5--4
T--311
Mounting Screw
Mounting Screw
Figure 5-9 Relay Boards Installed Inside Bus (Dual System)
To aid you in properly mounting the electrical panel
using the pre-punched mounting holes it will be easier if
you remove the MSR relay that is blocking the mounting
hole (See Figure 5-9). After installing the relay board,
carefully place the MSR back into its connector.
Figure 5-10 Wired Relay Boards (Dual System)
Figure 5-11 Relay Boards Inside Dash Panel
5.5.3 Electrical Control Panel - Torque Values
Torque values for all Split-System electrical panels are
as follows.
1. Torque value for wire connections at the plastic circuit
breakers are:
24 In-Lbs max.
2. Plastic Breaker mounting screw torque is:
15 In-Lbs.
3. Torque value for wire connections at the plastic termi-
nal strip are:
25 In-Lbs max.
4. Terminal Strip mounting screws are:
25 In-Lbs max.