in relation to the set points, due to one of the following causes:

- lack of gas due to the breakage of a pipe or to loose hub
- clogged up filters
- solenoid valve failure
- ice in the evaporator 

The minimum and maximum temperature pressure switches and the oil pressure

switch are located inside the motor casing. Before resetting, disconnect from mains.

d) Thermistors 

- automatic resetting

These are inserted in the compressor’s coil to protect the motor from overheating

(see electrical diagram)

e) Discharge Line Thermostat

Protects the compressor from elevated discharge temperatures which can occur

in certain conditions such as low gas charge or failed condenser fan.

f) Phase sequencing relay

Is an electronic device which prevents the compressor from starting if the phases

are not connected in the correct sequence. This device can be found either in the
electrical panel or integrated in the compressor protection module.

g) Minimum and maximum tension electronic relay

(Monitor) - automatic

reset (where applicable). It is used to protect the unit against anomalies in the
power supply (+/-12% of nominal value). The unit starts with a delay of 8 minu-
tes, indicated on the panel by a LED.

The main factors that cause the triggering of the device are anomalies in the

power supply (for further information see attachment)

h) Condenser fans variable speed drive

Electronic system for checking the speed of condenser fans. 
In case of system malfunction:

- turn off at mains
- open the electric control panel
- the variable speed drive is located inside the control panel.

Move the switch to position (1)

- close the electric control panel and reset the unit
- replace the variable speed drive as soon as possible
- having replaced it, move the variable speed drive to the automatic 
position (0).

9.5 Parts subject to wear and spares

Only qualified personnel or the Manufacturer are authorised to replace worn

parts.

M

aterials such as wood, plastics, polystyrene are used in packing and must be

disposed of in compliance with local legislation.

W

hen, for whatever reason, the owner wishes to dispose of the machine and

dismantle it, it is necessary to follow some fundamental rules for protecting

human health and the environment in which we live.

Conduits, flexible tubes, plastic or non-metallic components must be disassem-

bled and disposed of separately.

Electrical components such as switches, transformers, etc. must be disassem-

bled in order to be reused if they are still in good condition, or to be reconditioned
and recycled where possible.

Pneumatic and electrical components such as valves, electrical valves, pressure

regulators must be disassembled in order to be reused if they are still in good
condition, or to be reconditioned and recycled where possible.

1111..  D

DIISSM

MAAN

NTTLLIIN

NG

G  TTH

HEE  UUN

NIITT

1111..  D

DIISSM

MAAN

NTTLLIIN

NG

G  TTH

HEE  UUN

NIITT

1100..  D

DIISSPPO

OSSAALL  O

OFF  PPAAC

CKKIIN

NG

G

1100..  D

DIISSPPO

OSSAALL  O

OFF  PPAAC

CKKIIN

NG

G

Summary of Contents for CU-S 401

Page 1: ...I IT TU UN NG G B BE ED DI IE EN NU UN NG GS SA AN NL LE EI IT TU UN NG G I IN NS ST TR RU UC CT TI IO ON NS S D D U US SA AG GE E E ET T E EN NT TR RE ET TI IE EN N I IN NS ST TR RU UC CT TI IO ON NS...

Page 2: ...SHEET SERVICEBLATT FICHE DE SERVICE FOGLIO SERVIZIO DATE DATUM OPERATION MASSNAHME SERVICE FIRM SERVICEFIRMA SIGNATURE UNTERSCHRIFT DATE DATA OPERATION OPERAZIONE ETS DE SERVICE DITTA ASSISTENZA SIGNA...

Page 3: ...power sources page 10 6 2 1 Power mains connection page 10 6 2 2 Water mains connection page 11 6 3 Checks adjustments and settings page 11 6 4 Setting of the controll and power devices page 11 7 Star...

Page 4: ...d external to the cell 2 an electrical control panel located on the condenser unit 1 1 How the unit works The units CU S are condensing parts operating by means of a sealed or semi sealed a c mains po...

Page 5: ...lectric fans against excessive current absorption 2 High pressure switch with manual resetting protects against excessively high pressure 3 Thermistors or thermostats with manual resetting protects th...

Page 6: ...TOTERMICO MAI DIRETTAMENTE ALLA LINEA PRINCIPALE CONNECTION SHOULD ALWAYS BE MADE FROM A FUSED ISOLATOR NEVER CONNECT THE CABLE TO THE MAINS SUPPLY LINE DIRECTLY LA CONNEXION DOIT ETRE EFFECTUEE AU MO...

Page 7: ...UN NI IT T 2 2 T TE EC CH HN NI IC CA AL L F FE EA AT TU UR RE ES S O OF F T TH HE E U UN NI IT T fig 4 Mod Mod Matricola Serial Number Tensione Voltage Assorb Marcia Run Absorption Refrigerante Refri...

Page 8: ...he manufacturer distributor about any contraindi cations or dangers that may derive from the incorrect use of the unit The unit can be moved with lifting and transport devices Fig 5 WARNING Take the u...

Page 9: ...rams fig 6 7 CU S one fan CU S two fans PACKING 5 5 I IN NS ST TA AL LL LA AT TI IO ON N 5 5 I IN NS ST TA AL LL LA AT TI IO ON N 1104 504 504 1254 Mod A B C Kg GCU401N F 670 1350 810 89 GCU401T F 670...

Page 10: ...s of the panel make the electrical connection Connection to the mains supply must be made through a magnetothermal differential Safety devices magnetothermal and or fused switches should be installed...

Page 11: ...wired as per the schematic or can act directly on the liquid line solenoid valve B Select preheating position on the PREHEATING STOP RUN switch supplied by others Method of connection is shown in the...

Page 12: ...ndicator located on all units this must be checked when the unit is operating and the cell temperature is close to the required temperature Normally the indicator is clear while in the absence of gas...

Page 13: ...eed of condenser fans In case of system malfunction turn off at mains open the electric control panel the variable speed drive is located inside the control panel Move the switch to position 1 close t...

Page 14: ...osed of by specialists The casing and all metal parts of the unit should be disassembled and different materials should be separately grouped The various parts thus obtained will thus be allowed to be...

Page 15: ...VALVOLA SOLENOIDE 10 THERMAL EXPANSION VALVE THERMOSTATVENTIL SOUPAPE THERMOSTATIQUE VALVOLA TERMOSTATICA 11 ELECTRO MOTOR DRIVEN FAN MOTOVENTILATOR VERD MOTOVENTILATEUR EVAP MOTOVENTIL EVAPORATORE 12...

Page 16: ...52 2 1 3 4 41 40 5 6 7 8 9 12 10 11 13 14 36 37 39 38 35 34 15 18 17 19 16 20 21 33 32 31 30 29 28 27 23 42 43 44 44 45 46 48 47 1 CUS 1 30 05 01 Righetti Tav n Modello Data Disegnatore...

Page 17: ...25 1 1 1 1 3ING026 1 21 COMP CONTACTOR KOMPRESSORFERNSCHALTER TELERUPTEUR COMP TELERUTTORE COMP 3TLR166 1 1 1 3TLR168 1 3TLR170 1 23 FAN CONTACTOR VENTILATORFERNSCHALTER TELERUPTEUR VENTIL TELERUTTORE...

Page 18: ...54 1 2 3 5 6 4 14 15 7 13 16 12 9 10 11 21 22 20 17 18 19 46 25 24 23 33 35 36 37 38 40 31 30 28 27 45 44 43 42 41 8 52 53 51 49 50 48 47 28 2 CUS 2 30 05 01 Righetti Tav n Modello Data Disegnatore...

Page 19: ...GSCHALTKASTEN FERMET SUP TABLEAU L CHIUSURA SUP Q E 2335615 1 1 1 1 1 1 1 24 ELECTRIC PANEL SCHALTTAFEL PANNEAU ELECTRIQUE QUADRO ELETTRICO 2335614 1 1 1 1 1 1 1 25 LOWERSWITCHBOARDLOCK UNTERESCHLIE U...

Page 20: ...TER DECKEL COUVERCLE FENDU COPERCHIO ASOLATO 2235609 1 1 1 1 1 1 1 45 SHROUD LUFTLEITER CONVEYEUR D AIR CONVOGLIATORE 2235612 1 1 1 1 1 1 1 46 CONDENSER FAN KONDENSATORVENTILATOR VENTILATEUR COND MOTO...

Page 21: ...57...

Page 22: ...IBILE VARIATORE VELOCITA SPEED REGULATOR FUSE FUSIBLE VARIATEUR VITESSE GESCHW REGLERSICHERUNG FUSIBLE VARIADOR VELOCIDAD FUS VEL DO VARIADOR DE VELOCIDADE F6 FUSIBILE VENTOLA CONDENSATORE CONDENSER F...

Page 23: ...EVAPORATORE EVAPORATOR FAN MOTOR MOTEUR VENTILATEUR EVAPORATEUR VERDMF VENTILATORMOTOR MOTOR VENTILADOR EVAPORADOR MOTOR VENTILADOR EVAPORADOR P1MX PRESSOSTATO INSERZIONE VENTOLACOND COND FAN STARTIN...

Page 24: ...0MAN126A 04 2 2 001...

Reviews: