2 of 5
Standard Range Zone Pressure Multi-Sensor (ZPM)
Installation and Operation
Catalog No. 11-808-711-01
2. Select RANGE
If unit is ordered with a Custom Range,
then the switch must be set to R6.
3. Choose DIRECTION
Bidirectional is a plus/minus range so
choosing 5” range is -5” to +5” Bidirectional
and 0” to +5” Unidirectional
4. Choose UNITS - Inches WC or PASCALS
5. Choose RESPONSE TIME
Fast Response = 1/2 second
Slow Response = 4 seconds
#38592
–
1/10/19
Switch Setup - Outputs, Ranges, Units/Response
Do not have power applied to unit when changing settings. After changing settings, apply power and Auto-Zero
the unit in its orientation of operation.
Figure 2:
Setup
Switches for
Standard
Range Units
1. Select OUTPUT
6. Mount, Terminate and Auto-Zero the
unit as described in later sections.
Attach the deadhead tubing to the ports
during Auto-Zeroing