– 146 –
n
Changing of settings for Fahrenheit display
• When you use this air conditioner for the first time, it takes approx.
5 minutes until the remote controller becomes available after power-on.
Procedure
1
Push simultaneously
TEST
+
SET
+
CL
buttons for 4 seconds or more.
After a while, the display part flashes as shown right. Check the displayed
CODE No. is [10].
• When the CODE No. is other than [10], push
TEST
button to erase the
display and repeat procedure from the first step. (After pushing
TEST
button,
operation of the remote controller is not accepted for approx. 1 minute.)
(For a group control, No. of the firstly displayed indoor unit becomes the
header unit.)
Procedure
2
Every pushing
UNIT LOUVER
UNIT button, the indoor unit No. in the group control
is displayed in order. Select the indoor unit of which setup is changed.
In this time, the position of the indoor unit of which setup is changed can be
confirmed because fan and louver of the selected indoor unit operate.
Procedure
3
1. Using temp. setup
TEMP.
buttons, specify CODE No. [33].
(CODE No. [33]: Fahrenheit display)
2. Using timer
TIME
buttons, change the line address from [0] to [1].
3. Push
SET
button. In this time, the setup finishes when the display
changes from flashing to lighting.
TEMP.
/ OFF
SET
TIME
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
C
TIMER SET
MODE
FAN
TEST
CODE No.
UNIT No.
R.C.
No.
SET DATA
SETTING
CODE No.
UNIT No.
R.C.
No.
SET DATA
SETTING
SETTING
Procedure
4
After check of the changed contents, push
TEST
button. (Setup is determined.)
When pushing
TEST
button, the display disappears and the status becomes the usual stop status.
(When pushing
TEST
button the operation from the remote controller is not accepted for approx. 1 minute.)
• If the operation from the remote controller is not accepted even 1 minute or more passed after pushing
TEST
button, it is considered that the address setup is incorrect.
In this case, the automatic address must be again set up.
Therefore repeat procedure of the setup change from the
Procedure
1
.