13
Installing Optional HH57AC081 Single Outside
Air Enthalpy Sensor
When using the HH57AC081 (Honeywell C7400S) enthal-
py sensor (Fig. 30) for outside air changeover, the existing
HH79AH001 (Honeywell C7250) dry bulb sensor must be re-
moved. The enthalpy sensor will be mounted in the same loca-
tion as the dry bulb sensor; see Fig. 1. When the enthalpy sen-
sor’s OA temperature, enthalpy, and dew point are below the
respective setpoints, the outside air can be used for free-cool-
ing. When any of these is above the setpoint, free-cooling will
not be available. Figure 29 shows the enthalpy boundaries in
the W7220 Jade controller. There are 5 enthalpy boundaries
(setpoints ES1 through ES5), which are defined by dry bulb
temperature, enthalpy, and dew point. ES3 is the default set-
ting. Table 7 shows the High Limit Curves for each setting. Im-
portant: to use the HH57AC081 sensor for outside air sensor,
the dip switches on the sensor must be set to OFF-OFF-OFF.
See Table 8.
The 2 gray wires with a plug from the EconoMi$er X har-
ness in the return chamber plug directly into the HH57AC081
enthalpy sensor. See Fig. 23 and 28 for wiring.
Fig. 29 — Enthalpy Curve Boundaries
Fig. 30 — HH57AC081 Dimensional, Connection and
Switching Information
LEGEND
Default Setting = OFF-OFF-OFF
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ENTHALPY
RA
HUM (%RH)
RA
TEMP
TEMPERATURE
ABSOLUTE HUMIDITY
ES5
ES4
ES3
ES2
ES1
HL
P1
(T,RH)
P2 (T,RH)
SINGLE ENTHALPY
DUAL ENTHALPY
HIGH LIMIT
Table 7 — Single Enthalpy and Dual Enthalpy High Limit Curves
ENTHALPY
CURVE
TEMP. DRY
BULB (F)
TEMP.
DEWPOINT (F)
ENTHALPY
(btu/lb/da)
POINT P1
POINT P2
TEMP. (F)
HUMIDITY
(%RH)
TEMP. (F)
HUMIDITY
(%RH)
ES1
80
60
28.0
80
36.8
66.3
80.1
ES2
75
57
26.0
75
39.6
63.3
80.0
ES3
70
54
24.0
70
42.3
59.7
81.4
ES4
65
51
22.0
65
44.8
55.7
84.2
ES5
60
48
20.0
60
46.9
51.3
88.5
HL
86
66
32.4
86
38.9
72.4
80.3
DA
RA
OA
12
3
S-Bus
Temp & Humidity
HH57AC081
4-1/4 (108)
2-3/4 (70)
2-1/64 (55)
S-Bus
NOTE: Dimensions are in. (mm).
Table 8 — HH57AC081 Sensor Dip Switch Settings
USE
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
1
2
3
DA
OFF
ON
OFF
RA
ON
OFF
OFF
OA
OFF
OFF
OFF
DA
— Discharge Air (not used on EconoMi$er X)
RA
— Return Air
OA
— Outside Air