background image

LOCKOUT TIMER:

Seconds

If a lockout timer is active, this will show the current time value.
See furnace manual for details on lockout timers.

Service = FAN COIL STATUS

ELECTRIC HEAT:

OFF, LOW, MED, HIGH

Displays stages of electric heat that the fan coil is currently
delivering.

AIRFLOW CFM:

(fan coil model number dependent)

Cubic Feet per Minute of air the blower is currently delivering.

LEAVING AIR TEMP:

This sensor is NOT required. However, if LAT sensor is
connected to the Damper Control Module, the sensor will read
leaving air temperature of the fan coil.

COIL TEMP:

This sensor is NOT required. However, if HPT sensor is
connected to the Damper Control Module, the sensor will read
temperature at that location (i.e. if placed down stream from
evaporator coil, and before electric heat, will read coil leaving air
temperature).

BLOWER RPM:

Blower motor RPM value

STATIC PRESS:

Inches of water

Displays static pressure that the fan coil is currently experiencing.

Service = HEAT PUMP / AC STATUS

STAGE: (HEAT / COOL):

OFF, LOW, HIGH

Displays stage of heating or cooling that the Heat Pump/AC is
delivering.
DEFROST:

NO, YES

Displays status of defrost mode if heat pump.

AIRFLOW CFM:

Indoor unit CFM measurement.

LEAVING AIR TEMP:

This sensor is NOT required. However, if LAT sensor is
connected to the Damper Control Module, sensor will read leaving
air temperature of the indoor unit.

COIL TEMP (outdoor unit):

Degrees F.

Temperature of the outdoor unit coil (only available on 2-speed
communicating outdoor units).

BLOWER RPM:

RPM feedback from indoor motor.

STATIC PRESS:

Static pressure of indoor unit.

Service = ZONING STATUS

ZONE STATUS:

This screen will show each zone in the system with the corre-
sponding damper position (POS), and CFM being delivered to
each zone. Damper position range from 0 to 15 (0=closed,
15=open).

Service = LAST 10 SYSTEM FAULTS

This screen will show last 10 faults that occurred throughout the
system. Each fault has the time and date incident recorded. Service
technician should enter current date in

TODAY’S DATE

menu

section BEFORE checking and logging the last 10 system faults.
Each fault has a two-letter acronym preceding the fault name to
identify which piece of equipment generated the fault. This fault
history can be cleared under Thermostat Setup, Reset Factory
Defaults.

HP = heat pump

AC = air conditioner

FN = furnace

FC = fan coil

ZO = zoning

Service = RUN / FAULT HISTORY

The indoor unit and outdoor unit (if communicating) have the
following histories:

NOTE:

For Critical Fault Screens, see Troubleshooting section in

this document.

Resettable Faults:

Fault counters for each piece of equipment that can be reset.

Cycle Counters:

Number of heat/cool/power cycles the unit has performed.

Run Times:

Lifetime hours of operation in heating, cooling, and how long
the unit has been powered.

Service = TODAY’S DATE

This menu item allows the installer to enter the current date. It
is used for time/date stamping of system faults. This should be
entered every time prior to viewing

LAST 10 SYSTEM

FAULTS

section.

Service = MODEL / SERIAL NUMBERS

This menu item allows the installer to view the model number
and serial number (if available) of all communicating pieces of
equipment in the system.

Service = SERVICE PHONE NUMBER

This menu item allows the installer to enter a name and phone
number that the homeowner can call for future service of the
system. This name and phone number will appear to the home-
owner whenever a service reminder pop-up message is displayed
(i.e. Change Filter, etc.)

To edit:

Use Temp +/- button to move cursor left and right.

Use Time +/- button to select numbers and letters.

Use Scroll button to move up and down between NAME and
NUMBER.

12

Summary of Contents for Infinity SYSTXCCUIZ01

Page 1: ...or fan coils are variable speed and multi stage for maximum flexibility efficiency and comfort They support controlled ventilation humidification dehumidification and air quality control Either an Infinity dual capacity communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the Infinity furnace or fan coil provides the 24 volt signals needed to...

Page 2: ...te Room Sensor has priority over the Smart Sensor WIRING CONSIDERATIONS Ordinary thermostat wire is recommended Use 22 AWG or larger for normal wiring applica tions Continuous wire lengths over 100 ft should use 20 AWG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or brok...

Page 3: ...re to follow this warning could result in personal injury or death Before installing Infinity Zone Control turn off all power to equipment There may be more than one power source to disconnect 1 Turn off all power to equipment 2 If an existing User Interface or control is being replaced a Remove existing control from wall b Disconnect wires from existing control Fig 2 Infinity Zone Control A03185 ...

Page 4: ...eaks can affect operation 10 Attach Infinity Zone Control to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on 11 Perform installation of all other system equipment i e zone sensors dampers humidifier ventilator UV lights etc 12 Turn on power to equipment EQUIPMENT WIRING DIAGRAMS See wiring diagrams Fig 12 13 and 1...

Page 5: ...to become familiar with key function buttons such as System On Off Zone Fan Left Side and Right Side buttons etc These function buttons will be used frequently during setup SECTION 1 POWER UP SEQUENCE This section addresses initial power up or commissioning of a new Infinity Zone Control The User Interface will communi cate and identify all Infinity components in the system The following is a typi...

Page 6: ...IGHTS INSTALLED See Fig 18 Use either Time or Temp buttons to make appropriate selections in the highlighted area on the display screen Press right side button to continue or advance to the next screen AIR FILTER TYPE This accessory screen will appear first The installer will need to enter the type of filter MEDIA EAC or both See Table 1 and make a selection using Time or Temp button then press ri...

Page 7: ...irmed when the red LED next to the red HEAT button is lit 2 Use the TEMP button to select your desired heating temperature 3 The default time for temporarily overriding the temperature schedule is 2 00 HRS as indicated by the text on the lower left NOTE Override time will not appear if programming has been turned off 4 You can change the temporary override time in 15 minute increments by pressing ...

Page 8: ...t configuration made by dip switches Fig 23 shows all the information that can be found in the SETUP menu Setup THERMOSTAT AUTO MODE SETUP Enable Disable Auto Changeover mode default Enable Auto Changeover Time may be adjusted 5 to 120 minutes default 30 minutes When Auto mode is enabled factory default a change from heat to cool or vice versa will not occur until an opposite mode demand has exist...

Page 9: ...lt LOW HIGH Controls the staging of the furnace SYSTEM setting will allow the Infinity Zone Control to determine furnace staging LOW will only run the low stage of furnace heat HIGH will only run the high stage of furnace heat OFF DELAY 90 seconds 120 seconds default 150 seconds 180 seconds Amount of time the blower will continue to run after heating has shut off LOCKOUT TEMP NONE default 5 to 55 ...

Page 10: ...ault 90 Interval at which the Clean Ventilator Pre filter notification will turn on UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed Setup SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adj...

Page 11: ... room sensor is disconnected the Zone 2 damper will now open as indicated on the User Interface display The word FAIL will also be displayed instead of the actual temperature for Zone 2 Reconnect Zone 2 sensor and try all remaining sensors one at a time in the system Smart Sensors may also be checked see Smart Sensor Installation Instructions for procedure AIRFLOW LIMITS Low Medium High default Ma...

Page 12: ...vered to each zone Damper position range from 0 to 15 0 closed 15 open Service LAST 10 SYSTEM FAULTS This screen will show last 10 faults that occurred throughout the system Each fault has the time and date incident recorded Service technician should enter current date in TODAY S DATE menu section BEFORE checking and logging the last 10 system faults Each fault has a two letter acronym preceding t...

Page 13: ...um On Time In normal operation when a stage turns on it will remain on for a minimum of three minutes If the set point is changed this timer is automatically cancelled allowing the equipment to turn off imme diately when the demand is removed Heat Cool Set points Desired Temperatures A minimum difference of 2 default is enforced between heating and cooling desired temperatures This is done by allo...

Page 14: ...sts between the actual room temperature and operating set point yet the equipment does not turn on 1 The zone airflow limit may be set too low Perform the Zone Airflow Limit Checkout procedure raise airflow limit setting if possible Some zones provide too much airflow and are noisy 1 The zone airflow limit may be set too high Perform the Zone Airflow Limit Checkout procedure lower airflow limit se...

Page 15: ...le NIM communication fault Defrost Error defrost signal on for more than 15 minutes The user can press the right side button to dismiss the notice The regular run mode screen will then appear except SYSTEM MALFUNCTION will appear in place of the day time If the error has not disappeared within 24 hours the above display will return If the error code disappears SYSTEM MALFUNCTION will disappear and...

Page 16: ...231 uiz01 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab misc misc PC 101 Catalog No 809 50025 Printed in U S A Form UIZ01 1SI Pg 16 03 04 Replaces NEW ...

Reviews: