34
System design summary
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature is 125°F (51.7°C).
4. For reliable operation, unit should be level in all horizontal planes.
5. Maximum elevation of indoor coil above or below base of outdoor unit without additional consideration is: Indoor coil above = 20 ft, indoor
coil below = 20 ft. Consult Application Guideline and Service Manual see—Air Conditioners and Heat Pumps Using Puron® Refrigerant if
elevations are exceeded.
6. For interconnecting refrigerant tube lengths greater than 50 ft and/or 20 ft vertical differential, consult Residential Split System Application
Guideline and Service Manual available from equipment distributor.
7. If any refrigerant tubing is buried, provide a 6 in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may
be buried without further consideration. Do not bury lines longer than 36 in.
8. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
9. Do not apply capillary tube indoor coils to these units.
10. Factory-supplied filter drier must be installed. This must be replaced each time the refrigeration system is opened for service.
11. Do not deviate from factory supplied TXV’s and Liquid-Line Solenoids.
Condenser only ratings* continued
* ARI listing applies only to systems shown in Combination Ratings table.
KW
— Outdoor Unit Kilowatts Only
SDT
— Saturated Temperature Leaving Compressor (°F)
SST
— Saturated Temperature Entering Compressor (°F)
TCG
— Gross Cooling Capacity (1000 Btuh)
SST
°F
CONDENSER ENTERING AIR TEMPERATURES °F
55
65
75
85
95
105
115
125
38TZA060-33
30
TCG
SDT
KW
53.4
77.9
2.79
50.5
87.5
3.18
47.6
97.1
3.61
44.7
107.0
4.10
41.8
116.0
4.64
38.8
126.0
5.23
35.7
135.0
5.88
32.5
144.0
6.60
35
TCG
SDT
KW
58.4
79.8
2.85
55.2
89.2
3.24
52.1
98.8
3.67
48.9
108.0
4.16
45.7
118.0
4.71
42.5
127.0
5.30
39.1
137.0
5.95
35.5
146.0
6.66
40
TCG
SDT
KW
63.7
81.8
2.92
60.3
91.1
3.30
56.9
101.0
3.74
53.4
110.0
4.23
49.9
120.0
4.78
46.4
129.0
5.37
42.7
138.0
6.02
38.7
147.0
6.72
45
TCG
SDT
KW
69.3
83.9
2.99
65.6
93.1
3.37
62.0
102.0
3.81
58.2
112.0
4.30
54.4
121.0
4.85
50.5
131.0
5.45
46.4
140.0
6.10
42.1
149.0
6.80
50
TCG
SDT
KW
75.2
86.1
3.06
71.3
95.3
3.45
67.3
105.0
3.89
63.3
114.0
4.38
59.1
123.0
4.93
54.8
132.0
5.54
50.4
141.0
6.18
45.6
150.0
6.88
55
TCG
SDT
KW
81.4
88.5
3.15
77.2
97.5
3.54
72.9
107.0
3.98
68.5
116.0
4.47
64.0
125.0
5.02
59.3
134.0
5.63
54.5
143.0
6.28
49.2
152.0
6.96
Summary of Contents for Performance 12