401
No.
1
2
3
4
5
6
Parts name
Fan motor
Thermo. sensor (TA-sensor)
Heat exchanger sensor (TCJ-sensor)
Heat exchanger sensor (TC-sensor)
Float switch
Drain pump motor
Specifications
Output (Rated) 150 W
10 k
Ω
at 77°F (25°C)
10 k
Ω
at 77°F (25°C)
10 k
Ω
at 77°F (25°C)
—
—
5-2. Under Ceiling Type
RAV-SP180CT-UL, RAV-SP240CT-UL, RAV-SP300CT-UL, RAV-SP360CT-UL, RAV-SP420CT-UL
No.
1
2
3
4
5
6
7
8
Parts name
Fan motor (SP180CT-UL)
Fan motor (SP240CT-UL)
Fan motor (SP300, 360, 420CT-UL)
Thermo. sensor (TA-sensor)
Heat exchanger sensor (TCJ-sensor)
Heat exchanger sensor (TC-sensor)
Louver motor
Reactor
Type
SWF-340U60-1A
SWF-340U60-2A
SWF-340U120-2A
155 mm
Ø6 mm, 1200 mm
Ø6 mm, 1200 mm
MP24Z2N
CH-43-2Z-T
Specifications
Output (Rated) 60 W
Output (Rated) 60 W
Output (Rated) 120 W
10 k
Ω
at 77°F (25°C)
10 k
Ω
at 77°F (25°C)
10 k
Ω
at 77°F (25°C)
DC 12 V
10 mH, 1 A