* Includes HH57AC081 sensor and wiring harness.
† Accessory CO

2

 sensors.

** Accessory aspirator boxes required for duct-mounted applications.
†† CRCBDIOX005A00 is an accessory that contains both         

33ZCSENCO2 and 33ZCASPCO2 accessories.

Accessories List 

The EconoMi$er X system has several field-installed ac-

cessories available to optimize performance. Refer to Table 6

for authorized parts and power exhaust descriptions.

* When available, or order MicroMetl PN 9901-2022-DIFF JC2.

Compliance

Economizers meet California Energy Commission Title 24

prescriptive section 140.4 (damper leakage etc.), and mandato-

ry section 120.2.i for Fault Detection and Diagnostic controls.

Economizers meet ASHRAE 90.1 damper leakage require-

ments and meet Fault Detection and Diagnosis requirements.

Economizers meet IECC damper leakage and Fault Detec-

tion and Diagnostic requirements.
NOTE: IECC requires differential return air sensor, which must

be ordered separately. See Accessory CRDIFRASN01A00.

Outside air, and return air and relief air dampers are

AMCA rated.

       

Fig. 1 — EconoMi$er

®

 X Component Locations 

(CRECOMZR067A01 Shown)

For 48/50LC 07-12 Instructions, see “Instructions for 48/50LC

07-12 Units Only” on page 10.

INSTALLATION

NOTE: If installing economizer on 48/50LC 07-12 units, see

“Instructions for 48/50LC 07-12 Units Only” on page 10.
1. Turn off unit power supply(s) and install lockout tag.
2. Remove the existing unit filter access panel. Raise the

panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. See Fig. 2.
Set the filter door aside for re-installation later.

Fig. 2 — Typical Access Panel Locations

3. Remove the indoor coil access panel and discard. See

Fig. 2.

4. Slide the EconoMi$er X assembly into the rooftop unit.

See Fig. 3.

NOTE: On small and large cabinets be sure to engage the rear

EconoMi$er X flange under the tabs on the unit base in the re-

turn air chamber. See Fig. 4.

Table 5 — EconoMi$er

®

 X Sensor Usage

APPLICATION

ECONOMI$ER X WITH OUTDOOR AIR DRY 

BULB SENSOR

Accessories Required

Outdoor Air Dry 

Bulb

HH79AH001 outdoor air dry bulb sensor is 

factory installed on economizer.

Mixed Air 

Sensor

HH79AH001 provided with economizer and field-

installed in blower compartment.

Single Enthalpy

HH57AC081

Differential Dry 

Bulb or Enthalpy

CRDIFRASN01A00* (When available, or 

MicroMetl part number 9901-2022-DIFF JC2)

CO

2

 for DCV 

Control using a 

Wall-Mounted 

CO

2

 Sensor

33ZCSENCO2

or

CGCDXSEN004A00

CO

2

 for DCV 

Control using a 

Duct-Mounted 

CO

2

 Sensor

33ZCSENCO2 or

CGCDXSEN004A00†

and

33ZCSENCO2 or

CGCDXASP00100**

OR CRCBDIOX005A00††

Table 6 — EconoMi$er

®

 2 Field-Installed 

Accessories

DESCRIPTION

PART NUMBER

208/230v 1PH Power Exhaust for 

Small Cabinet

CRPWREXH030A01

460v 3PH Power Exhaust for Small 

Cabinet

CRPWREXH021A01

208/230v 1PH Power Exhaust for 

Large Cabinet

CRPWREXH022A01

460v 3PH Power Exhaust for Large 

Cabinet

CRPWREXH023A01

208/230v 1PH Power Exhaust for 

Extra Large Cabinet

CRPWREXH080A00

460v 3PH Power Exhaust for Extra 

Large Cabinet

CRPWREXH081A01

Enthalpy Sensor (OA)

HH57AC081

Differential (Return) Sensor

CRDIFRASN01A00*

CO

2

 Sensor and Aspirator Box

CRCBDIOX005A00

Return Air CO

2

 Sensor (4 to 20 mA)

CRCBDIOX002A00

CO

2

 Room Sensor  (4 to 20 mA)

33ZCSENCO2 or

CGCDXSEN004A00

Aspirator Box for Duct Mount

CO

2

 Sensor (4 to 20 mA)

33ZCASPCO2 or

CGCDXASP001A00

Economizer Angle Seal Kit for use 

with unit's with Hinged Filter Door - 

for Small Cabinet

CRPECONV003A00

Economizer Angle Seal Kit for use 

with unit's with Hinged Filter Door - 

for Large Cabinet

CRPECONV004A00

Economizer Angle Seal Kit for use 

with unit's with Hinged Filter Door - 

for Extra Large Cabinet

CRPECONV007B00

HH79AH001
OUTSIDE AIR
TEMPERATURE 
SENSOR
(IN OPERATING
POSITION)

ACTUATOR

ECONOMI$ER X
WIRING HARNESS

OUTSIDE  
AIR DAMPER

HH79AH001 OUTSIDE AIR 
TEMPERATURE SENSOR
(IN SHIPPING POSITION)

BAROMETRIC RELIEF
DAMPERS

COMPRESSOR
ACCESS PANEL

OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL

FILTER ACCESS PANEL

Summary of Contents for CRECOMZR067A01

Page 1: ...safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the poten tial for personal injury Understand the signal words DANGER WARNING CAU TION and NOTE The...

Page 2: ...8 50TC 04 07 CRECOMZR067A01 Large Cabinet 48 50HC 07 12 48 50LC 07 48 50TC 08 14 50HCQ 07 09 50TCQ 08 12 CRECOMZR069A01 Extra Large Cabinet 48 50HC 14 48 50LC 08 12 48 50TC 16 50HCQ 12 50TCQ 14 CRECOM...

Page 3: ...base in the re turn air chamber See Fig 4 Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dr...

Page 4: ...Harness to Unit PL6 Economizer Harness 8 Remove and save the 12 pin jumper plug from the unit economizer harness located in the upper left corner of the unit Insert the EconoMi er X plug into the unit...

Page 5: ...ee Fig 9 and page 9 Fig 9 Connect 10 pin Plugs Together 13 Connect the 10 pin female plug from the Jade controller harness to ECON on the CTB See Fig 10 and page 9 Fig 10 Connect 10 Pin Jade Plug to C...

Page 6: ...box and the indoor blower section See Fig 14 Fig 14 Route 48TMHSRSE A20 Harness to Indoor Blower Section Some control box configurations may differ 19 Screw the HH79AH001 mixed air MAT sensor Hon eywe...

Page 7: ...ween the filters Fig 17 EconoMi er X Hood Assembly Fig 18 Filter Divider on CRECOMZR071A01 Hood 23 Install aluminum filter s in EconoMi er X hood Clips at top of hood will hold filters in place See Fi...

Page 8: ...2 See base unit installation manual to make adjustments to meet building ventilation requirements See Fig 23 for typi cal EconoMi er X wiring diagram Fig 21 Barometric Relief Flow Capacity Fig 22 Retu...

Page 9: ...RA ORG YEL BLK BRN RED VIO 1 1 2 2 3 3 4 10 6 4 5 9 1 3 8 2 7 1 2 3 4 5 6 7 8 9 10 4 9 3 8 10 2 6 7 5 1 4 10 Pin Female Plug Disconnected from CTB CO2 Optional Ground W1 on CTB W7220 JADE Controller F...

Page 10: ...oller NOTE The 4 wire 48TMHSRSE A20 harness provided with the economizer will also NOT be used on the 48 50LC07 12 units see Fig 25 Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units 3 Step LC3 The...

Page 11: ...of Fig 26 on the 48LCHSRADH A00 harness attach to the unit s CSC board Connect J3 and J5 plugs to the CSC board 7 Step LC7 Screw the green wire with yellow stripe in the 48LCHSRADH A00 harness to the...

Page 12: ...d is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220...

Page 13: ...wires with a plug from the EconoMi er X har ness in the return chamber plug directly into the HH57AC081 enthalpy sensor See Fig 23 and 28 for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081...

Page 14: ...ive Director At altitudes substantially different than sea level the Fixed Enthalpy limit value shall be set to the enthalpy value at 75 F and 50 rela tive humidity As an example at approximately 6 00...

Page 15: ...acceptable to some codes is an an nunciator light visible by service personnel See Fig 34 for typical wiring to the Jade controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired...

Page 16: ...nt menu parameter 10 Press the Menu Up Exit button to return to the pre vious menu Menu Structure Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The me...

Page 17: ...10 Standard Jade W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F...

Page 18: ...d displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays m...

Page 19: ...t and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2...

Page 20: ...ON Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 t...

Page 21: ...A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux...

Page 22: ...to Minimum Damper po sition if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as...

Page 23: ...24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MI...

Page 24: ...ls If my enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset...

Reviews: