background image

OPERATIONAL INFORMATION

Zone Selection:

Press top left ZONE button to select zones.

Continuous Fan Operation

Pressing FAN button will scroll through the following:

AUTO = No fan operation except during equipment operation.

LOW = Approximately 50% of High Speed operation.

MED = Half way between High and Low speed operation.

HIGH = Highest of either High Heating or High Cooling CFM.

Five-Minute Compressor Timeguard

This timer prevents compressor from starting unless it has been off
for at least 5 minutes. It can be defeated by simultaneously
pressing the Fan and Temp + buttons.

Emergency Heat (for heat pump applications)

To activate Emergency Heat, you must press and hold the HEAT
button for 3 seconds to activate.

Keypad Lockout

Keypad can be locked by pressing

Fan

and

Zone

buttons at the

same time for 3 seconds. When keys are locked, a lock symbol will
appear in the upper left corner of screen. Follow same procedure
to unlock keypad.

Heat and Cool LED

The Heat and Cool LEDs will pulsate during actual equipment
operation.

Equipment Cycle Timer (adjustable 4-6 cycles per hour)

This timer prevents the start of a heating or cooling cycle until 15
(or 10) minutes after the last start of the same cycle. Its function is
to assure that the equipment is not cycled more than the selected
times per hour. This timer is adjustable from 4 to 6 cycles per hour.
This timer is defeated for one cycle when the desired temperature
is manually changed. It can also be defeated for one cycle by
simultaneously pressing the Fan and Temp + buttons.

Ten-Minute Staging Timer

In multistage heating or cooling, this timer prevents any higher
stage from turning on until the preceding stage has been on for 10
minutes. This timer is defeated if temperature error is greater than
5°F (usually due to a large change in desired temperature).

Three-Minute Minimum On Time

In normal operation, when a stage turns on, it will remain on for a
minimum of three minutes. If the set point is changed, this timer is
automatically cancelled, allowing the equipment to turn off imme-
diately when the demand is removed.

Heat/Cool Set points (Desired Temperatures)

A minimum difference of 2° (default) is enforced between heating
and cooling desired temperatures. This is done by allowing one
setting to

push

the other to maintain this difference. This

difference is adjustable via the Install/Service menu under Ther-
mostat Setup.

Auto Changeover

When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the set point is changed, the
30-minute requirement is defeated. This Auto Changeover time is
adjustable via the Install/Service menu under Thermostat Setup.
Range = 5 - 120 min.

Smart Recovery

With Smart Recovery selected (factory default), transition out of
setback begins 1.5 hours before selected recovery time and
gradually adjusts room temperature so desired temperature will be
achieved at selected recovery time. It operates in both heating and
cooling. This only applies to programmable operation.

Media Filter

If MEDIA or MEDIA+EAC is installed in the indoor unit, the
system will perform a static pressure check of the system every 24
hours at 1:00PM to monitor filter accumulation (TrueSense™
Dirty Filter Detection) or whenever power is applied to the system
or the system is transitioned from Off to Cool or Heat modes. The
blower will run at a medium airflow for one minute.

Unoccupied

Pressing the HOLD button for 3 sec. will set the selected zone to
unoccupied status.

All Zones

Pressing the zone button for 3 sec. will gray out the entire display
and put the User Interface into All Zones mode (indicated by All
Zones in upper left of the display). Any changes to set temperature,
fan, or Hold status will occur in all zones when the screen is exited.
Press the Zone button to exit All Zones mode.

13

Summary of Contents for Infinity SYSTXCCUIZ01

Page 1: ...or fan coils are variable speed and multi stage for maximum flexibility efficiency and comfort They support controlled ventilation humidification dehumidification and air quality control Either an Infinity dual capacity communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the Infinity furnace or fan coil provides the 24 volt signals needed to...

Page 2: ...te Room Sensor has priority over the Smart Sensor WIRING CONSIDERATIONS Ordinary thermostat wire is recommended Use 22 AWG or larger for normal wiring applica tions Continuous wire lengths over 100 ft should use 20 AWG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or brok...

Page 3: ...re to follow this warning could result in personal injury or death Before installing Infinity Zone Control turn off all power to equipment There may be more than one power source to disconnect 1 Turn off all power to equipment 2 If an existing User Interface or control is being replaced a Remove existing control from wall b Disconnect wires from existing control Fig 2 Infinity Zone Control A03185 ...

Page 4: ...eaks can affect operation 10 Attach Infinity Zone Control to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on 11 Perform installation of all other system equipment i e zone sensors dampers humidifier ventilator UV lights etc 12 Turn on power to equipment EQUIPMENT WIRING DIAGRAMS See wiring diagrams Fig 12 13 and 1...

Page 5: ...to become familiar with key function buttons such as System On Off Zone Fan Left Side and Right Side buttons etc These function buttons will be used frequently during setup SECTION 1 POWER UP SEQUENCE This section addresses initial power up or commissioning of a new Infinity Zone Control The User Interface will communi cate and identify all Infinity components in the system The following is a typi...

Page 6: ...IGHTS INSTALLED See Fig 18 Use either Time or Temp buttons to make appropriate selections in the highlighted area on the display screen Press right side button to continue or advance to the next screen AIR FILTER TYPE This accessory screen will appear first The installer will need to enter the type of filter MEDIA EAC or both See Table 1 and make a selection using Time or Temp button then press ri...

Page 7: ...irmed when the red LED next to the red HEAT button is lit 2 Use the TEMP button to select your desired heating temperature 3 The default time for temporarily overriding the temperature schedule is 2 00 HRS as indicated by the text on the lower left NOTE Override time will not appear if programming has been turned off 4 You can change the temporary override time in 15 minute increments by pressing ...

Page 8: ...t configuration made by dip switches Fig 23 shows all the information that can be found in the SETUP menu Setup THERMOSTAT AUTO MODE SETUP Enable Disable Auto Changeover mode default Enable Auto Changeover Time may be adjusted 5 to 120 minutes default 30 minutes When Auto mode is enabled factory default a change from heat to cool or vice versa will not occur until an opposite mode demand has exist...

Page 9: ...lt LOW HIGH Controls the staging of the furnace SYSTEM setting will allow the Infinity Zone Control to determine furnace staging LOW will only run the low stage of furnace heat HIGH will only run the high stage of furnace heat OFF DELAY 90 seconds 120 seconds default 150 seconds 180 seconds Amount of time the blower will continue to run after heating has shut off LOCKOUT TEMP NONE default 5 to 55 ...

Page 10: ...ault 90 Interval at which the Clean Ventilator Pre filter notification will turn on UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed Setup SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adj...

Page 11: ... room sensor is disconnected the Zone 2 damper will now open as indicated on the User Interface display The word FAIL will also be displayed instead of the actual temperature for Zone 2 Reconnect Zone 2 sensor and try all remaining sensors one at a time in the system Smart Sensors may also be checked see Smart Sensor Installation Instructions for procedure AIRFLOW LIMITS Low Medium High default Ma...

Page 12: ...vered to each zone Damper position range from 0 to 15 0 closed 15 open Service LAST 10 SYSTEM FAULTS This screen will show last 10 faults that occurred throughout the system Each fault has the time and date incident recorded Service technician should enter current date in TODAY S DATE menu section BEFORE checking and logging the last 10 system faults Each fault has a two letter acronym preceding t...

Page 13: ...um On Time In normal operation when a stage turns on it will remain on for a minimum of three minutes If the set point is changed this timer is automatically cancelled allowing the equipment to turn off imme diately when the demand is removed Heat Cool Set points Desired Temperatures A minimum difference of 2 default is enforced between heating and cooling desired temperatures This is done by allo...

Page 14: ...sts between the actual room temperature and operating set point yet the equipment does not turn on 1 The zone airflow limit may be set too low Perform the Zone Airflow Limit Checkout procedure raise airflow limit setting if possible Some zones provide too much airflow and are noisy 1 The zone airflow limit may be set too high Perform the Zone Airflow Limit Checkout procedure lower airflow limit se...

Page 15: ...le NIM communication fault Defrost Error defrost signal on for more than 15 minutes The user can press the right side button to dismiss the notice The regular run mode screen will then appear except SYSTEM MALFUNCTION will appear in place of the day time If the error has not disappeared within 24 hours the above display will return If the error code disappears SYSTEM MALFUNCTION will disappear and...

Page 16: ...231 uiz01 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab misc misc PC 101 Catalog No 809 50025 Printed in U S A Form UIZ01 1SI Pg 16 03 04 Replaces NEW ...

Reviews: