background image

 

2

and maintaining ease of coil cleaning. 
Finally, all screws on cabinet exterior are 
ceramic coated for a long-lasting, rust-
resistant, quality appearance.

 

High Efficiency Performance

 

— Is 

delivered through a combination of 
features including Carrier’s Puron 
refrigerant, unique scroll compressor, and 
advanced heat transfer surfaces. Efficiency 
ratings are 12 SEER (Seasonal Energy 
Efficiency Ratio) with enhanced ratings of 
up to 14 SEER. Sophisticated heat transfer 
surfaces utilized in Carrier’s 38TZA 
design allow heat to easily be transferred 
to the outdoor air and requires less energy. 
The unique scroll compressor found in the 
38TZA design performs quietly and adds 
to the overall efficiency of the system. For 
improved serviceability, all models are 
equipped with a compressor terminal plug. 
Finally, Carrier’s Puron refrigerant 
operates more efficiently than ordinary 
R-22 refrigerant found in other systems. 
The efficiency levels provided by the 
38TZA provide end users with lower costs 
of operation than traditional air 
conditioning systems.

 

Assured Future Service

 

— By utilizing 

the environmentally sound refrigerant, 
Puron, 38TZA models will remain 
serviceable well into the future. The Clean 
Air Act of 1990 has placed a cap on 
production of most other refrigerants 
which has scheduled reductions 
beginning in 2004. The resulting cap in 
production ultimately results in a 
complete ban on many other refrigerants 
in new equipment by the year 2010. These 
changes, required by federal law, mean 
the supply of other refrigerants may be 
limited in the near future making Puron 
the correct choice when considering long 
term serviceability.

 

Highly Reliable Performance

 

— Is 

delivered through the superior design of 
the system and componentry. The 

reliability of models with Puron 
refrigerant have been proven to provide 
the lowest incidence of warranty service 
of any product in the Carrier family in its 
last 3 years of service. Long term 
reliability is assured through the use of 
both high and low pressure switches 
which will not allow the system to operate 
in the event of a significant change in 
operating pressure. In doing this, the 
system is protected from damage if an 
unusual condition arises. Finally, Carrier 
includes a special liquid line filter drier 
designed to trap moisture and 
contaminants which could otherwise 
shorten the life of the system.

 

Carrier’s Silencer System

 

Is one of the most sought after features 
of the 38TZA family. Extremely low 
operating sound is the result of special 
attention to the air moving through the 
outdoor unit, a specially designed sound 
enclosure surrounding the compressor, 
and an unique laminated plate beneath the 
compressor to eliminate sound 
transmission to the rest of the system.

 

Application Versatility

 

— Carrier’s 

systems utilizing Puron refrigerant have 
the same application guidelines as other 
systems. Applications which include long 
line sets (50 to 175 ft) or applications 
which require the system to operate at low 
outdoor temperatures (below 55°F, 
12.8°C) are approved under Carrier’s 
standard guidelines.

 

Carrier Coils and Fan Coils to 
Complete the System

 

— Carrier 

specially designs both the outdoor 
product and indoor coil products to 
operate with assured reliability and 
performance. A wide range of indoor coil 
options are listed in the ratings section 
of this publication.

 

Special Protective Devices

 

— High 

and low pressure switches and internal 
protection in the compressor including 

temperature and current sensing 
overloads prevent operation under 
potentially damaging circumstances. 
A special liquid line filter drier designed 
to trap nearly 4 times the volume of 
contaminants of standard driers provides 
superior protection from moisture trapped 
in the system.

 

Electrical Range

 

— 208/230v, single 

phase.

 

Wide Range of Sizes

 

— Available in 

seven sizes: 1-1/2, 2, 2-1/2, 3, 3-1/2, 4, 
and 5 tons.

 

Totally Enclosed Fan Motor

 

Protected from adverse weather 
conditions.

 

Unit Design

 

— Enhanced copper and 

aluminum heat transfer surfaces with 
vertical air discharge to direct air up and 
away from the area.

 

External Service Valves

 

— Both 

service valves are back seating type valves 
which are externally located. These 
unique valves allow service technicians to 
evacuate or charge the system in less time 
than standard service valves.

 

Easy Serviceability

 

— Easy removal 

panels provide access to both electrical 
and refrigerant carrying components 
simplifying installation and service.

 

Agency Approvals

 

— 38TZA models 

are listed with UL (U.S. and Canada), 
ARI, and CEC. Special endorsements 
have also been awarded these products by 
Energy Star® which recognizes energy 
efficient products.

 

Limited Warranty

 

— A standard five 

year warranty on parts with 10 years on 
the compressor. Optional warranties are 
available through your Carrier distributor.

 

 

M

A

N

U

F

A

C

T

U

R

E

R

CE

RT

IFIED

TO ARI

AS

C

O

M

P

L

Y

IN

G
W
IT

H

A

RI

STANDARD

21

0

U

N

IT

A

R

Y

AIR

CO

N

D

IT

IO

N

IN

G

EQUIPMENT

 

CERTIFICATION APPLIES ONLY WHEN THE
COMPLETE SYSTEM IS LISTED WITH ARI.

REGISTERED QUALITY SYSTEM

As an ENERGY STAR® partner, Carrier Corporation has 
determined that this product meets the ENERGY STAR® 

guidelines for energy efficiency.

 

 

Model number nomenclature

 

38TZA

024

3

3

1

12 SEER Split-System
Air Conditioner

Packaging

Series

Nominal Capacity

 

018 — 18,000 Btuh

042 — 42,000 Btuh

024 — 24,000 Btuh

048 — 48,000 Btuh

030 — 30,000 Btuh

060 — 60,000 Btuh

036 — 36,000 Btuh

 

Electrical

 

3 — 208/230-1

Refer to the combination ratings in the Product Data Digest for system combinations that meet Energy Star® efficiency standards.

 

*

 

*

Summary of Contents for Performance 12

Page 1: ...en Puron refrigerant is in service in thousands of systems providing highly reliable environmentally sound performance For specific R 22 phase out information see your Carrier distributor Carrier s Infinity Controls These industry leading controls when installed with Carrier s Ideal Humidity variable speed furnaces or fan coils provide the homeowner with unparalleled control of temperature humidit...

Page 2: ...essor to eliminate sound transmission to the rest of the system Application Versatility Carrier s systems utilizing Puron refrigerant have the same application guidelines as other systems Applications which include long line sets 50 to 175 ft or applications which require the system to operate at low outdoor temperatures below 55 F 12 8 C are approved under Carrier s standard guidelines Carrier Co...

Page 3: ... with Ring Charge Lb 5 22 5 20 5 19 5 43 5 43 5 75 8 00 COND FAN Propeller Type Direct Drive Air Discharge Vertical Air Qty CFM 1700 2000 2400 2400 2800 2800 3300 Motor HP 1 12 1 10 1 8 1 8 1 5 1 5 1 4 Motor RPM 1100 1100 825 825 825 825 1100 COND COIL Copper Tube Aluminum Plate Fin Face Area Sq ft 10 9 10 9 12 2 12 2 12 2 12 2 18 2 Fins per In 25 25 25 25 25 25 25 Rows 1 1 1 1 1 1 1 Circuits 2 2 ...

Page 4: ...4 33 060 THERMOSTAT SUBBASE PKG DESCRIPTION TSTATCCPRH01 B Thermidistat Control Non Programmable Programmable Thermostat with Humidity Control TSTATCCPAC01 B Thermostat Auto Changeover 7 Day Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCNAC01 B Thermostat Auto Changeover Non Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCSAC01 Thermostat Manual Changeover 5 2 Day Programmable F C 1 Stage He...

Page 5: ...rature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Required when low ambient kit has been added 7 Liquid Line Solenoid Valve LLS This device serves two purposes It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation It maintains a column of refrigerant liquid ready fo...

Page 6: ... 0 64 0 60 5 53 0 060 33 78 61 5 69 5 71 0 71 5 69 0 66 0 59 5 9 Outdoor Air Temperature Sensor Designed for use with Carrier Thermostats listed in this publication This device enables the thermostat to display the outdoor temperature This device also is required to enable special thermostat features such as auxiliary heat lock out Usage Guideline Suggested for all Carrier thermostats listed in th...

Page 7: ...on is the 13th position of the unit model number 3 Center of gravity 4 NOTES A97084 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 018 33 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 1 2 14 15 1 2 2 3 8 20 x 27 024 34 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 1 2 14 15 1 2 2 3 8 20 x 27 030 33 ...

Page 8: ...RNACE CC5A CD5AW024 17 500 TDR 13 00 13 00 11 75 CE3AA024 17 500 TDR 13 00 13 00 11 80 CK5A CK5BW024 17 500 TDR 13 00 13 00 11 90 CK5PW024 17 500 TDR TXV 13 00 11 90 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE CC5A CD5AW024 17 500 TDR 13 00 13 00 11 85 CE3AA024 17 500 TDR 13 00 13 00 11 80 CK3BA024 17 500 TDR 13 00 13 00 12 00 CK5A CK5BA018 17 200 TDR 13 00 13 00 11 75 CK5A CK5BA024 17 500 TDR 13...

Page 9: ...W030 22 600 TDR 13 00 13 00 11 70 CE3AA024 22 200 TDR 13 00 13 00 11 50 CE3AA030 22 600 TDR 13 00 13 00 11 75 CK3BA024 22 200 TDR 13 00 13 00 11 80 CK3BA030 22 600 TDR 13 00 13 00 11 85 CK5A CK5BW024 22 200 TDR 13 00 13 00 11 65 CK5A CK5BW030 22 600 TDR 13 00 13 00 11 80 CK5PW024 22 200 TDR TXV 13 00 11 60 CK5PW030 22 600 TDR TXV 13 00 11 75 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CE3AA024 22...

Page 10: ... NONE 12 00 12 00 10 55 CK3BA030 28 000 NONE 11 70 11 70 10 35 CK3BA036 29 000 NONE 12 00 12 00 10 65 CK5A CK5BA030 28 000 NONE 11 70 11 70 10 35 CK5A CK5BT036 29 000 NONE 12 00 12 00 10 65 CK5A CK5BW030 28 000 NONE 11 70 11 70 10 35 CK5A CK5BW036 29 000 NONE 12 00 12 00 10 65 CK5PA030 28 000 TXV 11 70 10 35 CK5PA036 29 000 TXV 12 00 10 65 CK5PT036 29 000 TXV 12 00 10 65 CK5PW030 28 000 TXV 11 70 ...

Page 11: ...6 28 800 TDR TXV 13 00 11 60 COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CC5A CD5AW036 28 600 TDR 13 00 13 00 11 60 CE3AA030 27 800 TDR 12 50 12 50 11 30 CE3AA036 28 200 TDR 13 00 13 00 11 45 CK5A CK5BW036 28 800 TDR 13 00 13 00 11 65 CK5PW036 28 800 TDR TXV 13 00 11 65 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AW036 28 200 TDR 13 00 13 00 11 65 CE3AA030 27 800 TDR 12 50 12 50 11 35 CE...

Page 12: ...0 11 00 FE4ANF003 34 200 TDR TXV 13 00 11 50 FE4ANF005 35 000 TDR TXV 13 70 11 95 FE4ANB006 35 800 TDR TXV 14 00 12 25 FG3AAA036 34 000 NONE 11 50 11 50 10 35 FK4 C D NB006 35 400 TDR TXV 14 00 12 25 FK4 C D NF001 33 800 TDR TXV 12 50 10 95 FK4 C D NF002 34 000 TDR TXV 12 50 11 05 FK4 C D NF003 34 200 TDR TXV 13 00 11 50 FK4 C D NF005 35 000 TDR TXV 13 50 11 95 FV4 A B NB006 35 800 TDR TXV 14 00 1...

Page 13: ... 11 35 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 34 600 TDR 13 00 13 00 11 55 CC5A CD5AW036 34 600 TDR 13 00 13 00 11 35 CC5A CD5AW042 34 400 TDR 13 00 13 00 11 50 CE3AA036 34 200 TDR 12 50 12 50 11 25 CE3AA042 34 600 TDR 13 00 13 00 11 55 CK3BA042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BA042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BT042 34 600 TDR 13 00 13 00 11 55 CK5A CK5BW036 34 60...

Page 14: ... 11 50 9 90 FC4 B C N F B 048 39 500 TDR TXV 11 70 10 05 FC4 B C NB054 40 500 TDR TXV 12 20 10 65 FE4ANB006 40 500 TDR TXV 13 70 11 60 FE4ANF003 38 500 TDR TXV 12 70 10 85 FE4ANF005 40 500 TDR TXV 13 20 11 30 FG3AAA048 40 000 NONE 11 70 11 70 10 20 FK4 C D NB006 40 500 TDR TXV 13 50 11 60 FK4 C D NF003 38 500 TDR TXV 12 50 10 85 FK4 C D NF005 40 000 TDR TXV 13 00 11 30 FV4 A B NB006 40 500 TDR TXV...

Page 15: ...8 39 500 TDR 12 50 12 50 11 15 CE3AA042 39 000 TDR 12 50 12 50 11 05 CE3AA048 39 500 TDR 12 50 12 50 11 10 CK3BA042 39 000 TDR 12 50 12 50 11 00 CK3BA048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BA042 39 000 TDR 12 50 12 50 11 00 CK5A CK5BA048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BT042 39 000 TDR 12 50 12 50 11 00 CK5A CK5BT048 39 500 TDR 12 50 12 50 11 15 CK5A CK5BW048 39 500 TDR 13 00 13 00 11 15 CK...

Page 16: ...CK5PA060 46 000 TXV 12 00 10 40 CK5PT048 45 000 TXV 11 70 10 20 CK5PT060 46 000 TXV 12 00 10 40 CK5PW048 45 000 TXV 11 70 10 20 CK5PX060 46 500 TXV 12 00 10 50 F A B 4 A B N F B C 048 45 000 TDR 11 70 11 70 10 10 F A B 4 A B N F B C 060 46 000 TDR 11 70 11 70 10 10 FB4 A B NB070 46 500 TDR 12 00 12 00 10 45 FC4 B C N F B 048 44 500 TDR TXV 11 50 10 00 FC4 B C N F B 060 45 000 TDR TXV 11 50 9 95 FC...

Page 17: ...0 13 00 11 15 CD5AA048 44 500 TDR 12 50 12 50 10 90 CE3AA048 44 500 TDR 12 00 12 00 10 85 CE3AA060 45 000 TDR 12 50 12 50 11 15 CK3BA048 44 500 TDR 12 00 12 00 10 85 CK3BA060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BA048 44 500 TDR 12 00 12 00 10 85 CK5A CK5BA060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BT048 44 500 TDR 12 00 12 00 10 85 CK5A CK5BT060 45 000 TDR 12 50 12 50 11 15 CK5A CK5BW048 44 500 TDR...

Page 18: ...0 56 000 TDR TXV 12 00 10 15 COILS 58CV A X 110 20 VARIABLE SPEED FURNACE CC5A CD5AA060 56 000 TDR 11 50 11 50 10 00 CD5PX060 58 500 TDR TXV 12 00 10 35 CE3AA060 58 000 TDR 12 00 12 00 10 35 CK3BA060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BA060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BT060 58 000 TDR 12 00 12 00 10 35 CK5A CK5BX060 58 000 TDR 12 00 12 00 10 50 CK5PA060 58 000 TDR TXV 12 00 10 35 CK5PT0...

Page 19: ...e Delay Relay TXV Puron Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for central air conditioners Ratings for other combinations are determined under DOE computer simulation procedures 3 Determine...

Page 20: ...9 18 81 10 83 1 88 17 66 10 48 2 08 16 38 10 04 2 30 67 19 30 14 10 1 35 19 01 14 46 1 50 18 03 14 23 1 67 16 84 13 82 1 87 15 67 13 36 2 06 14 45 12 88 2 27 63 18 47 14 29 1 34 17 56 14 08 1 49 16 44 13 62 1 66 15 36 13 17 1 83 14 23 12 70 2 02 13 04 12 19 2 23 62 18 40 17 89 1 34 17 56 17 56 1 49 16 67 16 67 1 67 15 80 15 80 1 85 14 90 14 90 2 04 13 97 13 97 2 26 57 18 34 18 34 1 33 17 56 17 56 ...

Page 21: ...8 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 0 99 1 01 CK5A CK5BA 024 0 97 0 89 030 1 00 1 01 030 0 98 0 90 CC5A CD5AW 024 0 99 1 01 CK5A CK5BW 024 0 97 0 89 030 1 00 1 01 030 0 98 0 89 CE3AA 024 0 99 1 00 CK5PA 024 0 97 0 89 030 1 00 1 ...

Page 22: ... 23 62 1 71 22 93 22 93 1 93 21 79 21 79 2 19 20 57 20 57 2 46 19 32 19 32 2 73 17 99 17 99 3 05 67 25 80 19 11 1 72 24 77 19 02 1 94 23 33 18 61 2 19 21 81 18 07 2 45 20 21 17 48 2 75 18 46 16 79 3 05 72 26 66 14 25 1 73 26 38 14 46 1 96 25 42 14 30 2 21 24 05 13 90 2 48 22 47 13 40 2 76 20 68 12 80 3 07 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Co...

Page 23: ... 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 1 00 CE3AA 030 0 97 0 92 036 1 00 1 00 036 0 97 0 91 CC5A CD5AW 030 0 97 1 00 CK3BA 030 0 96 0 92 036 1 00 1 00 036 0...

Page 24: ... 2 27 28 6 23 0 2 49 26 2 22 0 2 73 23 7 21 0 3 00 22 2 20 4 3 32 20 1 19 4 3 67 62 30 3 30 0 2 26 29 0 29 0 2 49 27 0 27 0 2 74 25 7 25 7 3 03 24 3 24 3 3 36 21 9 21 9 3 71 57 30 2 30 2 2 26 28 6 28 6 2 49 27 0 27 0 2 74 26 1 26 1 3 04 24 6 24 6 3 36 21 9 21 9 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capaci...

Page 25: ...liers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CK5A CK5BE 042 0 99 0 92 042 1 00 1 00 CK5A CK5BT 036 0 99 0 94 CC5A CD5AW 036 1 00 1 00 CK5PA 036 0 99 0 94 042 0 99 1 00 CK5PE 042 0 99 0 93 CE3AA 036 0 99 1 00 CK5PT 036 0 99 0 94 042 1 00 1 00 COILS 58CV A X 090 16 VARIA...

Page 26: ...53 57 36 6 36 6 2 73 35 2 35 2 3 03 33 6 33 6 3 37 31 8 31 8 3 73 29 4 29 4 4 11 26 4 26 4 4 53 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CK3BA 036 0 99 0 94 CC5A CD5AA 042 0 99 0 91 042 0 99 0 93 CC5A CD5AW 036 0 99 0 92 CK5A CK5BA 036 0 9...

Page 27: ...1 1 41 1 3 20 39 6 39 6 3 55 37 4 37 4 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AC 048 0 99 1 00 CE3AA 042 0 98 0 92 CC5A CD5AW 042 0 99 1 00 048 0 99 0 92 048 1 00 1 00 CK3BA 042 0 98 0 92 CD5AA 048 1 00 1 00 048 0 99 0 92 CE...

Page 28: ... 3 92 36 2 36 2 4 36 33 1 33 1 4 82 30 3 30 3 5 34 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CE3AA 042 0 98 0 91 COILS 58MVP060 14 VARIABLE SPEED FURNACE 048 0 99 0 92 CK3BA 042 0 98 0 94 CK3BA 042 0 98 0 91 CK5A CK5BE 042 0 99 0 96 048 0 99 0 91 CK5PE 042 0 99 0 96 CK5A CK5BA 042 0 9...

Page 29: ...3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 1 00 CE3AA 048 0 97 0 95 CC5A CD5AC 048 0 96 0 99 060 0 98 0 93 CC5A CD5AW 048 0 98 1 00 CK3BA 048 0 97 0 95 060 1 01 1 02 CK5A CK5BA 048 0 97 0 95 CD5AA 048 0 98 1 0...

Page 30: ...94 62 48 7 48 6 3 65 46 4 46 4 4 03 44 4 44 4 4 47 42 2 42 2 4 97 38 5 38 5 5 49 34 4 34 4 6 07 57 48 5 48 5 3 64 46 4 46 4 4 03 44 3 44 3 4 47 42 2 42 2 4 97 39 6 39 6 5 51 35 2 35 2 6 09 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BT 048 0 97 0 94 CK5A CK5BA 048 0 97 0 97 060 ...

Page 31: ...3 58 6 42 9 4 46 55 0 41 3 4 94 51 2 39 7 5 47 49 2 38 8 6 11 44 4 36 8 6 76 39 2 34 7 7 47 62 57 5 53 4 4 44 54 0 51 7 4 92 50 6 50 0 5 46 48 8 48 8 6 10 45 6 45 6 6 79 41 6 41 6 7 55 57 54 7 54 7 4 39 51 8 51 8 4 88 50 2 50 2 5 45 48 5 48 5 6 10 45 6 45 6 6 79 41 6 41 6 7 55 2000 72 67 6 34 3 4 68 65 3 33 7 5 21 62 4 32 9 5 79 58 6 31 6 6 42 55 0 30 5 7 13 50 9 29 2 7 92 67 63 6 45 4 4 61 60 7 4...

Page 32: ... 52 1 73 1 94 2 15 2 37 40 TCG 29 5 24 9 23 2 21 3 19 4 17 3 15 0 12 4 SDT 74 5 83 7 92 8 102 0 111 2 120 4 129 3 138 2 KW 1 00 1 18 1 36 1 55 1 77 2 0 2 23 2 46 45 TCG 32 3 29 0 26 0 23 9 22 0 19 9 17 6 15 0 SDT 76 1 85 3 94 5 103 7 112 9 121 9 130 8 139 6 KW 1 02 1 20 1 39 1 60 1 82 2 05 2 29 2 54 50 TCG 37 7 35 9 30 0 27 2 24 8 22 6 20 3 17 9 SDT 77 7 86 7 95 9 105 1 114 2 123 2 132 1 140 8 KW ...

Page 33: ...142 0 4 61 40 TCG SDT KW 44 7 78 4 2 01 42 3 87 7 2 28 39 9 97 0 2 58 37 5 107 0 2 92 35 0 116 0 3 29 32 5 125 0 3 70 29 9 134 0 4 15 27 1 144 0 4 65 45 TCG SDT KW 48 7 80 3 2 06 46 1 89 4 2 32 43 6 98 7 2 62 40 9 108 0 2 96 38 2 118 0 3 34 35 5 127 0 3 75 32 6 136 0 4 20 29 5 145 0 4 69 50 TCG SDT KW 52 9 82 3 2 11 50 2 91 3 2 37 47 4 101 0 2 67 44 5 110 0 3 01 41 6 119 0 3 39 38 6 128 0 3 80 35 ...

Page 34: ...ided 9 Do not apply capillary tube indoor coils to these units 10 Factory supplied filter drier must be installed This must be replaced each time the refrigeration system is opened for service 11 Do not deviate from factory supplied TXV s and Liquid Line Solenoids Condenser only ratings continued ARI listing applies only to systems shown in Combination Ratings table KW Outdoor Unit Kilowatts Only ...

Page 35: ...35 ...

Page 36: ...pletion potential R 410A is approved under the EPA s Significant New Alternatives Program SNAP Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 38TZA 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclose...

Reviews: