Page 3

9.

Install power wiring and connect to power block or circuit
breakers.  In 12, 15 or 20kW models two power circuits
may be used to reduce wiring and breaker costs as in
Figure 7a.  If a single circuit supply is desired, install the
optional single circuit accessory kit, as shown in Figure 7b,
that can be obtained from your Carrier distributor.

10. Check unit CFM of Table 1 and ensure airflow setting is

above minimum airflow rating for the electric heat model
from Table 2. Low speed blower not allowed with
electric heat.

11. Check staging jumpers for the application.  Typically only

5 kW (factory setting on all models except 10kW on 20kW
models)  is needed for first stage electric (W1) to minimize
electric demand.  This staging can be adjusted by moving
the staging jumpers as shown in Figure 8.

12. Mark the appropriate box of the electric heat model

installed on the additional serial plate on the exterior of the
unit.

13. Turn on the power to the unit and the auxiliary electric

heat.

Auxiliary Electric Heat Start-up

14. Run thermostat to emergency heat mode  (or jumper t-stat

input R to W) and setpoint to high setting.  ‘Touch-jumper'
the test pins of the CXM or DXM into test mode to reduce
time delays.  Unit will require 15-20 seconds before
engaging emergency heat mode stage 1 (W1) and then
another 15-20 seconds to engage stage 2 (W2) when in
‘Test mode’.  Verify proper electric heat operation.

NO

Com

ER1

NO

Com

ER2

NO

Com

ER3

NO

Com

ER4

1

2

3

Tan

Ora

Factory Staging 
(see Table 2)

Low Voltage Connector 
(from Unit Control Board)

Genesis Electric 

Heat Relay Board

P1

P2

24V

W1

W2

4

Staging Example on a 15kW unit W1 (first stage) has 
5kW (‘ER1’ 5kW & ‘ER4’ 0kW) and W2 (second stage) 
will have 10kW (‘ER2 & 3’ 5kW each)

1

2

3

4

Tan

Ora

P2

Side View as seen in Control Box

P1

Figure 8.  Staging Jumpers

Table 1.  GT-G PSC Blower Performance Table

GT-G Electric

Heat Relay Board

GT-G 

Series 

Fan 

Airflow (cfm) at External Static Pressure (in. wg)

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

5 0 Y C G

Future Product - Data Not Available

5 0 Y C G

Future Product - Data Not Available

H

781

771

764

757

748

740

718

697

665

638

610

-

-

-

-

5 0 Y C G

M

739

719

710

702

688

675

658

641

619

598

-

-

-

-

-

L*

626

613

605

597

589

581

566

551

531

512

-

-

-

-

-

H

781

771

764

757

748

740

718

697

665

638

610

-

-

-

-

5 0 Y C G

M

739

719

710

702

688

675

658

641

619

598

-

-

-

-

-

L*

626

613

605

597

589

581

566

551

531

512

-

-

-

-

-

H

1066

1038

1010

983

954

926

900

874

838

803

707

-

-

-

-

5 0 Y C G

M

902

886

870

854

831

809

782

756

726

702

-

-

-

-

-

L*

797

779

761

738

726

709

683

657

634

606

-

-

-

-

-

H

1173

1152

1125

1104

1081

1058

1033

1007

984

955

841

-

-

-

-

5 0 Y C G

M

1085

1061

1037

1013

975

938

916

894

864

830

-

-

-

-

-

L*

939

924

909

894

871

853

827

802

779

752

-

-

-

-

H

1358

1330

1291

1258

1225

1198

1162

1132

1094

1057

965

858

-

-

-

5 0 Y C G

M

1216

1193

1166

1143

1112

1082

1050

1023

982

941

-

-

-

-

-

L*

1069

1059

1049

1039

1021

999

975

952

925

899

-

-

-

-

-

H

-

-

1780

1700

1622

1612

1580

1544

1491

1434

1343

1211

-

-

-

5 0 Y C G

M

1546

1524

1502

1480

1450

1426

1396

1371

1333

1294

-

-

-

-

-

L*

1217

1205

1193

1181

1168

1156

1128

1100

1063

1031

-

-

-

-

-

H

-

-

1893

1851

1807

1768

1718

1664

1630

1596

1454

1322

1195

-

-

5 0 Y C G

M

1744

1699

1664

1624

1578

1532

1498

1468

1419

1376

-

-

-

-

-

L*

1362

1336

1314

1298

1275

1252

1219

1187

1152

1112

-

-

-

-

-

H

-

-

-

-

2222

2197

2167

2137

2106

2076

2019

1941

1839

1705

1641

5 0 Y C G

M

2135

2113

2090

2068

2045

2022

2004

1981

1950

1924

1871

1869

-

-

-

L*

1909

1890

1876

1862

1841

1825

1803

1787

1762

1733

-

-

-

-

-

H

-

-

-

-

2501

2477

2439

2400

2370

2345

2275

2205

2061

1921

1779

5 0 Y C G

M

2465

2432

2403

2380

2353

2331

2304

2278

2250

2223

2158

2076

-

-

-

L*

2132

2117

2107

2092

2069

2052

2031

2001

1976

1940

-

-

-

-

-

Includes allowance for wet coil and clean factory-installed filter

Factory settings are indicated in bold print

(-)  operation not recommended 

* Electric Heat operation not allowed with blower motor set at low speed