3) ELECTRICAL HOOK-UP

To make the correct electrical connections:

1) Make sure the line voltage corresponds to the voltage indicated on the dataplate of the unit (± 10%).
2) To reach the electronic panel it is necessary to remove the front cover (C) of the condensing unit (pict.1). For this operation remove the fixing

screws and position the selector (A) on 0.

3) Unscrew  the screws (B) indicated in pict. 2 and remove the cover from the electronic panel.

LINE CABLE FOR SINGLE PHASE UNITS (230 V)

- Remove the plug (D) (pict.2) and insert a cable gland

PG16. Insert the power cable (of the section indicated in
the table of fuses) in the cable gland and connect:
1) the phase wire to the terminal1 (L1) of the isolator Q1
2) the neutral wire to the terminal 5 (N)
3) the protection wire (earth) to the terminal PE

- Tighten the cable gland.

LINE CABLE FOR THREE-PHASE UNITS (400 V)

- Remove the plug (D) (pict.2) and insert a cable gland PG 16. Insert the power cable (of the section indicated in the table of fuses) in the cable

gland and connect:
1) the phase wires to the terminals 1 (L1) - 3 (L2) - 5 (L3)
2) the neutral wire to the terminal 7 (N)
3) the protection wire (earth) to the terminal PE

- Tighten the cable gland.

CONNECTION CABLE DOOR HEATER

- Remove the plug (E) (pict. 2) and insert a cable gland PG 11. Insert the cable of the door heater and connect:

1) the phase wire to the terminal 40 of the electrionic control panel (G) 
2) the neutral wire to the terminal N of the electronic control panel (G)
3) the protection wire (earth) to the earth terminal (60) GND

- Tighten the cable gland.
Remeber that the voltage in output to the card is 230 V 1Amp. MAX. It is necessary to protect the door heater with a fuse (by costumer).

MICRO-DOOR CONNECTION

- Remove the plug (F) (pict.2) and insert a cable gland PG 11.
- Insert the cable deriving from the micro-door and connect the bands to the terminals 19 and 20 of the electronic control panel (G) after remo-

ving connection bridge .

The installation has to follow the sequence:
closed door - micro-door contact closed
opened door - micro-door contact opened 
- Tighten the cable gland.
WARNING: do not give voltage to the micro-door as it is fed with voltage deriving from the electronic control panel (low voltage).

When the operations for the electronic panel connection have finished close with the screws B (pict.2). Close the front cover (C) of the conden-

sing unit (pict. 1).

4) PROCEDURES BEFORE STARTING

Before switching on the unit check that:

The fixing screws are properly tightened
The electrical and refrigeration connections have been made correctly

If the unit has been opened check that:

No tools have been inadvertently left inside the enclosure
The enclosure has been assembled correctly
There are no gas leaks
The panels have been fitted correctly.

5) PLACING INTO SERVICE

Perform all the above mentioned connections and then the unit can be started.
A period of pre-heating is required; this is achieved by powering up the unit without switching on the control unit for at least 2 hours (3 hours in

cold climates). This procedure must be repeated whenever the plant is idle for periods in excess of 12 hours.

5

A

C

B

D

E

F

PE

G

Q1

pict. 1

pict. 2

E

N

G

L

I

S

H

Summary of Contents for BDB121NO170F

Page 1: ...USE AND MAINTENANCE BEDIENUNGSANLEITUNG INSTRUCTIONS D USAGE ET ENTRETIEN USO E MANUTENZIONE DB O DB O ...

Page 2: ...F 30 0 1162 5 8 0 5 230 1 50 0 7 4 3 7 9 R404A 600 4 43 13 12 6 BDB121NO170F 30 20 761 1 0 7 230 1 50 0 8 4 8 7 6 R404A 600 4 43 13 12 6 BDB121TO170F 30 20 965 1 2 0 9 230 1 50 0 8 5 0 7 5 R404A 600 4 46 13 12 6 MDB123TO170F 30 0 1332 3 4 0 6 230 1 50 0 8 5 0 8 4 R404A 600 4 43 13 12 6 BDB123TO170F 30 20 1096 1 7 1 3 230 1 50 0 9 5 5 11 3 R404A 600 4 50 13 12 6 MDB221TO170F 30 0 2243 1 2 0 9 400 3...

Page 3: ... SHEET SERVICEBLATT FICHE DE SERVICE FOGLIO SERVIZIO DATE DATUM OPERATION MASSNAHME SERVICE FIRM SERVICEFIRMA SIGNATURE UNTERSCHRIFT DATE DATA OPERATION OPERAZIONE ETS DE SERVICE DITTA ASSISTENZA SIGNATURE FIRMA ...

Page 4: ...water is collected in a tray located beneath the evaporator from where it is drained to outside the rooml 2 INSTALLATION For correct installation proceed thus 1 Position the condenser unit on floor level outside the coldroom 2 Secure the evaporator unit to the coldroom ceiling pict 1 as follows 2A Open the fan holder bottom A by loosing screws B pict 2 3 2B Drill the fixing holes on the coldroom c...

Page 5: ...ire earth to the earth terminal 60 GND Tighten the cable gland Remeber that the voltage in output to the card is 230 V 1Amp MAX It is necessary to protect the door heater with a fuse by costumer MICRO DOOR CONNECTION Remove the plug F pict 2 and insert a cable gland PG 11 Insert the cable deriving from the micro door and connect the bands to the terminals 19 and 20 of the electronic control panel ...

Page 6: ...eady for program ming It is necessary therefore to set the required room temperature bearing in mind the limits of the range which the unit is able to operate Press the SET 6 key the yellow LED will light The last set temperature will be displayed on the display screen 5 which showes the set value Press the set key 6 the yellow led will light for one second and the display 5 will start flashing a ...

Page 7: ...s terminals E3 and E4 Pict 2 5 A wire comes out from nr 30 on the card it is welded in the card an connented to terminal 4 Disconnect it and let it free 6 Enter the thermostat bulb inside room 7 Adjust the stat at the required temperature and switch the unit on 8 When the set temperature is reached compressor evaporator and condenser fans will stop 9 During emergency period defrost cycle is cut ou...

Page 8: ...n G Ga as s V Vo ollt ta ag ge e A Am mp pe er re e n nº º A Am mp pe er re e m mm m2 2 M MO OD DE EL LL LO O G Ga am mm ma a V Ve er rs siio on ne e T Te en ns siio on ne e 20 POWER CURRENT FUSE We advise the use of such a fuse circuit breaker fitted in the line otherwise a suitable fused isolator can be used LEISTUNGSSICHERUNG Man raet die Verwendung solcher Schmelzsicherung auf der Linie eingeb...

Page 9: ... associato al parametro 2C Modify the value pressing 8 and 9 until you reach the required one Um den wert zu änderu 8 und 9 bis zum gew wert drücken Modifier la valeur en pressant ensamble 8 et 9 jusqu on rejoint la valeur désiderée Modificare il valore agendo con i tasti 8 e 9 fino al raggiungimento di quello voluto 2D Press the key 6 to confirm temporarily the new value and return to the display...

Page 10: ...BRINAMENTO all accensione dello strumento 1 si 0 no d5 DEFROST DELAY AFTER RESET OR EXTERNAL TRIGGER VERZÖGERUNG ABTAUEN VON EINSCHALTEN INSTRUMENT DURCH MULTIFUNCTION EIN GANG RETARD DEGIVRAGE APRES ALLUMAGE DE L INSTRUMENT PAR ENTREE MULTIFONCTIONS RITARDO SBRINAMENTO dall accensione stru mento da ingr multifunction d6 DISPLAY LOCK DURING DEFROST 1 yes 0 no SPERRUNG ANZEIGE WÄHREND ABTAUEN 1 ja ...

Page 11: ...20 20 20 20 F F2 2 flag 0 1 0 0 0 0 F F3 3 flag 0 1 1 1 1 1 F Fd d min 0 15 1 1 1 1 H H0 0 0 15 0 0 0 0 H H1 1 flag 0 1 0 0 0 0 P PO O flag 0 15 10 10 10 10 P P1 1 min 0 199 60 60 60 60 T3 T4 T1 T2 C CO OD DE E C CO OD DE E C CO OD DE E C CO OD DIIC CE E MANUFACTURED STANDARDS HERSTELLERSTANDARD STANDARDS CONSTRUCTEUR STANDARD COSTRUTTORE Unit of measure Operating Field Arbitsbereich Electric defr...

Page 12: ...6 31 41 9 8 15 24 1 67 33 9 11 17 72 41 50 75 62 70 30 35 27 69 68 18 16 77 40 13 32 55 2 11 67 64 14 52 65 29 38 74 46 61 60 9 8 47 19 44 7 28 73 5 4 45 6 49 20 54 53 21 12 25 23 22 39 36 34 43 80 78 79 1 DB121 123 18 05 99 Arfini Tav n Modello Data Disegnatore ...

Page 13: ...R191 1 1 1 1 1 1 39 HANDLE HANDGRIFF POIGNÉE MANIGLIA 3MNG009 1 1 1 1 1 1 40 LEFT HAND SIDE LINKE SEITENWAND FLANC GAUCHE FIANCO SINISTRO 2225072 1 1 1 1 1 1 41 REINFORCEMENT VERSTÄRKUNG RENFORCEMENT RINFORZO 2009093 2 2 2 2 2 2 42 SIGHT GLASS SCHAUGLAS VOYANT LIQUIDE INDICATORE 3INU019 1 1 1 1 1 1 43 TERMINAL KLEMME BORNE MORSETTO 3MRS004 1 1 1 1 1 1 44 NUT MUTTER ECROU DADO 3DDO043 2 2 2 2 2 2 4...

Page 14: ...30 18 35 32 31 55 38 15 24 51 52 1 65 41 67 40 72 26 63 68 77 9 3 70 58 33 69 64 67 27 48 76 8 16 9 50 56 19 9 17 37 11 46 4 8 9 6 60 7 28 47 44 78 73 61 49 54 74 20 53 45 5 23 25 21 22 39 43 36 34 81 79 80 2 DB 221 18 05 99 Arfini Tav n Modello Data Disegnatore ...

Page 15: ...LLONGE PROLUNGA 3PRL009 1 1 1 37 TERMINAL KLEMME BORNE MORSETTO 3MOR010 8 8 8 38 CONTACTOR FERNSCHALTER TELERUPTEUR TELERUTTORE 3TLR191 1 1 1 39 HANDLE HANDGRIFF POIGNÉE MANIGLIA 3MNG009 1 1 1 40 LEFT HAND SIDE LINKE SEITENWAND FLANC GAUCHE FIANCO SINISTRO 2225072 1 1 1 41 REINFORCEMENT VERSTÄRKUNG RENFORCEMENT RINFORZO 2009093 2 2 2 42 SIGHT GLASS SCHAUGLAS VOYANT LIQUIDE INDICATORE 3INU006 1 1 1...

Page 16: ...6 13 14 76 65 67 46 29 20 45 10 38 14 3 63 31 15 52 68 77 40 33 47 22 21 19 2 32 73 4 72 9 49 33 25 69 41 9 8 16 26 28 42 23 27 61 9 11 37 17 11 24 1 51 41 30 35 59 67 58 57 75 43 36 34 78 80 79 56 50 3 DB 135 18 05 99 Arfini Tav n Modello Data Disegnatore ...

Page 17: ...OR FERNSCHALTER TELERUPTEUR TELERUTTORE 3TLR191 1 1 1 1 39 HANDLE HANDGRIFF POIGNÉE MANIGLIA 3MNG009 1 1 1 1 40 LEFT HAND SIDE LINKE SEITENWAND FLANC GAUCHE FIANCO SINISTRO 2135203 1 1 1 1 41 REINFORCEMENT VERSTÄRKUNG RENFORCEMENT RINFORZO 2009093 2 2 2 2 42 SIGHT GLASS SCHAUGLAS VOYANT LIQUIDE INDICATORE 3INU006 1 1 1 1 43 TERMINAL KLEMME BORNE MORSETTO 3MRS004 1 1 1 1 44 NUT MUTTER ECROU DADO 3D...

Page 18: ... SOLENOIDE SOLENOIDE 10 EXPANSION VALVE EXPANSIONVENTIL DETENDEUR THERMOSTATIQUE TERMOSTATICA 11 EVAPORATOR MOTOR DRIVEN FAN VERDAMPFER MOTORVENTILATOR MOTOVENTILATEUR EVAPORATEUR MOTOVENTIL EVAPORATORE 12 EVAPORATOR VERDAMPFER EVAPORATEUR EVAPORATORE 13 DEFROST HEATER ABTAUHEIZUNG RESISTANCE DEGIVRAGE RESISTENZA SBRINAMENTO 14 DEFROST DRAIN LINE ABTAUWASSERABFLUSS ECOULEMENT EAU DEGIVRAGE SCARICO...

Page 19: ...N NO OT TE E N NO OT TE ES S 31 ...

Page 20: ...0MAN043 C del 04 2001 ...

Reviews: