TROUBLESHOOTING

SAFETY HAZARD

Failure to follow this caution may result in personal injury

or equipment damage.
The following instructions are for use by qualified

personnel only.

CAUTION

!

ELECTRICAL SHOCK AND HIGH VOLTAGE

HAZARD

Failure to follow this warning could result in personal injury

or death.
The following procedures will expose electrical components.

Disconnect power between checks and proceed carefully.

!

WARNING

The Infinity

t

Air Purifier is equipped with a power indicator

light located on the door (see Fig. 13). This power indicator light

will illuminate when the Infinity

t

Air Purifier door is installed,

the power switch is in the on position, AND the fan coil blower is

running and airflow is sensed. If the power indicator light is not

illuminated, follow the troubleshooting steps below.

Step 1

Check that the Infinity

t

Air Purifier door is installed.

NOTE

: A magnet in the door (see Fig. 8) is used to activate a

safety switch in the power supply when the door is installed. The
power supply will not energize the air purifier unless the safety
switch is activated.

Step 2

Check that the Infinity

t

Air Purifier power switch is in

the on (closed) position.

Step 3

Confirm that the fan coil blower is operating.

Step 4

Confirm that 208/230 VAC power is provided. Attach

power supply connector to the air purifier when the fan coil
blower is operating.

NOTE

: Even though power is supplied to the Infinity

t

Air

Purifier, it will not turn on unless the airflow sensor senses
airflow or the airflow sensor’s bypass plug is inserted.

Step 5

Confirm that the airflow sensor cable or airflow sensor

bypass plug is connected to the power supply (See Fig. 7).

Step 6

If still not functioning, disconnect the airflow sensor

cable and the power cord from the power supply.
Remove the enhancement module from the air purifier cabinet
and inspect the airflow sensor (See Fig. 11).
Confirm the airflow sensor is properly seated in its bracket and
the airflow sensor cable is connected to the back of the sensor.
Replace the enhancement module.

Step 7

Reconnect the power cord to the power supply and

insert the airflow sensor disable jumper (from parts bag).
If the power indicator light illuminates, then replace the airflow
sensor.
Install the door onto the air purifier and turn the power switch to
the “ON” position.

Step 8

If all of the above steps are completed and the power

indicator light is still not illuminating, replace the power supply
on the enhancement module. Note that there are no serviceable
parts within the power supply.

GAP

A

B

Summary of Contents for INFINITY 1620

Page 1: ...ified for shock and electrical fire hazard only La Infinityt Air Purifier certification CSA vise uniquement les risques de choc electrique et A06377 Fig 1 GAPAB Unit SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installe...

Page 2: ...1 x1 x2 x3 x1 x2 Installation Components in bag attached to power cord Installation Manual 1 GAPA Infinity Air Purifier Sizes 1620 2020 2420 Installation Start up and Operating Instructions NOTE Readth eentireinstruct ion manual befores tartingth e install TABLE OF CONTE NTS Pa ge SAFETY CONSID ERA TIONS 1 INTROD UCTION 2 PLANN ING 2 5 Applica tion 2 Ins tallation Require ments 2 Dimens ions Table...

Page 3: ...urifier or door can be rotated 180_ to accommodate the cabinet orientation c The location of the Infinityt Air Purifier should be readi ly accessible Enough room should be provided for peri odic replacement of the air purifier cartridges ELECTRICAL SHOCK AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Only a trained experienced service person should i...

Page 4: ... work See Fig 6 h Seal seams with tape or caulking after the Infinityt Air Purifier cabinet has been secured ELECTRICAL SHOCK AND HIGH VOLTAGE HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be more than 1 disconnect switch WARNING UNIT DAMAGE HAZARD Failure to follow this caution ma...

Page 5: ...g With the bypass jumper in place the air purifier will be on at all times when connected to electrical line power see Fig 10 d Attach the quick connect terminals to the fused power connector leads in parts bag attached to power cord and connect to incoming field power Attach the ground ring to fan coil chassis ground See Fig 10 ELECTRICAL SHOCK AND HIGH VOLTAGE HAZARD Failure to follow this warni...

Page 6: ...POWER CONNECTION TO L2 FIELD POWER SUPPLY TO L1 FIELD POWER SUPPLY 5 AMP IN LINE FUSES GROUND ATTACH TO FAN COIL GROUND CHASSIS CABLE CONNECTOR TO SECURE POWER CORD TO FAN COIL CABINET A06515 Fig 10 Fan Coil Chassis Ground Air Flow Sensor 1 Slide flow sensor tabs into support bracket 2 Rotate flow sensor and clip into bracket A06412 Fig 11 Flow Sensor Install GAPAB ...

Page 7: ...r the TrueSenset dirty filter algorithm or time The installer should use their discretion to select the most appropriate option based on the initial system static pressure Step 3 Maximizing Performance a Maximum air purification performance is obtained when the furnace blower is set for continuous operation on the thermostat or Infinity Control Door Switch Magnet A06379 Fig 12 Door Switch Magnet P...

Page 8: ...ate protective clothing and gloves when handling parts WARNING Step 6 Slide out the Safety Screen and set aside NOTE Best cleaning tools 5 inch handle paint brush with 2 inch width or greater brush point synthetic or natural bristle See Fig 14 or vacuum cleaner with brush attachment Step 7 Gently stroke the ionization pins on the top plane of each bar with enough brush depth to hit front and back ...

Page 9: ...tion Step 3 Confirm that the fan coil blower is operating Step 4 Confirm that 208 230 VAC power is provided Attach power supply connector to the air purifier when the fan coil blower is operating NOTE Even though power is supplied to the Infinityt Air Purifier it will not turn on unless the airflow sensor senses airflow or the airflow sensor s bypass plug is inserted Step 5 Confirm that the airflo...

Page 10: ...imum Airflow CFM 1350 1800 2000 Efficiency Equivalent to MERV 15 Equivalent to MERV 15 Equivalent to MERV 15 Replacement Cartridge GAPCCCAR1620 GAPCCCAR2020 GAPCCCAR2420 Initial Pressure Drop in w c at maximum airflow 22 25 22 Dimensions GAPABXCC1620 GAPABXCC2020 GAPABXCC2420 A 18 1 2 22 25 1 2 B 15 1 8 18 5 8 22 1 8 C 13 1 8 13 1 8 13 1 8 D 17 5 8 21 1 8 24 5 8 E 19 3 4 19 3 4 19 3 4 F 22 1 4 22 ...

Page 11: ...a registered servicing dealer for credit 4 All work shall be performed during normal working hours LIMITATIONS OF WARRANTIES ALL IMPLIED WARRANTIES AND OR CONDITIONS INCLUDING IMPLIED WARRANTIES OR CON DITIONS OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY OR CONDITION IS GIVEN AND APPLIES SOME STATES OR PROVINCES...

Page 12: ... W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No GAPAB 2SI Replaces GAPAB 1SI Printed in U S A Edition Date 02 07 GAPAB ...

Reviews: