background image

PROCEDURE 4—VENTING

Refer to Installation, Start-Up, and Operating Instructions supplied with each furnace for venting information. Each furnace must always be
individually vented. Do not common-vent or breach-vent condensing furnaces. For direct-vent installations, refer to Fig. 32, 33, 34, 35, or 36 for
proper termination. It is important that vent terminations be made as shown to avoid recirculation of flue gases.

PROCEDURE 5—GAS SUPPLY PIPING

NOTE:

All gas connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supply-

and return-air ducts.

Furnaces are recommended to be provided with a single shutoff valve. However, individual shutoff valves may be required by local codes or
jurisdictions. Refer to Installation, Start-Up, and Operating Instructions provided with each furnace for additional gas supply information.

PROCEDURE 6—CONDENSATE DRAIN CONNECTIONS

The condensate trap is factory installed in blower shelf and factory connected for UPFLOW applications. Install condensate trap extension drain
such that field drain connections are on the left side for LH (MAIN) furnace and on right side for RH (SECONDARY) furnace. (See Fig. 29.)

The condensate trap must be relocated for downflow and horizontal applications.

See furnace Installation, Start-Up, and Operating Instructions for details on attaching field drain for downflow and horizontal applications.

PROCEDURE 7—ELECTRICAL SUPPLY CONNECTIONS

NOTE:

All electrical power connections must be made through exposed outer side of each furnace. Do not common connect any connection other

than supply- and return-air ducts.

1. Each furnace shall be connected to its own 115-vac power supply. The twinning kit installation interconnects the furnaces, allowing them

to operate as a single furnace. The L1 (black) connection to each furnace must be connected to circuit breakers connected to the same service
panel 115-vac phase leg.

On single-phase

(residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or

each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of
the 1-phase power supply.

On 3-phase

(commercial) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each

furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the
3-phase power supply.
The proper 115-vac phasing of furnace connections permits 24-vac transformer phasing as described below.

2. Phasing of the connected 24-vac transformer secondary circuits can be determined with the LED status of both furnaces. See furnace

Installation, Start-Up, and Operating Instructions and status code label on blower access panel or main furnace door. The furnaces’
transformers’ black leads should be connected to PR1 connectors and white leads to PR2 connectors on controls. If 1 or both LEDs are
rapidly flashing, disconnect lead at TEST/TWIN terminal of LH furnace and observe LED at each furnace.

IF:

a. Both LEDs are on continuously:

System phasing is okay.

b. One or both LEDs are rapidly flashing:

(1.) Line voltage polarity is reversed.

(2.) Reverse SEC-1 and SEC-2 in furnace with rapid flashing LED.

c. One LED is off, 1 LED is on continuously:

(1.) The 24-vac circuit is inoperative on furnace with LED light off.

(2.) Check transformers, auxiliary limits, and door switches in both furnaces and correct problem.

3. Reconnect lead at TWIN/TEST terminal of LH furnace and observe LED at each furnace. The LEDs will glow steady for proper phasing.

PROCEDURE 8—START-UP AND ADJUSTMENT

NOTE:

Refer to Installation, Start-Up, and Operating Instructions supplied with furnace for detailed information.

1. Shut off all power and gas to both furnaces.

Fig. 32—Rooftop Termination (Dimension “A” is Touching or 2-in. Maximum Separation)

A96128

A

—34—

Summary of Contents for KGATW0601HSI

Page 1: ...ctrical Supply Connections 34 Start Up and Adjustment 34 Sequence of Operation 36 Fixed Capacity Furnaces 36 SAFETY CONSIDERATIONS Installing and servicing of heating equipment can be hazardous due to...

Page 2: ...should be at least as high upflow downflow or as long horizontal as the width of one furnace Supply air dampers when used should be installed in the branch ducts not in the common plenum Fire or smoke...

Page 3: ...furnace Example 2 8 MIN Common Return Air Plenum Return Air Plenum Return Air Plenum Twinned Furnace Common Supply Air Plenum Fig 2 Downflow Horizontal Ductwork Connections A02224 A A A A A A Common...

Page 4: ...r installed and uninstalled ungrounded furnaces 6 Before removing a new control from its container discharge your body s electrostatic charge to ground to protect the control from damage If the contro...

Page 5: ...imit switch cycling will occur 4 Remove bottom closure panels from both furnaces See Fig 4 a Lay furnaces on back or sides b Remove 2 screws from bottom front panel c Rotate front panel downward to re...

Page 6: ...e top of discharge opening and through both furnaces See Fig 6 Drill two 1 8 in holes approximately 1 in below return air flange from inside top of return air opening and through both furnaces See Fig...

Page 7: ...strips equal distance from top and bottom as shown in Fig 5 Trim off excess material 6 Determine which side of furnace will be used to route external extension harness Remove 7 8 in diameter accessor...

Page 8: ...onal support along the bottom of the rafter or joist Consult local or regional building codes for design and loading requirements For suspended installations See Fig 8b Not recommended for wood trusse...

Page 9: ...e d Remove bottom closure panel and set aside for possible use as roll out protection e Reinstall bottom front panel f Stand furnaces upright Fig 8b Suspended Installation for Horizontal Furnaces Back...

Page 10: ...in the horizontal position consideration must be made to the type of building construction Attic floors should be constructed to support normal live and dead loads of the furnaces and the person s se...

Page 11: ...r compartment and through both furnaces See Fig 7 10 Drive 1 factory supplied screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 11 Connect...

Page 12: ...e blower compartment d Install the lock nuts on the 90 conduit connectors e Install 2 kit supplied straps approximately 18 inches from each end of harness Single Stage Heat with Single Stage Gas Heat...

Page 13: ...econdary Harness includes the Auxiliary Door Switch and Auxiliary Limit Switch The harness is also tagged Secondary Furnace near the plug ends of the harness a Connect red wire labeled R Secondary to...

Page 14: ...s 7 Dress wires to ensure they do not contact sharp or moving parts nor interfere with blower operation removal of filters or operation of switches 8 Make all thermostat connections to LH furnace only...

Page 15: ...by side only 2 harness assemblies are required If the furnaces are installed back to back all 3 harness assemblies included in the kit must be used 1 Remove outer doors and blower access doors from bo...

Page 16: ...harness on R H furnace The Secondary Harness includes the Auxiliary Door Switch and Auxiliary Limit Switch The harness is also tagged Secondary Furnace near the plug ends of the harness a Connect red...

Page 17: ...nnect any connection other than supply and return air ducts Furnaces are recommended to be provided with a single shutoff valve However individual shutoff valves may be required by local codes or juri...

Page 18: ...C Y OUTDOOR UNIT NO 2 LEGEND NOTES Y G W R COM NOTE 3 NOTE 6 327893 101 REV A 1 ALS S and ILK 1 are located in the SECONDARY or RH furnace blower compartment 2 Primary connections of transformer not...

Page 19: ...L2 NOTE 2 PR1 MAKE NO THERMOSTAT CONNECTIONS TO SECONDARY OR RH FURNACE 1 2 ORN BLU RED EXTENSION HARNESS IF USED PLA 1 2 ORN BLU ILK 1 ALS S NOTE 1 ORN NOTE 3 24 VAC TRANSFORMER FIELD SUPPLIED NOTE 4...

Page 20: ...ENSION HARNESS IF USED PLA 1 2 ORN BLU ILK 1 ALS S NOTE 1 ORN NOTE 3 24 VAC TRANSFORMER FIELD SUPPLIED NOTE 4 115 VAC C Y OUTDOOR UNIT NO 1 C Y OUTDOOR UNIT NO 2 ACRDJ AIR CONDITIONINGRELAY DISABLE JU...

Page 21: ...beled TEST from LH furnace control TEST TWIN terminal After removing yellow wire component test can be initiated on each furnace individually as stated in Installation Start Up and Operating Instructi...

Page 22: ...ultipoise units can be installed in UPFLOW DOWNFLOW or HORIZONTAL configurations A Upflow Downflow Side By Side Configuration Refer to Fig 20 for appearance and dimensional drawing of twinned furnaces...

Page 23: ...tructions for details on optimum speed selection 10 Factory connected when BVSS Chimney Adapter Accessory Kit is not installed 11 Factory connected when LGPS is not used 12 Ignition lockout will occur...

Page 24: ...INTERLOCK SWITCH SPST N O JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS 1 2 LIMIT SWITCH AUTO RESET SPS...

Page 25: ...tighten until furnaces are secure and foam strips have sealed gap between furnaces Fig 20 Dimensional Drawing for Twinned Single Speed Condensing Furnaces Upflow Downflow A93537 17 5 16 24 1 2 27 1 2...

Page 26: ...e from inside top of return air opening and through both furnaces See Fig 25 Fig 21 Back to Back Upflow Downflow or Horizontal A02234 Table 4 Dimensions INPUT HEATING SIZE BTUH NOMINAL COOLING SIZE A...

Page 27: ...eath DO NOT use the back of the furnace for return air duct connections as limit cycling will occur B Upflow Downflow Back to Back Configuration Refer to Fig 21 and Table 4 for appearance and dimensio...

Page 28: ...both furnaces See Fig 25 c Drive 1 factory supplied No 6 X 3 4 in LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 7 Determine which si...

Page 29: ...bles per the furnace Installation Start up and Operating Instructions 5 Unistrut or similar material may be used provided that the furnaces do not sag in the middle or bend or twist at the support end...

Page 30: ...w applications reference the furnaces from the front as you would see them in the upflow application See Fig 29 The LH furnace is the main furnace and the RH furnace is the secondary furnace b In the...

Page 31: ...20 and 29 Route female four pin connector through previously installed bushings in unused condensate drain holes located on casing in blower compartment area Connect to male four pin connector of RH...

Page 32: ...ZARD Failure to follow this caution could result in intermitted furnace operation and unit damage Supply air temperature will be uneven left to right when only main system is operating Fig 29 Twinning...

Page 33: ...as shown in Fig 23 2 Position ALS S so terminals face front of furnace 3 Secure bracket to blower housing using factory supplied No 6 X 3 4 in LG screw b Install auxiliary door switch ILK 1 1 Drill 7...

Page 34: ...ers connected to the same service panel 115 vac phase leg On single phase residential systems each furnace circuit breaker should be located directly across from each other in service panel or each fu...

Page 35: ...single stage thermostat 327893 101 Single Stage furnaces with two stage thermostat 327892 101 Two Stage furnaces with single stage or 2 stage thermostat 327891 101 Fig 33 Concentric Vent and Combusti...

Page 36: ...out main limit or twinning kit auxiliary limit switch in which case both furnaces respond Before performing component test disconnect TKR yellow wire labeled TEST from LH furnace control center TEST...

Page 37: ...RELAY SPST N O HUM 24VAC HUMIDIFIER CONNECTION 0 5 AMP MAX IDM INDUCED DRAFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMP...

Page 38: ...BOX LED LIGHT EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOA...

Page 39: ...ard Energizes accessory cooling relay s to start L H and R H A C for cooling G G Starts both indoor fans on cooling speed With Y Y2 energized Dehum Dehum Reduces airflow in cooling mode from cooling s...

Page 40: ...on cooling speed With Y Y2 energized Dehum Dehum Reduces airflow in cooling mode from cooling speed to heating speed when Dehum input is removed Do not remove ACRDJ from furnace control boards Dehum...

Reviews: