background image

PA4G: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

13

attached  to  the  inside  of  the  compressor  access  panel.  (See 

Fig. 18

Subcool  chart  for  units  with TXV  and  superheat  chart  for  units  with

fixed orifice.) The chart  includes the required liquid line temperature at

given discharge line pressures and outdoor ambient temperatures.
A superheat chart is attached to the inside of the compressor access panel

for the unit with fixed metering device. Refer to the charging procedure

on the label.
An accurate  thermocouple- or thermistor-type thermometer, and a gauge

manifold are required when using the subcooling charging method for

evaluating  the  unit  charge.  Do  not  use  mercury  or  small  dial-type

thermometers  because  they  are  not  adequate  for  this  type  of

measurement.

NOTE: 

 Allow system to operate for a minimum of 15 minutes before

checking or adjusting refrigerant charge.

IMPORTANT: 

 When  evaluating  the  refrigerant  charge,  an  indicated

adjustment to the specified factory charge must always be very minimal.

If  a  substantial  adjustment  is  indicated,  an  abnormal  condition  exists

somewhere  in  the  cooling  system,  such  as  insufficient  airflow  across

either coil or both coils.
Proceed as follows:

1. Remove caps from low- and high-pressure service fittings.
2. Using  hoses  with  valve  core  depressors,  attach  low-  and

high-pressure  gauge  hoses  to  low-  and  high-pressure  service

fittings, respectively.

3. Start unit and let run until system pressures stabilize.
4. Measure and record the following:

a.

Outdoor ambient-air temperature (

°F [°C] db).

b. Liquid line temperature (°F [°C]) at TXV.

c. Discharge (high-side) pressure (psig). 

d. Suction (low-side) pressure (psig) (for reference only).

5. Using  Cooling  Charging  Charts  compare  outdoor-air  temperature

(°F  [°C] db) with the discharge line pressure (psig) to determine

desired system operating liquid line temperature (See 

Fig. 18

).

6. Compare  actual  liquid  line  temperature  with  desired  liquid  line

temperature. Using a tolerance of ±2°F (±1.1°C), add refrigerant if

actual  temperature  is  more  than  2°F  (1.1°C)  higher  than  proper

liquid line temperature, or remove refrigerant if actual temperature

is  more  than  2°F  (1.1°C)  lower  than  required  liquid  line

temperature.

NOTE: 

 If the problem causing the inaccurate readings is a refrigerant

leak, refer to Check for Refrigerant Leaks section.

Indoor Airflow and Airflow Adjustments

NOTE: 

Be sure that all supply-and return-air grilles are open, free from

obstructions, and adjusted properly. 

This unit is factory-set up for use with a  single cooling fan  speed.  In

addition, this unit has the field-selectable capability to run two different

cooling  fan  speeds: The  rated  cooling  fan  speed  (350~400  CFM/Ton)

and an enhanced dehumidification fan speed (As low as 320 CFM/Ton)

for  use  with  either  a  dehumidistat  or  a  thermostat  that  supports

dehumidification.
The cooling speed is marked “LOW” on the interface fan board (IFB)

(See 

Fig. 11

). The factory-shipped settings are noted in 

Table 4

. There

are  4  additional  speed  tap  wires  available  for  use  in  either  electric

heating or cooling (For color coding on the indoor fan motor leads, see

Table 3

). The additional 4 speed tap wires are shipped loose with vinyl

caps  and  are  located  in  the  control  box,  near  the  interface  fan  board

(IFB) (See 

Fig. 11

).

Single Cooling Fan Speed Set-up (Dehumidification 

feature not used)

To change cooling speed:

1. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding). Add the wet coil pressure drop in 

Table 5

to the system static to determine the correct cooling airflow speed

in 

Table

 that will deliver the nominal cooling airflow as listed in

Table

 for each size.

2. Remove the current speed tap wire from the “LOW” terminal on the

interface fan board (IFB) (See 

Fig. 11

) and place vinyl cap over the

connector on the wire.

3. Connect the desired speed tap wire to the “LOW” terminal on the

interface fan board (IFB).

NOTE: 

If accessory electric heat is installed, and the electric heat fan

speed is chosen to be the same as the normal cooling fan speed, the dry

airflow  must  meet  or  exceed  the  minimum  airflow  speed  specified  in

Table 2

 for the specific size unit.

Two Cooling Fan Speeds Set-up (Dehumidification 

feature used)

IMPORTANT: 

Dehumidification control must open control circuit on

humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of either a 24

VAC dehumidistat or a thermostat which includes control of a 24 VAC

dehumidistat  connection.  In  either  case,  the  dehumidification  control

must  open  the  control  circuit  on  humidity  rise  above  the

dehumidification set point. 

1. Using 

Fig. 11

, move the two pin DEHUM jumper from the “STD”

position to the “DEHUM” position.

2. Remove  fan  speed  tap  wire  from  the  “LOW”  terminal  on  the

interface fan board (IFB) (See 

Fig. 11

).

3. Determine  correct  normal  cooling  fan  speed  for  unit  and

application.  Add the wet coil pressure drop in 

Table 5

 to the system

static to determine the correct cooling airflow speed in 

Table 5

 that

will deliver the nominal cooling airflow as listed in 

Table 1

 for each

size.

NOTE: 

If accessory electric heat is installed, the dry airflow must meet

or  exceed  the  minimum  airflow  speed  specified  in 

Table 2

  for  the

specific size unit. The  electric  heat  fan  speed  will  be  the  same as the

normal cooling fan speed.

4. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding) for the normal cooling fan speed and place

desired speed tap wire on “HIGH” on the interface board. 

5. Refer  to  airflow  tables  (

Table 4

-

Table 6

)  to  determine  allowable

speeds  for  the  dehumidification  cooling  fan  speed.  In 

Table 4

,

speeds  that  are  not  allowed  for  dehumidification  cooling  are

shaded.

6. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding) for the dehumidification cooling fan speed

and place desired speed tap wire on the “LOW” connection on the

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for

each 12,000 Btuh of rated cooling capacity. For heating operation, the

airflow  must  produce  a  temperature  rise  that  falls  within  the  range

stamped on the unit rating plate.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before

changing blower speed.

Summary of Contents for PA4G

Page 1: ...manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor...

Page 2: ...ion cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water tight seal Install gasketing material supplied with the roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in 6 35 mm See Fig 4 This is necessary for unit drain to function p...

Page 3: ...PA4G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 3 A221496 Fig 2 24 30 Unit Dimensions ...

Page 4: ...PA4G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A221497 Fig 3 36 48 Unit Dimensions ...

Page 5: ...E CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whether the unit is a small basepan or a large basepan C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Smallor Large CPRFCURB011B00 14 356 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 Large...

Page 6: ...rk joints and roof openings with counter flashing and mastic in accordance with applicable codes Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit the return should be ducted through the roof deck to comply with applicable fire codes See unit rating plate for any required clearances around ductwork Cabinet ...

Page 7: ...er drainage Make sure that the outlet of the trap is at least 1 in 25 mm lower than the drain pan condensate connection to prevent the pan from overflowing See Fig 8 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap Do not undersize the tube Pitch the ...

Page 8: ...es Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for side shot installation 2 Select and size ductwork supply air registers and return air grilles according to American Society of Heating Refrigeration and Air Conditioning Engineers ASHRAE recommendations 3 Use flexible transition between rigid ductwork and unit to prevent transmission of...

Page 9: ...d more than 100 ft 30 5 m from the unit as measured along the control voltage wires use no 16 AWG color coded insulated 35 C minimum wires Standard Connection Locate the seven eight for 3 phase low voltage thermostat leads in 24 volt splice box A gray wire is standard on 3 phase units for connection to an economizer See Fig 10 for connection diagram Run the low voltage leads from the thermostat th...

Page 10: ...ions If the electric heater 24V wires do not have a matching plug cut the 24V wires from the unit receptacle strip the ends and wire nut together to match the schematic connections Factory wires are provided for electric heat staging W1 and W2 W2 and W3 on IFB If room thermostat has only one stage of supplemental heat connect white and violet wires shown in Fig 10 to second stage heat field wire S...

Page 11: ...6 INDOOR BLOWER Nominal Cooling Airflow Cfm Size in Size mm Motor HP RPM 750 10x10 254x254 1 2 1050 950 10x10 254x254 1 2 1050 1150 11x10 279 4x254 1 2 1000 1350 11x10 279 4x254 3 4 1075 1600 11x10 279 4x254 1 0 1075 1750 11x10 279 4x254 1 0 1040 HIGH PRESSURE SWITCH psig Cut out Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH psig cut out Reset auto N A RETURN AIR FILTERS Throwaway Si...

Page 12: ...start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires IMPORTANT Three phase scroll compressors are direction oriented Unit must be checked to ensure proper compressor 3 phase power lead orientation If not corrected within 5 minutes the internal protector will shut off the compressor The 3 p...

Page 13: ...coding on the indoor fan motor leads see Table 3 The additional 4 speed tap wires are shipped loose with vinyl caps and are located in the control box near the interface fan board IFB See Fig 11 Single Cooling Fan Speed Set up Dehumidification feature not used To change cooling speed 1 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding Add the wet coil pressur...

Page 14: ...nd G These completed circuits through the thermostat connect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 V secondary of transformer TRAN The normally open contacts of energized contactor C close and complete the circuit through compressor motor COMP to condenser outdoor fan motor OFM Both motors start instantly A set of normally open contacts on ...

Page 15: ...0 11 0 11 0 11 Med Low Pink CFM 817 744 673 597 516 431 325 190 BHP 0 14 0 15 0 15 0 16 0 17 0 17 0 18 0 18 Medium Red CFM 1159 1104 1045 990 937 878 821 759 693 618 BHP 0 31 0 32 0 33 0 33 0 34 0 35 0 36 0 37 0 37 0 38 Med High Orange CFM 1201 1147 1095 1037 987 934 877 818 755 671 BHP 0 34 0 35 0 36 0 37 0 37 0 38 0 39 0 40 0 41 0 40 High Black CFM 1291 1236 1181 1131 1080 1033 978 909 792 661 B...

Page 16: ...6 0 06 0 07 0 07 0 08 0 08 0 09 Med Low Pink CFM 1437 1395 1351 1307 1265 1221 1176 1132 1084 1039 BHP 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 Medium Red CFM 1771 1735 1699 1664 1627 1592 1557 1522 1486 1450 BHP 0 51 0 52 0 53 0 55 0 56 0 57 0 58 0 59 0 61 0 62 Med High Orange CFM 1928 1897 1862 1830 1796 1764 1732 1698 1620 1512 BHP 0 64 0 65 0 67 0 68 0 69 0 71 0 72 0 73 0 71 0 66 High...

Page 17: ...FM 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 600 1400CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 0 03 0 05 0 06 0 08 0 10 0 11 0 13 0 14 0 16 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 0 07 0 08 0 09 0 09 0 10 0 11 0 12 1100 2200 CFM 16x24x1 18x24x1 406x610x25 457x610x25 3 0 4 0 5 0 0 02 0 02 0 03 0 03 0 04 0 06 0 08 0 10 0 11 0 13 0 14 0 1...

Page 18: ...G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 18 A221589 Fig 12 Connection Wiring Diagram 208 230 1 60 ...

Page 19: ...A4G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A221590 Fig 13 Ladder Wiring Diagram 208 230 1 60 ...

Page 20: ...G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A221587 Fig 14 Connection Wiring Diagram 208 230 3 60 ...

Page 21: ...A4G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 21 A221588 Fig 15 Ladder Wiring Diagram 208 230 3 60 ...

Page 22: ...A4G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 22 A221585 Fig 16 Connection Wiring Diagram 460 3 60 ...

Page 23: ...PA4G Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221586 Fig 17 Ladder Wiring Diagram 460 3 60 ...

Page 24: ...tions 24 Superheat charging table is derived from optimum performance point 95_F 35_C outdoor ambient and 80_F 27_C dry bulb 67_F 19_C wet bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 Fig 18 Cooling Charging Chart ...

Page 25: ...n in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscrew s that secures wheel to motor shaft remove screws that secure motor mount brackets to housing and slide motor and motor mount out of housing 2 Remove and clean blower wheel as follows a Ensure proper reassembly by marking wheel orientation b Lift w...

Page 26: ...in trough with clear water Do not splash water on the insulation motor wiring or air filter s If the drain trough is restricted clear it with a plumbers snake or similar probe device Outdoor Fan 1 Remove 6 screws holding condenser grille and motor to top cover 2 Turn motor grille assembly upside down on top cover to expose the fan blade 3 Inspect the fan blades for cracks or bends 4 If fan needs t...

Page 27: ... pressure It opens at 650 psig 31 1 kPa High pressure may be caused by a dirty condenser coil failed fan motor or condenser air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmmeter leads across switch You should have continuity on a good switch Compressor R 410A Refrigerant The compressor used in this product is specifically designed to operate w...

Page 28: ...device coil accumulator or reversing valve Synthetic Roof Precautionary Procedure 1 Cover extended roof working area with an impermeable polyethylene plastic drip cloth or tarp Cover an approximate 10 x 10 ft 3 x 3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills prevent run offs and protect drop cloth from tears caused by tools or com...

Page 29: ...erant evacuate system and recharge to capacities shown on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restrict...

Page 30: ...TS PER INSTALLATION INSTRUCTIONS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS INSPECT TUBING III START UP ELECTRICAL SUPPLY VOLTAGE_______________________________________ COMPRESSOR AMPS ___________...

Reviews: