2

sor when outdoor-air temperature is too cold. Demand control

ventilation is supported.

This EconoMi$er X system can be used with 1 or 2 speed

indoor fan motor units. (All other speed settings listed are for

future use.)

The EconoMi$er X system utilizes gear-drive technology

with a direct-mount spring return actuator that will close

upon loss of power. The EconoMi$er X system comes stan-

dard with fault detection and diagnostics (FDD), an outdoor

air temperature sensor, and mixed air temperature sensor (al-

so called supply air temperature sensor). Outdoor enthalpy,

indoor (return) dry bulb or enthalpy, and CO

2

 sensors are

available for field installation. 

Standard integrated barometric relief dampers provide nat-

ural building pressurization control. An optional power ex-

haust system is available for applications requiring even

greater exhaust capabilities. The power exhaust set point is

adjustable at the EconoMi$er X controller.

See Tables 1-3 for package usage. See Table 4 for package

contents. See Table 5 for sensor usage.

 

 

 

 

* Shipped in hardware kit for field installation.

HW = Honeywell

IMPORTANT: These economizers meet all the econo-

mizer requirements as specified in ASHRAE 90.1, IECC

and California’s Title 24. Economizer must be installed

square to avoid damper leakage or damper binding.

Squareness tolerance is ± 

1

/

32

 inch.

IMPORTANT: Read these instructions completely before

attempting to install the accessory economizer.

Table 1 — Carrier Usage Chart

CARRIER MODEL NUMBER ECONOMI$ER

®

 X PART NUMBER

Small Cabinet

48/50FC*04-07

48/50GC*04-06

50HCQ 04-06

50KCQ 04-06

50TCQ 04-07

48/50HC, LC 04-06

48/50KC 04-06

48/50TC 04-07

CRECOMZR067A01

Large Cabinet

48/50HC 07-12

48/50LC 07

48/50TC 08-14

50HCQ 07-09

50TCQ 08-12

CRECOMZR069A01

Extra Large Cabinet

48/50HC 14

48/50LC 08-12

48/50TC 16

50HCQ 12

50TCQ 14

CRECOMZR071A01

Table 2 — Bryant Usage Chart

BRYANT MODEL NUMBER ECONOMI$ER

®

 X PART NUMBER

Small Cabinet

548J/580J/558J 04-07

549J/547J/559J/582J 04-06

581J/551J 04-06

581K/551K 04-06

582K/559K 04-07

CRECOMZR067A01

Large Cabinet

548J 08-12

549J 07-09

580J/558J 08-14

581J/551J 07-12

CRECOMZR069A01

Extra Large Cabinet

548J 14

549J 12

580J/558J 16

581J/551J 14

CRECOMZR071A01

Table 3 — ICP Usage Chart

ICP MODEL NUMBER

ECONOMI$ER

®

 X PART NUMBER

Small Cabinet

RGH/RAH 036-060

RGS/RAS 036-072

RGV/RAV 036-072

RGW/RAW 036-060

RGX/RAX 036-060

RHX/RHH 036-060

RHS 036-072

CRECOMZR067A01

Large Cabinet

RAS/RGS 090-150

RGH/RAH 072-120

RHH 072-102

RHS 090-120

CRECOMZR069A01

Extra Large Cabinet

RAS/RGS 150

RGH/RAH 150

RHS 150

RHH 120

CRECOMZR071A01

Table 4 — Package Contents

ECONOMIZER PART 

NUMBER

QTY

CONTENTS

CRECOMZR067A01,

CRECOMZR069A01

1

EconoMi$er Damper Assembly with 

Actuator and HH79AH001 (HW: 

C7250) Outside Air Sensor

1

Jade HW63AW002 (HW: W7220) 

Controller with Attached Harness*

1

HH79AH001 (HW: C7250) Mixed Air 

Temp Sensor*

1

50HE403859 2-(green) wire harness 

for mixed air temperature sensor*

1

48TMHSRSE--A20 4-Wire Harness*

1

Hood Assembly with Top and 2 Sides

1

Hood Divider

1

Aluminum Filter

1

Hardware Bag*

CRECOMZR071A01

1

EconoMi$er Damper Assembly with 

Actuator and HH79AH001 (HW: 

C7250) Outside Air Sensor

1

Jade HW63AW002 (HW: W7220) 

Controller with Attached Harness*

1

HH79AH001 (HW: C7250) Mixed Air 

Temp Sensor*

1

50HE403859 2-(green) wire harness 

for mixed air temperature sensor*

1

48TMHSRSE--A20 4-Wire Harness*

1

Hood Assembly with Top and 2 Sides

1

Hood Divider

1

Hood Filter Divider

2

Aluminum Filters

1

Hardware Bag*

Summary of Contents for CRECOMZR067A01

Page 1: ...safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the poten tial for personal injury Understand the signal words DANGER WARNING CAU TION and NOTE The...

Page 2: ...8 50TC 04 07 CRECOMZR067A01 Large Cabinet 48 50HC 07 12 48 50LC 07 48 50TC 08 14 50HCQ 07 09 50TCQ 08 12 CRECOMZR069A01 Extra Large Cabinet 48 50HC 14 48 50LC 08 12 48 50TC 16 50HCQ 12 50TCQ 14 CRECOM...

Page 3: ...base in the re turn air chamber See Fig 4 Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dr...

Page 4: ...Harness to Unit PL6 Economizer Harness 8 Remove and save the 12 pin jumper plug from the unit economizer harness located in the upper left corner of the unit Insert the EconoMi er X plug into the unit...

Page 5: ...ee Fig 9 and page 9 Fig 9 Connect 10 pin Plugs Together 13 Connect the 10 pin female plug from the Jade controller harness to ECON on the CTB See Fig 10 and page 9 Fig 10 Connect 10 Pin Jade Plug to C...

Page 6: ...box and the indoor blower section See Fig 14 Fig 14 Route 48TMHSRSE A20 Harness to Indoor Blower Section Some control box configurations may differ 19 Screw the HH79AH001 mixed air MAT sensor Hon eywe...

Page 7: ...ween the filters Fig 17 EconoMi er X Hood Assembly Fig 18 Filter Divider on CRECOMZR071A01 Hood 23 Install aluminum filter s in EconoMi er X hood Clips at top of hood will hold filters in place See Fi...

Page 8: ...2 See base unit installation manual to make adjustments to meet building ventilation requirements See Fig 23 for typi cal EconoMi er X wiring diagram Fig 21 Barometric Relief Flow Capacity Fig 22 Retu...

Page 9: ...RA ORG YEL BLK BRN RED VIO 1 1 2 2 3 3 4 10 6 4 5 9 1 3 8 2 7 1 2 3 4 5 6 7 8 9 10 4 9 3 8 10 2 6 7 5 1 4 10 Pin Female Plug Disconnected from CTB CO2 Optional Ground W1 on CTB W7220 JADE Controller F...

Page 10: ...oller NOTE The 4 wire 48TMHSRSE A20 harness provided with the economizer will also NOT be used on the 48 50LC07 12 units see Fig 25 Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units 3 Step LC3 The...

Page 11: ...of Fig 26 on the 48LCHSRADH A00 harness attach to the unit s CSC board Connect J3 and J5 plugs to the CSC board 7 Step LC7 Screw the green wire with yellow stripe in the 48LCHSRADH A00 harness to the...

Page 12: ...d is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220...

Page 13: ...wires with a plug from the EconoMi er X har ness in the return chamber plug directly into the HH57AC081 enthalpy sensor See Fig 23 and 28 for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081...

Page 14: ...ive Director At altitudes substantially different than sea level the Fixed Enthalpy limit value shall be set to the enthalpy value at 75 F and 50 rela tive humidity As an example at approximately 6 00...

Page 15: ...acceptable to some codes is an an nunciator light visible by service personnel See Fig 34 for typical wiring to the Jade controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired...

Page 16: ...nt menu parameter 10 Press the Menu Up Exit button to return to the pre vious menu Menu Structure Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The me...

Page 17: ...10 Standard Jade W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F...

Page 18: ...d displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays m...

Page 19: ...t and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2...

Page 20: ...ON Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 t...

Page 21: ...A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux...

Page 22: ...to Minimum Damper po sition if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as...

Page 23: ...24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MI...

Page 24: ...ls If my enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset...

Reviews: