Accessory usage guideline

 

* For Tubing line sets greater than 50 ft and/or 20 ft vertical differential, refer to Application Guideline and Service Manual—Air Conditioners and 

Heat Pumps Using Puron® Refrigerant.

† Only when low-pressure switch is used.
‡ Required for low-ambient controller (full modulation feature) and MotorMaster® Control only.

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

1.

Ball-Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. 

Usage Guideline:

Required on all units when low-ambient controller (full modulation feature) or MotorMaster®—Low-Ambient Controller is installed.

2.

Coastal Filter 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.

3.

Compressor Start Assist – Capacitor and Relay

Start capacitor and relay gives a "hard" boost to compressor motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the following applications: 

Long line
Low ambient
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for scroll compressors in the following applications:

Long line
Low ambient

Suggested for all compressors in areas with a history of low voltage problems.

4.

Compressor Start Assist — PTC Type

Solid state electrical device which gives a "soft" boost to the reciprocating compressor at each start-up.

Usage Guideline:

Suggested in installations with marginal power supply.

5.

Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on
restart and minimizes the chance of liquid slugging. 

Usage Guideline:

Required in low ambient applications.
Required in long line applications.
Suggested in all commercial applications.

6.

Evaporator Freeze Thermostat

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7.

Liquid-Line Solenoid Valve (LLS)  

This device serves two purposes. It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation.
It maintains a column of refrigerant liquid ready for action at next compressor operation cycle. It also provides system protection against off-cycle refrigerant
migration. 

Note:

 

When LLS is used with reciprocating compressors, Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required in air conditioner long line applications with a piston indoor metering device to prevent off cycle refrigerant migration. A hard shut 
off TXV can be used instead of an LLS in single flow air conditioner applications. See Long Line Application Guideline.

8.

MotorMaster®—Low-Ambient Controller

A fan-speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temper-
ature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F (37.8°C
± –12°C).

Usage Guideline:

A MotorMaster®—Low Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 
Suggested for all commercial applications.

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

MotorMaster® Low-Ambient Controller

or Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

Summary of Contents for Performance 12

Page 1: ...en Puron refrigerant is in service in thousands of systems providing highly reliable environmentally sound performance For specific R 22 phase out information see your Carrier distributor Carrier s Infinity Controls These industry leading controls when installed with Carrier s Ideal Humidity variable speed furnaces or fan coils provide the homeowner with unparalleled control of temperature humidit...

Page 2: ...essor to eliminate sound transmission to the rest of the system Application Versatility Carrier s systems utilizing Puron refrigerant have the same application guidelines as other systems Applications which include long line sets 50 to 175 ft or applications which require the system to operate at low outdoor temperatures below 55 F 12 8 C are approved under Carrier s standard guidelines Carrier Co...

Page 3: ... with Ring Charge Lb 5 22 5 20 5 19 5 43 5 43 5 75 8 00 COND FAN Propeller Type Direct Drive Air Discharge Vertical Air Qty CFM 1700 2000 2400 2400 2800 2800 3300 Motor HP 1 12 1 10 1 8 1 8 1 5 1 5 1 4 Motor RPM 1100 1100 825 825 825 825 1100 COND COIL Copper Tube Aluminum Plate Fin Face Area Sq ft 10 9 10 9 12 2 12 2 12 2 12 2 18 2 Fins per In 25 25 25 25 25 25 25 Rows 1 1 1 1 1 1 1 Circuits 2 2 ...

Page 4: ...4 33 060 THERMOSTAT SUBBASE PKG DESCRIPTION TSTATCCPRH01 B Thermidistat Control Non Programmable Programmable Thermostat with Humidity Control TSTATCCPAC01 B Thermostat Auto Changeover 7 Day Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCNAC01 B Thermostat Auto Changeover Non Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCSAC01 Thermostat Manual Changeover 5 2 Day Programmable F C 1 Stage He...

Page 5: ...rature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Required when low ambient kit has been added 7 Liquid Line Solenoid Valve LLS This device serves two purposes It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation It maintains a column of refrigerant liquid ready fo...

Page 6: ... 0 64 0 60 5 53 0 060 33 78 61 5 69 5 71 0 71 5 69 0 66 0 59 5 9 Outdoor Air Temperature Sensor Designed for use with Carrier Thermostats listed in this publication This device enables the thermostat to display the outdoor temperature This device also is required to enable special thermostat features such as auxiliary heat lock out Usage Guideline Suggested for all Carrier thermostats listed in th...

Page 7: ...on is the 13th position of the unit model number 3 Center of gravity 4 NOTES A97084 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 33 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 1 2 14 15 1 2 2 3 8 20 x 27 024 34 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 1 2 14 15 1 2 2 3 8 20 x 27 030 33 ...

Page 8: ...RNACE CC5A CD5AW024 17 500 TDR 13 00 13 00 11 75 CE3AA024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE CC5A CD5AW024 17 500 TDR 13 00 13 00 11 85 CE3AA024 17 500 TDR 13 00 13 00 11 80 CK3BA024 17 500 TDR 13 00 13 00 12 00 CK5A CK5BA018 17 200 TDR 13 00 13 00 11 75 CK5A CK5BA024 17 500 TDR 13...

Page 9: ...W030 22 600 TDR 13 00 13 00 11 70 CE3AA024 22 200 TDR 13 00 13 00 11 50 CE3AA030 22 600 TDR 13 00 13 00 11 75 CK3BA024 22 200 TDR 13 00 13 00 11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13 00 13 00 11 80 CK5PW024 22 200 TDR TXV 13 00 11 60 CK5PW030 22 600 TDR TXV 13 00 11 75 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CE3AA024 22...

Page 10: ... NONE 12 00 12 00 10 55 CK3BA030 28 000 NONE 11 70 11 70 10 35 CK3BA036 29 000 NONE 12 00 12 00 10 65 CK5A CK5BA030 28 000 NONE 11 70 11 70 10 35 CK5A CK5BT036 29 000 NONE 12 00 12 00 10 65 CK5A CK5BW030 28 000 NONE 11 70 11 70 10 35 CK5A CK5BW036 29 000 NONE 12 00 12 00 10 65 CK5PA030 28 000 TXV 11 70 10 35 CK5PA036 29 000 TXV 12 00 10 65 CK5PT036 29 000 TXV 12 00 10 65 CK5PW030 28 000 TXV 11 70 ...

Page 11: ...6 28 800 TDR TXV 13 00 11 60 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CC5A CD5AW036 28 600 TDR 13 00 13 00 11 60 CE3AA030 27 800 TDR 12 50 12 50 11 30 CE3AA036 28 200 TDR 13 00 13 00 11 45 CK5A CK5BW036 28 800 TDR 13 00 13 00 11 65 CK5PW036 28 800 TDR TXV 13 00 11 65 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AW036 28 200 TDR 13 00 13 00 11 65 CE3AA030 27 800 TDR 12 50 12 50 11 35 CE...

Page 12: ...0 11 00 FE4ANF003 34 200 TDR TXV 13 00 11 50 FE4ANF005 35 000 TDR TXV 13 70 11 95 FE4ANB006 35 800 TDR TXV 14 00 12 25 FG3AAA036 34 000 NONE 11 50 11 50 10 35 FK4 C D NB006 35 400 TDR TXV 14 00 12 25 FK4 C D NF001 33 800 TDR TXV 12 50 10 95 FK4 C D NF002 34 000 TDR TXV 12 50 11 05 FK4 C D NF003 34 200 TDR TXV 13 00 11 50 FK4 C D NF005 35 000 TDR TXV 13 50 11 95 FV4 A B NB006 35 800 TDR TXV 14 00 1...

Page 13: ... 11 35 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 TDR 13 00 13 00 11 55 CC5A CD5AW036 34 600 TDR 13 00 13 00 11 35 CC5A CD5AW042 34 400 TDR 13 00 13 00 11 50 CE3AA036 34 200 TDR 12 50 12 50 11 25 CE3AA042 34 600 TDR 13 00 13 00 11 55 CK3BA042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BA042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BT042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BW036 34 60...

Page 14: ... 11 50 9 90 FC4 B C N F B 048 39 500 TDR TXV 11 70 10 05 FC4 B C NB054 40 500 TDR TXV 12 20 10 65 FE4ANB006 40 500 TDR TXV 13 70 11 60 FE4ANF003 38 500 TDR TXV 12 70 10 85 FE4ANF005 40 500 TDR TXV 13 20 11 30 FG3AAA048 40 000 NONE 11 70 11 70 10 20 FK4 C D NB006 40 500 TDR TXV 13 50 11 60 FK4 C D NF003 38 500 TDR TXV 12 50 10 85 FK4 C D NF005 40 000 TDR TXV 13 00 11 30 FV4 A B NB006 40 500 TDR TXV...

Page 15: ...8 39 500 TDR 12 50 12 50 11 15 CE3AA042 39 000 TDR 12 50 12 50 11 05 CE3AA048 39 500 TDR 12 50 12 50 11 10 CK3BA042 39 000 TDR 12 50 12 50 11 00 CK3BA048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BA042 39 000 TDR 12 50 12 50 11 00 CK5A CK5BA048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BT042 39 000 TDR 12 50 12 50 11 00 CK5A CK5BT048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 15 CK...

Page 16: ...CK5PA060 46 000 TXV 12 00 10 40 CK5PT048 45 000 TXV 11 70 10 20 CK5PT060 46 000 TXV 12 00 10 40 CK5PW048 45 000 TXV 11 70 10 20 CK5PX060 46 500 TXV 12 00 10 50 F A B 4 A B N F B C 048 45 000 TDR 11 70 11 70 10 10 F A B 4 A B N F B C 060 46 000 TDR 11 70 11 70 10 10 FB4 A B NB070 46 500 TDR 12 00 12 00 10 45 FC4 B C N F B 048 44 500 TDR TXV 11 50 10 00 FC4 B C N F B 060 45 000 TDR TXV 11 50 9 95 FC...

Page 17: ...0 13 00 11 15 CD5AA048 44 500 TDR 12 50 12 50 10 90 CE3AA048 44 500 TDR 12 00 12 00 10 85 CE3AA060 45 000 TDR 12 50 12 50 11 15 CK3BA048 44 500 TDR 12 00 12 00 10 85 CK3BA060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BA048 44 500 TDR 12 00 12 00 10 85 CK5A CK5BA060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BT048 44 500 TDR 12 00 12 00 10 85 CK5A CK5BT060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BW048 44 500 TDR...

Page 18: ...0 56 000 TDR TXV 12 00 10 15 COILS 58CV A X 110 20 VARIABLE SPEED FURNACE CC5A CD5AA060 56 000 TDR 11 50 11 50 10 00 CD5PX060 58 500 TDR TXV 12 00 10 35 CE3AA060 58 000 TDR 12 00 12 00 10 35 CK3BA060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BA060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BT060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BX060 58 000 TDR 12 00 12 00 10 50 CK5PA060 58 000 TDR TXV 12 00 10 35 CK5PT0...

Page 19: ...e Delay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for central air conditioners Ratings for other combinations are determined under DOE computer simulation procedures 3 Determine...

Page 20: ...9 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19 01 14 46 1 50 18 03 14 23 1 67 16 84 13 82 1 87 15 67 13 36 2 06 14 45 12 88 2 27 63 18 47 14 29 1 34 17 56 14 08 1 49 16 44 13 62 1 66 15 36 13 17 1 83 14 23 12 70 2 02 13 04 12 19 2 23 62 18 40 17 89 1 34 17 56 17 56 1 49 16 67 16 67 1 67 15 80 15 80 1 85 14 90 14 90 2 04 13 97 13 97 2 26 57 18 34 18 34 1 33 17 56 17 56 ...

Page 21: ...8 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 0 99 1 01 CK5A CK5BA 024 0 97 0 89 030 1 00 1 01 030 0 98 0 90 CC5A CD5AW 024 0 99 1 01 CK5A CK5BW 024 0 97 0 89 030 1 00 1 01 030 0 98 0 89 CE3AA 024 0 99 1 00 CK5PA 024 0 97 0 89 030 1 00 1 ...

Page 22: ... 23 62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 72 26 66 14 25 1 73 26 38 14 46 1 96 25 42 14 30 2 21 24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Co...

Page 23: ... 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 1 00 CE3AA 030 0 97 0 92 036 1 00 1 00 036 0 97 0 91 CC5A CD5AW 030 0 97 1 00 CK3BA 030 0 96 0 92 036 1 00 1 00 036 0...

Page 24: ... 2 27 28 6 23 0 2 49 26 2 22 0 2 73 23 7 21 0 3 00 22 2 20 4 3 32 20 1 19 4 3 67 62 30 3 30 0 2 26 29 0 29 0 2 49 27 0 27 0 2 74 25 7 25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capaci...

Page 25: ...liers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CK5A CK5BE 042 0 99 0 92 042 1 00 1 00 CK5A CK5BT 036 0 99 0 94 CC5A CD5AW 036 1 00 1 00 CK5PA 036 0 99 0 94 042 0 99 1 00 CK5PE 042 0 99 0 93 CE3AA 036 0 99 1 00 CK5PT 036 0 99 0 94 042 1 00 1 00 COILS 58CV A X 090 16 VARIA...

Page 26: ...53 57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CK3BA 036 0 99 0 94 CC5A CD5AA 042 0 99 0 91 042 0 99 0 93 CC5A CD5AW 036 0 99 0 92 CK5A CK5BA 036 0 9...

Page 27: ...1 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AC 048 0 99 1 00 CE3AA 042 0 98 0 92 CC5A CD5AW 042 0 99 1 00 048 0 99 0 92 048 1 00 1 00 CK3BA 042 0 98 0 92 CD5AA 048 1 00 1 00 048 0 99 0 92 CE...

Page 28: ... 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CE3AA 042 0 98 0 91 COILS 58MVP060 14 VARIABLE SPEED FURNACE 048 0 99 0 92 CK3BA 042 0 98 0 94 CK3BA 042 0 98 0 91 CK5A CK5BE 042 0 99 0 96 048 0 99 0 91 CK5PE 042 0 99 0 96 CK5A CK5BA 042 0 9...

Page 29: ...3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 1 00 CE3AA 048 0 97 0 95 CC5A CD5AC 048 0 96 0 99 060 0 98 0 93 CC5A CD5AW 048 0 98 1 00 CK3BA 048 0 97 0 95 060 1 01 1 02 CK5A CK5BA 048 0 97 0 95 CD5AA 048 0 98 1 0...

Page 30: ...94 62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BT 048 0 97 0 94 CK5A CK5BA 048 0 97 0 97 060 ...

Page 31: ...3 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 54 7 54 7 4 39 51 8 51 8 4 88 50 2 50 2 5 45 48 5 48 5 6 10 45 6 45 6 6 79 41 6 41 6 7 55 2000 72 67 6 34 3 4 68 65 3 33 7 5 21 62 4 32 9 5 79 58 6 31 6 6 42 55 0 30 5 7 13 50 9 29 2 7 92 67 63 6 45 4 4 61 60 7 4...

Page 32: ... 52 1 73 1 94 2 15 2 37 40 TCG 29 5 24 9 23 2 21 3 19 4 17 3 15 0 12 4 SDT 74 5 83 7 92 8 102 0 111 2 120 4 129 3 138 2 KW 1 00 1 18 1 36 1 55 1 77 2 0 2 23 2 46 45 TCG 32 3 29 0 26 0 23 9 22 0 19 9 17 6 15 0 SDT 76 1 85 3 94 5 103 7 112 9 121 9 130 8 139 6 KW 1 02 1 20 1 39 1 60 1 82 2 05 2 29 2 54 50 TCG 37 7 35 9 30 0 27 2 24 8 22 6 20 3 17 9 SDT 77 7 86 7 95 9 105 1 114 2 123 2 132 1 140 8 KW ...

Page 33: ...142 0 4 61 40 TCG SDT KW 44 7 78 4 2 01 42 3 87 7 2 28 39 9 97 0 2 58 37 5 107 0 2 92 35 0 116 0 3 29 32 5 125 0 3 70 29 9 134 0 4 15 27 1 144 0 4 65 45 TCG SDT KW 48 7 80 3 2 06 46 1 89 4 2 32 43 6 98 7 2 62 40 9 108 0 2 96 38 2 118 0 3 34 35 5 127 0 3 75 32 6 136 0 4 20 29 5 145 0 4 69 50 TCG SDT KW 52 9 82 3 2 11 50 2 91 3 2 37 47 4 101 0 2 67 44 5 110 0 3 01 41 6 119 0 3 39 38 6 128 0 3 80 35 ...

Page 34: ...ided 9 Do not apply capillary tube indoor coils to these units 10 Factory supplied filter drier must be installed This must be replaced each time the refrigeration system is opened for service 11 Do not deviate from factory supplied TXV s and Liquid Line Solenoids Condenser only ratings continued ARI listing applies only to systems shown in Combination Ratings table KW Outdoor Unit Kilowatts Only ...

Page 35: ...35 ...

Page 36: ...pletion potential R 410A is approved under the EPA s Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 38TZA 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclose...

Reviews: