background image

Checkout = HEAT PUMP HEATING

HIGH HEAT RUNTIME: 5 min.

LOW HEAT RUNTIME: 5 min.

DEFROST: NO

The heat pump heating mode can be exercised with this menu
option. With a 2-speed heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost
cycle is also selectable. Default time = Fixed 5 min. minimum,
range = 5 - 120 min.

Checkout = HEAT PUMP COOLING OR AC COOLING

HIGH COOL RUNTIME: 5 min.

LOW COOL RUNTIME: 5 min.

The heat pump cooling mode (or AC cooling mode) can be
exercised with this menu option. With a 2-speed heat pump or AC
unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat
pump or AC operating status. Default time = Fixed 5 min.
minimum, range = 5 - 120 min.

Checkout = HUMIDIFIER

OFF

ON

The humidifier can be exercised On and Off with this menu option.

Checkout = VENTILATOR

SPEED:

OFF

LOW

HIGH

The ventilator can be exercised through all of its operating speeds
with this menu option.

Checkout = ZONING

DUCT ASSESSMENT

This is the same Duct Assessment that runs on first start-up.

Measures duct capacity for each zone. The Duct Assessment will
perform an airflow measurement on each zone and determine the
relative size of each zone along with damper leakage. This
assessment will require approximately 1 minute for each zone in
the system.

NOTE:

A Duct Assessment will automatically occur every 24

hours at 1:00 p.m. to check system static and calibrate dampers.

SENSOR DAMPER CHECK:

The Sensor/Damper Check allows the installer to check each zone
damper for operation, as well as insure the zone sensor corre-
sponds to that particular zone.

When first initiated, the Zone 1 damper will fully OPEN, and all
other zones will CLOSE. Using the scroll button, the installer can
select each zone and verify the damper is fully open while all other
dampers remain closed.

After proper damper operation has been verified, the installer can
now check and verify that each remote room sensor corresponds to
the proper zone damper in the same zone. Start from the top and
highlight zone 1 to open damper. Temporarily disconnect any
other zone remote room sensor (at sensor location). That zone
damper will now OPEN, while the Zone 1 damper will close.
EXAMPLE: If the Zone 2 remote room sensor is disconnected, the
Zone 2 damper will now open as indicated on the User Interface
display. The word

FAIL

will also be displayed instead of the

actual temperature for Zone 2. Reconnect Zone 2 sensor and try all
remaining sensors one at a time in the system. Smart Sensors may
also be checked, see Smart Sensor Installation Instructions for
procedure.

AIRFLOW LIMITS:

Low

Medium

High (default)

Maximum

Because there is no bypass damper, the Zone Airflow Limit check
will allow the installer to assess the airflow noise generated by the
system providing the maximum amount of airflow to each zone.
Select 9 ZONE, then select AIRFLOW LIMIT: Low, Medium,
High (default), or Maximum. When Start is pressed (right side
button), the selected zone’s damper will fully open, all others will
close, and the indoor unit will provide the maximum airflow for
that zone (as selected in Setup = ZONING, Airflow Limits). If the
airflow noise is objectionable, the installer can select a lower
airflow noise limit. If the noise is not objectionable, the installer
should leave High selected, or even Maximum.

NOTE:

Selecting a lower airflow noise limit may decrease the

homeowner’s comfort in that zone.

SERVICE MENUS

The Service Info menu will only show the equipment installed in
the system. Below is a sample using a furnace and a heat pump
(dual fuel). A sample service menu is shown in Fig. 25.

Service = FURNACE STATUS

The Status screens will show all of the current operating param-
eters of each installed piece of equipment.

HEAT STAGE:

OFF, LOW, HIGH

Displays stage of heat that the furnace is currently delivering.

AIRFLOW CFM:

(furnace model dependent)

Cubic Feet per Minute of air the blower is currently delivering.

LEAVING AIR TEMP:

This sensor is NOT required. However, if LAT sensor is
connected to the Damper Control Module, the sensor will read
leaving air temperature of the furnace.

COIL TEMP:

This sensor is NOT required. However, if HPT sensor is
connected to the Damper Control Module, the sensor will read
temperature at that location (i.e. if placed in return-air, will read
return-air temperature).

INDUCER RPM (90% furnaces only):

Inducer motor RPM value.

BLOWER RPM:

Blower motor RPM value.

STATIC PRESS:

Inches of water. Displays static pressure that the furnace is
currently experiencing.

Fig. 25 — SERVICE INFO MENUS

A04092

SERVICE INFO

FURNACE STATUS
HEAT PUMP STATUS
ZONING STATUS
LAST 10 SYSTEM FAULTS
RUN/FAULT HISTORY
TODAY’S DATE
MODEL/SERIAL NUMBER
SERVICE PHONE NUMBER
   BACK               SELECT

11

Summary of Contents for Infinity SYSTXCCUIZ01

Page 1: ...or fan coils are variable speed and multi stage for maximum flexibility efficiency and comfort They support controlled ventilation humidification dehumidification and air quality control Either an Infinity dual capacity communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the Infinity furnace or fan coil provides the 24 volt signals needed to...

Page 2: ...te Room Sensor has priority over the Smart Sensor WIRING CONSIDERATIONS Ordinary thermostat wire is recommended Use 22 AWG or larger for normal wiring applica tions Continuous wire lengths over 100 ft should use 20 AWG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or brok...

Page 3: ...re to follow this warning could result in personal injury or death Before installing Infinity Zone Control turn off all power to equipment There may be more than one power source to disconnect 1 Turn off all power to equipment 2 If an existing User Interface or control is being replaced a Remove existing control from wall b Disconnect wires from existing control Fig 2 Infinity Zone Control A03185 ...

Page 4: ...eaks can affect operation 10 Attach Infinity Zone Control to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on 11 Perform installation of all other system equipment i e zone sensors dampers humidifier ventilator UV lights etc 12 Turn on power to equipment EQUIPMENT WIRING DIAGRAMS See wiring diagrams Fig 12 13 and 1...

Page 5: ...to become familiar with key function buttons such as System On Off Zone Fan Left Side and Right Side buttons etc These function buttons will be used frequently during setup SECTION 1 POWER UP SEQUENCE This section addresses initial power up or commissioning of a new Infinity Zone Control The User Interface will communi cate and identify all Infinity components in the system The following is a typi...

Page 6: ...IGHTS INSTALLED See Fig 18 Use either Time or Temp buttons to make appropriate selections in the highlighted area on the display screen Press right side button to continue or advance to the next screen AIR FILTER TYPE This accessory screen will appear first The installer will need to enter the type of filter MEDIA EAC or both See Table 1 and make a selection using Time or Temp button then press ri...

Page 7: ...irmed when the red LED next to the red HEAT button is lit 2 Use the TEMP button to select your desired heating temperature 3 The default time for temporarily overriding the temperature schedule is 2 00 HRS as indicated by the text on the lower left NOTE Override time will not appear if programming has been turned off 4 You can change the temporary override time in 15 minute increments by pressing ...

Page 8: ...t configuration made by dip switches Fig 23 shows all the information that can be found in the SETUP menu Setup THERMOSTAT AUTO MODE SETUP Enable Disable Auto Changeover mode default Enable Auto Changeover Time may be adjusted 5 to 120 minutes default 30 minutes When Auto mode is enabled factory default a change from heat to cool or vice versa will not occur until an opposite mode demand has exist...

Page 9: ...lt LOW HIGH Controls the staging of the furnace SYSTEM setting will allow the Infinity Zone Control to determine furnace staging LOW will only run the low stage of furnace heat HIGH will only run the high stage of furnace heat OFF DELAY 90 seconds 120 seconds default 150 seconds 180 seconds Amount of time the blower will continue to run after heating has shut off LOCKOUT TEMP NONE default 5 to 55 ...

Page 10: ...ault 90 Interval at which the Clean Ventilator Pre filter notification will turn on UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed Setup SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adj...

Page 11: ... room sensor is disconnected the Zone 2 damper will now open as indicated on the User Interface display The word FAIL will also be displayed instead of the actual temperature for Zone 2 Reconnect Zone 2 sensor and try all remaining sensors one at a time in the system Smart Sensors may also be checked see Smart Sensor Installation Instructions for procedure AIRFLOW LIMITS Low Medium High default Ma...

Page 12: ...vered to each zone Damper position range from 0 to 15 0 closed 15 open Service LAST 10 SYSTEM FAULTS This screen will show last 10 faults that occurred throughout the system Each fault has the time and date incident recorded Service technician should enter current date in TODAY S DATE menu section BEFORE checking and logging the last 10 system faults Each fault has a two letter acronym preceding t...

Page 13: ...um On Time In normal operation when a stage turns on it will remain on for a minimum of three minutes If the set point is changed this timer is automatically cancelled allowing the equipment to turn off imme diately when the demand is removed Heat Cool Set points Desired Temperatures A minimum difference of 2 default is enforced between heating and cooling desired temperatures This is done by allo...

Page 14: ...sts between the actual room temperature and operating set point yet the equipment does not turn on 1 The zone airflow limit may be set too low Perform the Zone Airflow Limit Checkout procedure raise airflow limit setting if possible Some zones provide too much airflow and are noisy 1 The zone airflow limit may be set too high Perform the Zone Airflow Limit Checkout procedure lower airflow limit se...

Page 15: ...le NIM communication fault Defrost Error defrost signal on for more than 15 minutes The user can press the right side button to dismiss the notice The regular run mode screen will then appear except SYSTEM MALFUNCTION will appear in place of the day time If the error has not disappeared within 24 hours the above display will return If the error code disappears SYSTEM MALFUNCTION will disappear and...

Page 16: ...231 uiz01 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab misc misc PC 101 Catalog No 809 50025 Printed in U S A Form UIZ01 1SI Pg 16 03 04 Replaces NEW ...

Reviews: