8--2
T--311
CLOSE-UP VIEW
COIL FINS
Figure 1-11 Micro-Channel Style Condenser Assembly
Table 8-2 SPLIT SYSTEM REFRIGERANT AND OIL CHARGING TABLE (GEN--5)
Evaporator
GEN 5
Condenser
All Series
Recommended
R134a Charge
Recommended
Oil Charge*
GEN 5 - EM-1
CM-2 or CM-4
4.75 Pounds
9.5 Ounces
GEN 5 - EM-1
CM-11
5.00 Pounds
10.0 Ounces
GEN 5 - EM-1
CM-3
5.25 Pounds
10.5 Ounces
GEN 5 - EM-1
CM-7
6.25 Pounds
12.5 Ounces
GEN 5 - EM-7
CM-2 or CM-4
4.00 Pounds
8.0 Ounces
GEN 5 - EM-7
CM-11
4.25 Pounds
8.5 Ounces
GEN 5 - EM-2
CM-2 or CM-4
4.50 Pounds
9.0 Ounces
GEN 5 - EM-2
CM-11
4.75 Pounds
9.5 Ounces
GEN 5 - EM-2
CM-3
5.00 Pounds
10.0 Ounces
GEN 5 - EM-2
CM-7
6.00 Pounds
12.0 Ounces
Table 8-3 SPLIT--SYSTEM GEN--5 WITH MICRO--CHANNEL CONDENSER
Evaporator
Condenser
Micro--Channel
Recommended
R134a Charge
Recommended
Oil Charge
EM--1, EM--9, IW--1
CM--2
3.25 Pounds
6.5 Ounces
EM--1, EM--9, IW--1
CM--3
3.75 Pounds
7.5 Ounces
EM--2, IW--2
CM--2
3.00 Pounds
6.0 Ounces
EM--2, IW--2
CM--3
3.50 Pounds
7.0 Ounces
EM--7, IW--14
CM--2
2.75 Pounds
5.0 Ounces
EM--7, IW--14
CM--3
3.00 Pounds
6.0 Ounces
EM--3 (dual loop)
(2) CM--3
4.50 Pounds (each)
9.0 Ounces (each)
After determining the
approximate charge
using the above tables, refer to “System Performance Chart” (Table 8-5)
to determine if the correct charge has been obtained.
The data listed in Table 8-1 trough Table 8-3 is based on a 20 foot liquid line. Increase the charge by 0.5 pound for each
additional 10 feet of liquid line.
8.1.5 Evaporator Tie-In
.
When an after market in-dash evaporator is added to a standard system the refrigerant charge will increase by
approximately 1 pound.
If attempting to use a CM-2 condenser with a tie-in call Carrier Transport Air conditioning technical support for an
application review.