Superheat charging table is derived from optimum performance point. (95
_
F [35
_
C] outdoor ambient and (80
_
F [27
_
C] dry bulb; 67
_
F [19
_
C] wet bulb indoor condition.) Where a dash(--)
appears do not attempt to check charge or charge unit under these conditions using the superheat method. (Weigh in method should be used.)
A150625
Fig. 18 – Cooling Charging Chart