Step 4

Wiring

a. Ensure power has been removed from the heating and

cooling system.

b. Turn the Infinity

t

Air Purifier power switch off.

c. Connect the power cord and the flow sensor cord to the

power supply connector and the flow sensor connector

(see Fig. 7 and Fig. 8).

NOTE

: The power cord can be routed through the opposite side

of the cabinet. Zip ties have been enclosed to secure the power
cord to the side of the power supply.

NOTE

: Cable connector and block--off plates will need to be

removed and re--installed if the power cord is re--routed. Screws
on the cable connector clamp should be tightened to 9 in. -- lbs.
torque.

NOTE

:

The Infinity

t

Air Purifier is to be powered by

208/230Vac/60 Hz.

NOTE

: The Infinity

t

Air Purifier should only be powered

when airflow is present. An airflow sensor is factory--installed
(See Fig. 2 and Fig. 11). In order to bypass the airflow sensor,
use the special bypass jumper included in the parts bag. With the
bypass jumper in place, the air purifier will be on at all times
when connected to electrical line power (see Fig. 10).

d. Attach the quick connect terminals to the fused power

connector leads (in parts bag attached to power cord) and

connect to incoming field power. Attach the ground ring

to fan coil chassis ground. (See Fig. 10.)

ELECTRICAL

SHOCK

AND

HIGH

VOLTAGE

HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than 1 disconnect

switch.

!

WARNING

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
This unit cannot be powered directly from blower motor

leads. Do not wire directly to blower motor. Wiring to

blower motor will damage power supply and void

warranty.

CAUTION

!

A06414

Fig. 7

---

Flow Sensor Cable Installed

A06413

Fig. 8

---

Power Cord Installed

AIR FLOW SENSOR CABLE OR AIR FLOW

SENSOR BYPASS PLUG MUST BE CONNECTED

TO THE POWER SUPPLY IN ORDER TO

ACTIVATE THE AIR PURIFIER

NOTICE

A06670

Fig. 9

---

Airflow Sensor Bypass Plug Installed

GAP

A

B

Summary of Contents for INFINITY 1620

Page 1: ...ified for shock and electrical fire hazard only La Infinityt Air Purifier certification CSA vise uniquement les risques de choc electrique et A06377 Fig 1 GAPAB Unit SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installe...

Page 2: ...1 x1 x2 x3 x1 x2 Installation Components in bag attached to power cord Installation Manual 1 GAPA Infinity Air Purifier Sizes 1620 2020 2420 Installation Start up and Operating Instructions NOTE Readth eentireinstruct ion manual befores tartingth e install TABLE OF CONTE NTS Pa ge SAFETY CONSID ERA TIONS 1 INTROD UCTION 2 PLANN ING 2 5 Applica tion 2 Ins tallation Require ments 2 Dimens ions Table...

Page 3: ...urifier or door can be rotated 180_ to accommodate the cabinet orientation c The location of the Infinityt Air Purifier should be readi ly accessible Enough room should be provided for peri odic replacement of the air purifier cartridges ELECTRICAL SHOCK AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Only a trained experienced service person should i...

Page 4: ... work See Fig 6 h Seal seams with tape or caulking after the Infinityt Air Purifier cabinet has been secured ELECTRICAL SHOCK AND HIGH VOLTAGE HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be more than 1 disconnect switch WARNING UNIT DAMAGE HAZARD Failure to follow this caution ma...

Page 5: ...g With the bypass jumper in place the air purifier will be on at all times when connected to electrical line power see Fig 10 d Attach the quick connect terminals to the fused power connector leads in parts bag attached to power cord and connect to incoming field power Attach the ground ring to fan coil chassis ground See Fig 10 ELECTRICAL SHOCK AND HIGH VOLTAGE HAZARD Failure to follow this warni...

Page 6: ...POWER CONNECTION TO L2 FIELD POWER SUPPLY TO L1 FIELD POWER SUPPLY 5 AMP IN LINE FUSES GROUND ATTACH TO FAN COIL GROUND CHASSIS CABLE CONNECTOR TO SECURE POWER CORD TO FAN COIL CABINET A06515 Fig 10 Fan Coil Chassis Ground Air Flow Sensor 1 Slide flow sensor tabs into support bracket 2 Rotate flow sensor and clip into bracket A06412 Fig 11 Flow Sensor Install GAPAB ...

Page 7: ...r the TrueSenset dirty filter algorithm or time The installer should use their discretion to select the most appropriate option based on the initial system static pressure Step 3 Maximizing Performance a Maximum air purification performance is obtained when the furnace blower is set for continuous operation on the thermostat or Infinity Control Door Switch Magnet A06379 Fig 12 Door Switch Magnet P...

Page 8: ...ate protective clothing and gloves when handling parts WARNING Step 6 Slide out the Safety Screen and set aside NOTE Best cleaning tools 5 inch handle paint brush with 2 inch width or greater brush point synthetic or natural bristle See Fig 14 or vacuum cleaner with brush attachment Step 7 Gently stroke the ionization pins on the top plane of each bar with enough brush depth to hit front and back ...

Page 9: ...tion Step 3 Confirm that the fan coil blower is operating Step 4 Confirm that 208 230 VAC power is provided Attach power supply connector to the air purifier when the fan coil blower is operating NOTE Even though power is supplied to the Infinityt Air Purifier it will not turn on unless the airflow sensor senses airflow or the airflow sensor s bypass plug is inserted Step 5 Confirm that the airflo...

Page 10: ...imum Airflow CFM 1350 1800 2000 Efficiency Equivalent to MERV 15 Equivalent to MERV 15 Equivalent to MERV 15 Replacement Cartridge GAPCCCAR1620 GAPCCCAR2020 GAPCCCAR2420 Initial Pressure Drop in w c at maximum airflow 22 25 22 Dimensions GAPABXCC1620 GAPABXCC2020 GAPABXCC2420 A 18 1 2 22 25 1 2 B 15 1 8 18 5 8 22 1 8 C 13 1 8 13 1 8 13 1 8 D 17 5 8 21 1 8 24 5 8 E 19 3 4 19 3 4 19 3 4 F 22 1 4 22 ...

Page 11: ...a registered servicing dealer for credit 4 All work shall be performed during normal working hours LIMITATIONS OF WARRANTIES ALL IMPLIED WARRANTIES AND OR CONDITIONS INCLUDING IMPLIED WARRANTIES OR CON DITIONS OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY OR CONDITION IS GIVEN AND APPLIES SOME STATES OR PROVINCES...

Page 12: ... W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No GAPAB 2SI Replaces GAPAB 1SI Printed in U S A Edition Date 02 07 GAPAB ...

Reviews: