background image

Programmable Dual Fuel Thermostats

Installation, Start-Up, and Operating Instructions

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

INDEX

Page

SAFETY CONSIDERATIONS .....................................................1
INTRODUCTION ..........................................................................1
SYSTEM CONSIDERATIONS ....................................................1
APPLICATION ..............................................................................2
DESCRIPTION OF OPERATION ............................................2-3
INSTALLATION CONSIDERATIONS .......................................3
INSTALLATION......................................................................3-12

Thermostat Location .................................................................3
Set DIP Switches...................................................................3-4
Install Thermostat .....................................................................4
Set Thermostat Configuration ...............................................4-6
Check Thermostat Operation....................................................6
Final Settings ............................................................................7
Checklist....................................................................................7

WIRING DIAGRAMS .............................................................7-10
OPERATIONAL INFORMATION.............................................11
TROUBLESHOOTING ...............................................................11
CONFIGURATION RECORD....................................................12

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installa-
tion may damage thermostat.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.

INTRODUCTION

Carrier’s 7-day programmable dual fuel thermostat is a wall-
mounted, low-voltage thermostat which provides proper control of
a heat pump (HP) and furnace combination without using a
HP/furnace interface kit. Separate heating and cooling set points,
plus auto changeover allow setback programming for maximum
energy savings. Up to 4 time/temperature settings per 24 hour
period for 7 independent days may be programmed. Batteries are
not required; during a power interruption, the internal memory
stores programs for an unlimited time and the clock continues to
run for at least 72 hrs.

SYSTEM CONSIDERATIONS

The dual fuel thermostat is designed to be used only in HP/furnace
installations. It replaces a conventional 2-stage HP thermostat and
a HP/furnace interface kit. An outdoor temperature sensor, Part
No. TSTATXXSEN01-B MUST be used with this thermostat. It is
supplied with thermostat.

If HP is not already equipped with a high-pressure switch, one
must be added for dual fuel applications. It protects HP from
overpressure which would occur if a failure resulted in both
HP

and

furnace

operating

at

same

time.

Kit

No.

KSAHI0201HPS includes required switch and instructions
for its proper installation.

A HP/furnace installation has several special requirements. Fore-
most is that furnace and HP must not be allowed to operate at same
time, except during HP defrost. A second is to have furnace
complete a heating cycle once it is turned on. A third is the need
to have HP not operate at all when outdoor temperatures are below
a certain value. A fourth is to have the furnace not operate at all
when outdoor temperatures are above a certain higher value.
Finally, HP and furnace must work together properly to provide an
efficient and comfortable defrost. These requirements are ad-
dressed by the dual fuel thermostat itself and an interface kit is
NOT required.

As an ENERGY STAR Partner, Carrier Corporation has
determined that this product meets the ENERGY STAR
guidelines for energy efficiency.

Fig. 1—Carrier Programmable Thermostat

A98426

HEIGHT (IN.)

WIDTH (IN.)

DEPTH (IN.)

4-1/4

7-1/2

1-3/8

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

misc. misc.

PC 101

Catalog No. 03TS-TA9

Printed in U.S.A.

Form TSTAT-18SI

Pg 1

10-98

Replaces: TSTAT-9SI

Summary of Contents for Programmable Dual Fuel Thermostats

Page 1: ...ettings per 24 hour period for 7 independent days may be programmed Batteries are not required during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs SYSTEM CONSIDERATIONS The dual fuel thermostat is designed to be used only in HP furnace installations It replaces a conventional 2 stage HP thermostat and a HP furnace...

Page 2: ...ing The temperature range is 5 55 F When the outdoor temperature is above the auxiliary heat lockout setting the heat pump will become the primary source and the gas furnace cannot come on except in defrost or emergency heat mode The auxiliary heat lockout setting can never be set below the balance point setting and likewise the balance point can never be set above the auxiliary heat lockout setti...

Page 3: ...lied with the unit and must be installed Plan installation so that 2 wires can be run from the thermostat to an outdoor location preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection Sensor can be mounted to outdoor unit and existing control wires may be used for its connection Details are provided in ...

Page 4: ...s See Fig 2 through 9 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push any excess wire into wall and against mounting base Seal hole in wall to prevent air leaks Leaks can affect operation 10 Snap hinge back together 11 Close the...

Page 5: ...gain to flash upper small display for selection of another option or press END to exit the configuration mode Option 8 Auxiliary Heat Lockout Setting This option allows selection of an outdoor temperature of 5 through 55 F in 5 steps or equivalent values in C or OF off Furnace is prevented from operating for outdoor temperatures above the selected temperature If OF off is selected furnace operatio...

Page 6: ...ater due to a staging timer which requires 15 minutes of low before high comes on The UP and FAN buttons cannot be used to defeat this timer This timer can be defeated by reducing the set point to more than 5 below room temperature bringing on a high speed demand within 5 seconds Remember 2 speed units have a 1 minute off time between lo and high speed so the thermostat s demand will not show imme...

Page 7: ... The FAN button may be used to select between AUTO fan on only with equipment and ON fan on continuously fan modes Step 7 Checklist 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner 4 Fill out and return survey card Table 4 Dual Fuel Thermostat Quick Reference THERMOSTAT OUTPUTS Outdoor Unit Set DIP Switch D 24v Hot Comm...

Page 8: ... notes 1 2 3 4 and 9 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 5 Two Stage Furnace with 2 Speed Heat Pump A98563 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT TWO STAGE FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R Y Y2 C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC HOT 24 VAC COM N A RVS SENSI...

Page 9: ...GS ON A B C D OFF OFF OFF OFF FURNACE BOARD O Y1 VARIABLE SPEED 80 NON CONDENSING FURNACE Fig 9 Variable Speed Furnace with 2 Speed Heat Pump A98446 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT VARIABLE SPEED CONDENSING FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC ...

Page 10: ...ot select the FURNACE INTERFACE or BALANCE POINT option on the 2 speed heat pump control board This is controlled internally by the Dual Fuel Thermostat 7 As an option lock the furnace into low fire operation and let Y1 W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 8 Furnace must control its own second stage heat operation via furnace control a...

Page 11: ...imum brownout level all outputs are turned off and the display indicates E2 If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read 2 dashes E6 If defrost timer continues for longer than 15 minutes E6 will...

Page 12: ...ctory default 2 3 Fahrenheit or Celsius F or C factory default F 4 7 N A 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 10 N A 11 Balance Point Temperature Off or 5 55 F factory default 40 12 N A 13 Room Temperature Offset 5 to 5 factory default 0 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL TIME HEAT COOL TIME HEAT COOL TIME HEAT...

Reviews: