G e n e s i s

Supply

Heater  Amps

Min Circ Ampacity

Max  Fuse

Supply Wire

Electric Heat Model

Circuit

2 4 0 V

2 0 8 V

2 4 0 V

2 0 8 V

2 4 0 V

2 0 8 V

Min AWG

Max  Ft

AGS4 or AGSH4

Single

15.8

13.7

19.8

17.1

20

20

12

50

AGM5 or AGMH5

Single

20.0

17.3

25.0

21.6

25

25

10

70

AGM8 or AGMH8

Single

31.7

27.5

39.6

34.4

40

35

8

70

AGM10 or AGMH10

Single

40.0

34.7

50.0

43.4

50

45

6

90

Single

47.5

41.2

59.4

51.5

60

60

6

70

AGM12 or AGMH12

Dual - L1/L3

31.7

27.5

39.6

34.4

40

35

8

70

Dual - L2/L4

15.8

13.7

19.8

17.1

20

20

12

50

AGL10 or AGLH10

Single

40.0

34.7

50.0

43.4

50

45

6

80

Single

60.0

52.0

75.0

65.0

80

70

6

50

AGL15 or AGLH15

Dual - L1/L3

40.0

34.7

50.0

43.4

50

45

6

80

Dual - L2/L4

20.0

17.3

25.0

21.6

25

25

10

70

Single

80.0

69.3

100.0

86.6

100

90

2

100

AGL20 or AGLH20

Dual - L1/L3

40.0

34.7

50.0

43.4

50

45

6

80

Dual - L2/L4

40.0

34.7

50.0

43.4

50

45

6

80

All heaters rated single phase 208-240V  60 Hz

Wire length based on one way measurement with 2% voltage drop

Wire size based on 90°C copper conductor

Part numbers with "H" included are for horizontal units only

All models 12kW or larger feature internal circuit breakers 

Genesis Auxiliary

Gensis Model Compatibility (shaded)

kW Rating (kW)

Btuh Rating (Btuh)

Minimum

Electric Heat Model

009 012 015 018 024 030 036 042 048 060 070

240V

208V

240V

208V

CFM 

Required

AGS4 or AGHS4

3.8

2.9

12900

9700

250

AGM5 or AGMH5

4.8

3.6

16300

12300

500

AGM8 or AGMH8

7.6

5.7

25900

19400

650

AGM10 or AGMH10

9.6

7.2

32700

24600

650

AGM12 or AGMH12

11.4

8.6

38900

29200

750

AGL10 or AGLH10

9.6

7.2

32700

24600

1300

AGL15 or AGLH15

14.4

10.8

49100

36900

1350

AGL20 or AGLH20

19.2

14.4

65500

49200

1350

Note: Horizontal units rated for zero clearance  unit and 1" clearance for first three feet of duct, vertical units rated for zero clearance for 

            both unit and duct. 

Table 4.  GT-G Electric Heat Staging Options

Table 3.  GT-G Electric Heat Electrical Data

Table 2.  GT-G Electric Heat Ratings

Carrier works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without
notice and may not be as described herein. Please contact Carrier’s Customer Service Department at 1-405-745-6620 for specific information on the
current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain
between the parties, but are merely Carrier’s opinion or commendation of its products.

7300 S.W. 44th Street

 Oklahoma City, OK 73179

Phone: 405-745-6000

FAX: 405-745-2051

www.Carrier.com

© Carrier 1999

*97B0005N01*

97B0005N01

G e n e s i s

S t a g i n g

F a c t o r y

Staging in kW

Auxiliary Electric 

O p t i o n s

S e t t i n g

Jumper 1-4, 2-3†

Jumper 1-3, 2-4

Jumper  1-2-3

Heat Model

Stage 1

Stage 1

Stage 2

Stage 1

Stage 2

Stage 1 Stage 2

AGS4 or AGSH4

4

4

4

0

4

0

4

0

AGM5 or AGMH5

5

5

5

0

5

0

5

0

AGM8 or AGMH8

4 or 8

4

4

4

4

4

8

0

AGM10 or AGMH10

5 or 10

5

5

5

5

5

10

0

AGM12 or AGMH12

4, 8 or 12

4

4

8

8

4

12

0

AGL10 or AGLH10

5 or 10

5

5

5

5

5

10

0

AGL15 or AGLH15

5,10 or 15

5

5

10

10

5

15

0

AGL20 or AGLH20

5,10, 15 or 20

10

10

10

10

10

15

5

Part numbers with "H" included are for horizontal units only
† Factory jumper setting

®