Wiring
For the wiring in the furnace and fan coil wiring

compartments

The incoming power supply wiring and connections for the air
purifier should be routed away from the output duct of the furnace

or fan coil unit, and the incoming power connections for the air

purifier in the furnace or fan coil unit must be properly rated. The
maximum rated current draw for the furnace 120VAC and fan coil

230VAC air purifiers is 0.3 Amps.
The installation involves direct connection to the duct and to a

furnace controller EAC terminal output. The field wiring

connection shall be suitable for a maximum possible rating of
90

_

C of the field wiring terminal box/terminals.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one disconnect

switch. Lock out and tag switch with a suitable warning label.

!

WARNING

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
This unit cannot be powered directly from blower motor

leads. Voltages can exceed 190 VAC (120v motors). Do not

wire directly to blower motor. Wiring to blower motor will

damage power supply and void warranty.

CAUTION

!

1. Ensure power has been removed from the heating and cool-

ing system.

2. Turn the Air Purifier power switch off.

For mounting on furnaces:

1. Route the power conduit from the purifier to a knockout on

the furnace that provides access to the EAC terminals on the

furnace control board. Affix the end of the conduit to the
furnace using the included conduit fitting.

2. Attach the quick connect terminals on the wires exiting the

power conduit assembly to the furnace EAC--1 and EAC--2
spade connections. Attach the ground ring terminal on the

third wire to furnace chassis ground. See Fig. 11 and 12.

NOTE

: The Air Purifier should only be powered when airflow is

present. The furnace control EAC spade connections, shown in
Fig. 12, provide power only when the furnace blower is operating.
Air Purifier models PGAPAXX1625 and PGAPAXX2025 are
designed to be powered from the electronic air cleaner (EAC)
terminals on a furnace electronic control. If EAC terminals are not
available, the Accessory Flow Sensor Kit, model KIT--160--000,
must be purchased for use with the Air Purifier.

120 VAC

INPUT POWER

BLK

WHT

GRN

CHASSIS
GROUND

FURNACE AIR

PURIFIER ASSEMBLY 

LINE 1 IN

(EAC-1)

NEUTRAL IN

(EAC-2)

A11465

Fig. 11 -- Furnace Installation

Sample Furnace Circuit Board

LHT
OFF
DLY

ON

OFF

W2

BL W

EAC-1 TERMINAL

Y1

DHUM

G

C

OM

24V

W

W

1
Y/Y2

R

TEST/TWIN

HUM

1  2  3

PL
T

A

CRDJ

0.5-AMP024 V AC

FUSE 3-AMP

SEC-1

SEC-2

PL1

NEUTRAL-L2

1

EA C-2

BHT/CLR

BHI/LOR

PL3       1

BL WR

COOL

SP ARE-1

SP ARE-2

1-AMP@115 V AC

EA C-1

PR-1

IDR

HSIR

IDM

IHI/L

O

R

PL2

1

HSI     HI    LO

S TAT U

S

C

OD

EL

E

D

EAC-2 TERMINAL

HI HEA

T

LO

 HEA

T

L1

Use terminals to connect the

power cord wires to the furnace

EAC-1 & 2, & ground terminals

A11491

Fig. 12 -- Air Purifier Connection to Furnace

Summary of Contents for PGAPAXX1620

Page 1: ... Underwriters Laboratories Inc A11332 Fig 1 PGAP Unit SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause death personal injury or property damage Consult a qualified installer service agency or your distributor or branch for information or assistance The qualified installer or ag...

Page 2: ... per running ft of expansion should be used on each side of the transition fitting Turning Vanes If the Air Purifier is installed adjacent to a 90_ duct elbow turning vanes should be added inside duct to improve air distribution across the face of the Air Purifier Electrical Power and Flow Sensing The Air Purifier should only be powered when airflow is present The furnace control EAC terminals pro...

Page 3: ...T 2 Ensure airflow direction through the Air Purifier matches the arrows on the face of the Air Purifier cart ridge and those on the label on the front of the cabinet The Air Purifier can be rotated 180_ to accommodate the cabinet orientation 3 The location of the Air Purifier should be readily accessible Enough room should be provided for periodic replacement of the Air Purifier cartridges ELECTR...

