Start-up and Commissioning
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
33
All rights reserved
3
Optimization program is either scheduled or the
Schedule
present value is locked to
On
.
NOTE
In order to lock the Schedule microblock from the
Properties
page, you must select
Show Service
Config
view.
4
Verify the outdoor air conditions are met. OAT must be greater than the configured value.
5
The part load conditions are met.
6
The current chilled water delta temperature is greater than the configured limit.
7
Verify all delays are sufficient.