2

INSTALLATION

NOTE

: If a fully communicating Infinity/Evolution Control is

being used for low ambient cooling, a winter start control is not

required.
For outdoor units with Infinity/Evolution and TechAssist

single--stage control boards and two--stage non--communicating

AC:

1. Mount the winter start control board in outdoor control box

using provided screws. If necessary, mark and drill 1/8”

diameter pilot holes.

2. Connect the following wires to the TDR:

S

13” (330 mm) Yellow wire to T1 (24 VAC input)

S

13” (330 mm) Brown wire to T3 (24 VAC common)

S

13” (330 mm) Blue--tap wire to T2 (N.O. relay contact)

3. Secure the open end of Blue Tap wire to the insulated tap

connector (see Fig. 1). To do this, simply butt the tap--wire

against the wire stop. Fold the top cover half over to meet

the base. Squeeze on the top cover and base with ordinary

pliers until the latch locks. DO NOT place pliers on top of

the raised plastic flange.

4. Identify the LPS (low pressure switch) connector at the

ODU circuit board, and identify the 24vac LPS run--wire

(or main lead) for the pressure switch. The LPS run--wire is

different between circuit boards (see Fig. 3, 4, 5 and 6).

S

Infinity/Evolution (HK38EA004) LPS run--wire is

connected to pin #1 (see Fig. 3).

S

TechAssist (HK35AC005) LPS run--wire is connected to

pin #2 (middle pin) (see Fig. 4).

S

Two--stage non--communicating AC LPS run--wire is

located just before quick connect connecting to high

pressure switch (see Fig. 5).

S

Two--stage communicating AC (HK38EA016) LPS

run--wire is connected to pin #2 (middle pin, see Fig. 6).

Secure the LPS run--wire by inserting the run--wire into the

remaining open section of connector. Fold the base over to

meet the run--wire section. Squeeze on the base and run--

wire section with ordinary pliers until the latch locks. DO

NOT place pliers on top of the raised plastic flange.

5. Connect the open strip end of 13” (330 mm) Brown wire to

(C) 24vac common side of the ODU and thermostat field

connections.

6. Connect the open strip end of 13” (330 mm) Yellow wire to

(Y single stage and Y1 2--stage) 24vac side of the ODU and

thermostat field connections.

Additional

Installation

Instructions

for

Two--stage

Communicating Capable AC Units:

When TDR is in the circuit and allowing the low pressure switch to

be bypassed but is closed, the outdoor transformer may be out of

phase with the indoor transformer causing the ID or OD fuse to

blow.
To eliminate this possibility, the outdoor transformer needs to be

removed from the circuit.
To do this:

1. Remove the red and black wires from the outdoor trans-

former secondary that are attached to SEC 1 and SEC 2 on

the control board.

2. Remove the black wire connected to the primary side of the

transformer and the other side from 11 of the contactor.

Since the transformer powers the outdoor control board and

compressor solenoid, a low voltage control wire will need

to be connected from R on the indoor to the UTIL terminal

on the control board. See Fig. 6.

NOTE

: The Winter Start Control time--delay logic is now wired in

parallel with the outdoor unit low--pressure switch. When indoor

thermostat calls, the TDR logic will energize (closing T1, T2) for

approximately 3--minutes bypassing the LPS. After 3--minutes, the

TDR logic will de--energize (opening T1, T2) and the LPS circuit is

restored (see Fig. 2).

Troubleshooting Upon Start--up

If the TDR does not energize, make sure LPS run and tap wires are

not reversed (double check figures below). You can also apply

24vac direct to T1 and T3 to verify that the TDR relay will

energize.

Wire

Contact

Base

Wire

Stop

Blue

Tap

Wire

Plastic 

Flange

LPS

Run

Wire

Yellow w/ Red

Blue Tap

Wire

A07934

A07944

Fig. 1 -- Installation

(Y)

(C)

T1

T2

C

T3

LPS

24 VAC

24 VAC

LPS = Low Pressure Switch

C = Contactor Coil

T1 = 24 VAC Input
T2 = Switch Override

T3 = 24 VAC Com

TDR = Time Delay Relay 
            Circuit Board

A07933

Fig. 2 -- Wiring for Winter Start Control