Page 4: ...dle latch at the bottom A11333 Fig 3 Air Purifier Cabinet Orientation Downflow 14 Furnace with Top Mount Upflow 14 Furnace with Bottom Mount Horizontal 14 Furnace with Side Mount Plenum Box Upflow Furnace with Plenum Box Horizontal 24 Furnace Downflow 24 Furnace with Top Mount Upflow 24 Furnace On Stand with Bottom Mount Upflow Furnace A11331 Fig 4 Air Purifier Cabinet Orientation with Transition ...

Page 5: ...When setting furnace on cabinet do not drop it into place Position the furnace correctly on the cabinet to prevent a corner from slipping down and damaging the cabinet or its components CAUTION 1 Turn off power to the heating and cooling system 2 Remove the existing furnace filter and discard Excessive system static may result if the Air Purifier is used with other filtration devices 3 Remove the ...

Page 6: ... flange of the purifier adjacent to the incoming power wir ing slide off the wiring cover as illustrated in Fig 9 The wiring cover must be reinstalled prior to operating the puri fier 8 Seal seams with tape or caulking after the Air Purifier cabi net has been secured Special consideration must be given when applying the 2025 Air Purifier to a 24 1 2 inch 622 mm wide furnace 1 Prepare transition fo...

Page 7: ...ng on furnaces 1 Route the power conduit from the purifier to a knockout on the furnace that provides access to the EAC terminals on the furnace control board Affix the end of the conduit to the furnace using the included conduit fitting 2 Attach the quick connect terminals on the wires exiting the power conduit assembly to the furnace EAC 1 and EAC 2 spade connections Attach the ground ring termi...

Page 8: ...lack primary wires to their respective transformer terminals on the piggyback terminals Attach the ground ring terminal on the third wire to fan coil air handler chassis ground See Figures 13 and 14 NOTE Power connections are to be made inside the fan coil wiring compartment per local electrical codes and the two in line fuses that are provided with the air purifier must be installed in the fan co...

Page 9: ...e purifier and then snap the Carrier or Bryant logo into place with the text in upright po sition See Fig 18 5 Affix the Captures Kills label to the front of the purifi er door as desired A11497 Fig 18 Attach Logo Checking Air Purifier Operation ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main...

Page 10: ...lace the Air Purifier cartridge complete the following steps Turn the heating and cooling system power off ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be more than one disconnect switch Lock out and tag switch with a suitable warning label WARNING NOTE Use of any...

Page 11: ...the Air Purifier Additionally care must be taken when handling the FEM due to the sharp points on the ionizer 5 Slide in enhancement module 6 Replace the Air Purifier door 7 Turn the Air Purifier switch to the on position 8 Turn heating and cooling system power on TROUBLESHOOTING SAFETY HAZARD Failure to follow this caution may result in personal injury or equipment damage The following instructio...

Page 12: ...s undamaged and properly installed on purifier cabinet Damaged or disconnected incoming power wiring Call for service ON continuously Air purifier on Normal operation when airflow is present FLASHING 1 flash every 4 seconds Standby Mode Normal operation when airflow is not present for models with flow sensor Ions detected in airflow due to miss ing replaceable filter element Place filter in air pu...

Page 13: ... Module FEM Clean service air purifier unit Damaged Filter Enhancement Module FEM Replace the filter enhancement module 5 FLASHES Over current fault Excessively dirty Damaged Filter Enhancement Module FEM and or filter Clean service air purifier unit Wet Damaged Filter Enhancement Module FEM and or filter Call service to locate and eliminate the source of water in the air purifier Verify that the ...

Page 14: ...ment Module FEM KIT 140 000 KIT 141 000 KIT 142 000 KIT 143 000 KIT 144 000 Front Door including Power Supply KIT 150 000 KIT 151 000 KIT 150 000 KIT 151 000 KIT 152 000 Flow Sensor KIT 160 000 Included as standard with Models PGAPAXX1620 PGAPAXX2020 and PGAPAXX2420 Flow Sensor Bypass KIT 161 000 Included as standard with Models PGAPAXX1625 and PGAPAXX2025 Front Screen Accessory KIT 170 000 KIT 17...

Page 15: ...15 ...

Page 16: ...C BDP D 7310 W Morris St D Indianapolis IN 46231 Edition Date 09 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM PGAP 01 Replaces NEW ...

Reviews: