20
SETPOINTS
(cont)
EXH1 H SET
50%
0 to 100%;
Increment by 1
EXHAUST FAN SETPOINT AT HIGH SPEED (on 2 speed unit)
Setpoint for OA damper position when exhaust fan is powered by the
economizer
EXH2 L SET
80%
0 to 100%;
Increment by 1
EXHAUST FAN STAGE 2 SETPOINT AT LOW SPEED
Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer. Only used when AUX1—O is set to EHX2.
NOTE: Standard power exhaust kits have only 1 speed, therefore EXH2 is
not applicable
EXH2 H SET
75%
0 to 100%;
Increment by 1
EXHAUST FAN STAGE 2 SETPOINT AT HIGH SPEED
Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer. Only used when AUX1—O is set to EHX2.
NOTE: Standard power exhaust kits have only 1 speed, therefore EXH2 is
not applicable
SYSTEM
SETUP
INSTALL
01/01/10
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG
°F
°F or °C
Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT
CONV
Conventional or
HP
Always set to CONV even for heat pump
AUX2 I
W
W required for
2-speed
mode
Always set to W
FAN TYPE
2 speed
1 speed / 2 speed Sets the economizer controller for operation of 1 speed or 2 speed indoor
fan system.
FAN CFM
5000cfm
100 to 15000 cfm;
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter ONLY if using DCVCAL ENA = AUTO
AUX OUT
NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
ERV = Energy Recovery Ventilator††
EXH2 = second damper position relay closure for second exhaust fan
SYS = use output as an FDD remote alarm signal
OCC
INPUT
INPUT or
ALWAYS
Always set to INPUT
ADVANCED
SETUP
MA LO SET
45°F
(7°C)
35° to 55°F;
(2° to 12°C)
Incremented by
1°
MIXED AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if
temperature falls below setup value)
FREEZE POS
CLO
CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CLO = closed
MIN = MIN POS or VENTMIN
CO2 ZERO
0 ppm
0 to 500 ppm;
increment by 10 CO
2
ppm level to match CO
2
sensor start level.
CO2 SPAN
2000 ppm
1000 to
3000 ppm;
increment by 50
CO
2
ppm span to match CO
2
sensor.
STG3 DLY
2.0 h
0 min, 5 min,
15 min, then
15 min intervals.
Up to 4 h or OFF
COOLING STAGE 3 DELAY
Delay after stage 2 for cool has been active. Turns on second stage of
cooling when economizer is first stage and mechanical cooling is second
SD DMPR POS
CLO
CLO or OPN
Function NOT AVAILABLE with 2-speed mode
DCVCAL ENA
MAN
MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers.
Resets ventilation. For single speed units only.
MAT T CAL
0.0°F
(or C)
±2.5°F
(±1.4°C)
MIXED AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration mixed air
temperature (MAT) sensor
OA T CAL
1.0°F
(or C)
±2.5°F
(±1.4°C)
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration outside air
temperature (OAT) sensor
OA H CAL
0% RH
±10% RH
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration outside air enthalpy
sensor
RA T CAL
2.0°F
(or C)
±2.5°F
(±1.4°C)
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration return air
temperature (RA) sensor
RA H CAL
0% RH
±10% RH
RETURN AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration return air enthalpy
sensor
DA T CAL
0.0°F
(or C)
±2.5°F
(±1.4°C)
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration discharge air
temperature (DAT) sensor
2SP FAN DELAY
5 Minutes
0 to 20 minutes in
1 minute
increments
TIME DELAY ON SECOND STAGE ECONOMIZING
While in the Economizing mode, this is the delay between thermostat Y2 call
and Y1—O output to mechanical cooling stage, to allow high speed fan
operation to attempt to cool space first.
Table 11 — Menu Structure*(cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT†
NOTES