4. Attach twinning reference label 327956-101 on the outside of blower access door of RH furnace

5. Manually close the blower switch.

6. Turn on power and gas to furnaces.

7. Using appropriate section below, operate furnaces through 2 cycles in each mode to confirm correct operation by operating only the

thermostat.

a. Single- or 2-stage gas heating thermostat R-to-W/W1 for low-gas heat. Single-stage thermostat with adaptive heating mode causes

furnace to operate in low-gas-heat mode for up to 16 minutes, and then furnace automatically switches to high-gas heat. First stage of
a 2-stage thermostat without adaptive heating mode causes furnace to operate in low-gas-heat mode indefinitely.

b. First and second-stage of 2-stage heating thermostat R-to-W/W1-and-W2 for high-gas-heat.

c. Thermostat R-to-G for continuous fan or 2-stage cooling low-cool blower.

d. Cooling thermostat R-to-G-and-Y/Y2 for single-speed cooling blower or for 2-stage cooling high-cool blower.

8. Reinstall control doors on both furnaces.

9. Instruct user in operation of furnaces and thermostat.

PROCEDURE 9—SEQUENCE OF OPERATION

See Fig. 13, 14, or 15 and 37 or 38 for condensing furnace twinning connection and schematic wiring diagrams while reviewing sequence of
operation.

Twinning operation is controlled by LH or MAIN furnace. The TEST/TWIN connection wire ensures the 2 furnaces coordinate their blower
operation. When either furnace requires blower operation, both furnace blowers operate at same speed. Both furnaces operate simultaneously in
the same mode: heat, cool, or continuous fan. Exceptions can occur if a safety switch on either furnace is opened by a problem (such as pressure
switch, flame roll-out switch, main limit switch, twinning kit auxiliary limit switch, or flame-proving sensor). In such a case, the other furnace
continues to operate unless open switch is the flame roll-out, main limit, or twinning kit auxiliary limit switch, in which case both furnaces respond.

Before performing component test, disconnect TKR yellow wire labeled TEST from LH furnace control center TEST/TWIN terminal. After
removing yellow wire, component test can be initiated on each furnace individually as stated in Installation, Start-Up, and Operating Instructions.

A.

Fixed Capacity Furnaces

SINGLE-STAGE HEAT, SINGLE STAGE FURNACES WITH SINGLE-STAGE GAS-HEAT THERMOSTAT

Operation in all modes (sequence of operation) is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up,
and Operating Instructions for more information on the sequence of operation.

TWO-STAGE HEAT, SINGLE STAGE FURNACES WITH 2-STAGE GAS-HEAT THERMOSTAT

1. The two-stage thermostat determines if furnaces are operating in first-stage heat (LH furnace operates in heat while RH furnace blower

operates but RH furnace is not heating) or if furnaces are operating in second-stage heat (both furnaces operate in heat), depending on how
many thermostat stages are calling for heat. If two-stage cooling is used, Y1 from the thermostat will initiate both furnace blowers to the
cooling speed and the first A/C unit. Y2 from the thermostat will go directly to the outdoor unit and initiate the second A/C unit.

2. Operation in all modes (sequence of operation) is the same for twinned furnaces as for an individual furnace. See furnace Installation,

Start-Up, and Operating Instructions for more information on sequence of operation.

TWO-STAGE HEAT, TWO STAGE FURNACES WITH SINGLE-STAGE GAS-HEAT THERMOSTAT

NOTE:

See Section 2, Procedure 2 - Electrical Connections, Step 3 for control board wiring and LHT switch setup.

1. LH furnace control determines whether furnaces are both operating in low-gas heat or high-gas heat, depending on the control’s adaptive

gas heating mode when the R-to-W/W1 circuit is closed in LH furnace.

Fig. 36—Sidewall Termination of More Than 12 in. (Dimension “A” is Touching or 2-in. Maximum Separation)

A96130

COMBUSTION AIR

COMBUSTION AIR

VENT

A

—36—

Summary of Contents for KGATW0601HSI

Page 1: ...ctrical Supply Connections 34 Start Up and Adjustment 34 Sequence of Operation 36 Fixed Capacity Furnaces 36 SAFETY CONSIDERATIONS Installing and servicing of heating equipment can be hazardous due to...

Page 2: ...should be at least as high upflow downflow or as long horizontal as the width of one furnace Supply air dampers when used should be installed in the branch ducts not in the common plenum Fire or smoke...

Page 3: ...furnace Example 2 8 MIN Common Return Air Plenum Return Air Plenum Return Air Plenum Twinned Furnace Common Supply Air Plenum Fig 2 Downflow Horizontal Ductwork Connections A02224 A A A A A A Common...

Page 4: ...r installed and uninstalled ungrounded furnaces 6 Before removing a new control from its container discharge your body s electrostatic charge to ground to protect the control from damage If the contro...

Page 5: ...imit switch cycling will occur 4 Remove bottom closure panels from both furnaces See Fig 4 a Lay furnaces on back or sides b Remove 2 screws from bottom front panel c Rotate front panel downward to re...

Page 6: ...e top of discharge opening and through both furnaces See Fig 6 Drill two 1 8 in holes approximately 1 in below return air flange from inside top of return air opening and through both furnaces See Fig...

Page 7: ...strips equal distance from top and bottom as shown in Fig 5 Trim off excess material 6 Determine which side of furnace will be used to route external extension harness Remove 7 8 in diameter accessor...

Page 8: ...onal support along the bottom of the rafter or joist Consult local or regional building codes for design and loading requirements For suspended installations See Fig 8b Not recommended for wood trusse...

Page 9: ...e d Remove bottom closure panel and set aside for possible use as roll out protection e Reinstall bottom front panel f Stand furnaces upright Fig 8b Suspended Installation for Horizontal Furnaces Back...

Page 10: ...in the horizontal position consideration must be made to the type of building construction Attic floors should be constructed to support normal live and dead loads of the furnaces and the person s se...

Page 11: ...r compartment and through both furnaces See Fig 7 10 Drive 1 factory supplied screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 11 Connect...

Page 12: ...e blower compartment d Install the lock nuts on the 90 conduit connectors e Install 2 kit supplied straps approximately 18 inches from each end of harness Single Stage Heat with Single Stage Gas Heat...

Page 13: ...econdary Harness includes the Auxiliary Door Switch and Auxiliary Limit Switch The harness is also tagged Secondary Furnace near the plug ends of the harness a Connect red wire labeled R Secondary to...

Page 14: ...s 7 Dress wires to ensure they do not contact sharp or moving parts nor interfere with blower operation removal of filters or operation of switches 8 Make all thermostat connections to LH furnace only...

Page 15: ...by side only 2 harness assemblies are required If the furnaces are installed back to back all 3 harness assemblies included in the kit must be used 1 Remove outer doors and blower access doors from bo...

Page 16: ...harness on R H furnace The Secondary Harness includes the Auxiliary Door Switch and Auxiliary Limit Switch The harness is also tagged Secondary Furnace near the plug ends of the harness a Connect red...

Page 17: ...nnect any connection other than supply and return air ducts Furnaces are recommended to be provided with a single shutoff valve However individual shutoff valves may be required by local codes or juri...

Page 18: ...C Y OUTDOOR UNIT NO 2 LEGEND NOTES Y G W R COM NOTE 3 NOTE 6 327893 101 REV A 1 ALS S and ILK 1 are located in the SECONDARY or RH furnace blower compartment 2 Primary connections of transformer not...

Page 19: ...L2 NOTE 2 PR1 MAKE NO THERMOSTAT CONNECTIONS TO SECONDARY OR RH FURNACE 1 2 ORN BLU RED EXTENSION HARNESS IF USED PLA 1 2 ORN BLU ILK 1 ALS S NOTE 1 ORN NOTE 3 24 VAC TRANSFORMER FIELD SUPPLIED NOTE 4...

Page 20: ...ENSION HARNESS IF USED PLA 1 2 ORN BLU ILK 1 ALS S NOTE 1 ORN NOTE 3 24 VAC TRANSFORMER FIELD SUPPLIED NOTE 4 115 VAC C Y OUTDOOR UNIT NO 1 C Y OUTDOOR UNIT NO 2 ACRDJ AIR CONDITIONINGRELAY DISABLE JU...

Page 21: ...beled TEST from LH furnace control TEST TWIN terminal After removing yellow wire component test can be initiated on each furnace individually as stated in Installation Start Up and Operating Instructi...

Page 22: ...ultipoise units can be installed in UPFLOW DOWNFLOW or HORIZONTAL configurations A Upflow Downflow Side By Side Configuration Refer to Fig 20 for appearance and dimensional drawing of twinned furnaces...

Page 23: ...tructions for details on optimum speed selection 10 Factory connected when BVSS Chimney Adapter Accessory Kit is not installed 11 Factory connected when LGPS is not used 12 Ignition lockout will occur...

Page 24: ...INTERLOCK SWITCH SPST N O JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS 1 2 LIMIT SWITCH AUTO RESET SPS...

Page 25: ...tighten until furnaces are secure and foam strips have sealed gap between furnaces Fig 20 Dimensional Drawing for Twinned Single Speed Condensing Furnaces Upflow Downflow A93537 17 5 16 24 1 2 27 1 2...

Page 26: ...e from inside top of return air opening and through both furnaces See Fig 25 Fig 21 Back to Back Upflow Downflow or Horizontal A02234 Table 4 Dimensions INPUT HEATING SIZE BTUH NOMINAL COOLING SIZE A...

Page 27: ...eath DO NOT use the back of the furnace for return air duct connections as limit cycling will occur B Upflow Downflow Back to Back Configuration Refer to Fig 21 and Table 4 for appearance and dimensio...

Page 28: ...both furnaces See Fig 25 c Drive 1 factory supplied No 6 X 3 4 in LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 7 Determine which si...

Page 29: ...bles per the furnace Installation Start up and Operating Instructions 5 Unistrut or similar material may be used provided that the furnaces do not sag in the middle or bend or twist at the support end...

Page 30: ...w applications reference the furnaces from the front as you would see them in the upflow application See Fig 29 The LH furnace is the main furnace and the RH furnace is the secondary furnace b In the...

Page 31: ...20 and 29 Route female four pin connector through previously installed bushings in unused condensate drain holes located on casing in blower compartment area Connect to male four pin connector of RH...

Page 32: ...ZARD Failure to follow this caution could result in intermitted furnace operation and unit damage Supply air temperature will be uneven left to right when only main system is operating Fig 29 Twinning...

Page 33: ...as shown in Fig 23 2 Position ALS S so terminals face front of furnace 3 Secure bracket to blower housing using factory supplied No 6 X 3 4 in LG screw b Install auxiliary door switch ILK 1 1 Drill 7...

Page 34: ...ers connected to the same service panel 115 vac phase leg On single phase residential systems each furnace circuit breaker should be located directly across from each other in service panel or each fu...

Page 35: ...single stage thermostat 327893 101 Single Stage furnaces with two stage thermostat 327892 101 Two Stage furnaces with single stage or 2 stage thermostat 327891 101 Fig 33 Concentric Vent and Combusti...

Page 36: ...out main limit or twinning kit auxiliary limit switch in which case both furnaces respond Before performing component test disconnect TKR yellow wire labeled TEST from LH furnace control center TEST...

Page 37: ...RELAY SPST N O HUM 24VAC HUMIDIFIER CONNECTION 0 5 AMP MAX IDM INDUCED DRAFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMP...

Page 38: ...BOX LED LIGHT EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOA...

Page 39: ...ard Energizes accessory cooling relay s to start L H and R H A C for cooling G G Starts both indoor fans on cooling speed With Y Y2 energized Dehum Dehum Reduces airflow in cooling mode from cooling s...

Page 40: ...on cooling speed With Y Y2 energized Dehum Dehum Reduces airflow in cooling mode from cooling speed to heating speed when Dehum input is removed Do not remove ACRDJ from furnace control boards Dehum...

Reviews: