13. Winter Start Control

This control is designed to alleviate nuisance opening of the

low--pressure switch by bypassing it for the first 3 minutes of
operation.

ELECTRICAL DATA

UNIT

SIZE

V/PH

OPER

VOLTS*

COMPR

FAN

MCA

MIN WIRE

SIZE

{

MIN WIRE

SIZE

{

MAX

LENGTH

(FT)

}

MAX

LENGTH

(FT)

}

MAX

FUSE**

or CKT

BRK

AMPS

MAX

MIN

LRA

RLA

FLA

60

°

C

75

°

C

60

°

C

75

°

C

18

208/230/1

253

197

48.0

9.0

0.5

11.7

14

14

67

64

15

24

58.3

13.5

0.75

17.6

14

14

45

43

25

30

64.0

12.8

0.75

16.8

14

14

47

45

25

36

77.0

14.1

1.4

19.0

12

12

66

63

30

42

112.0

17.9

1.1

23.5

12

12

53

51

40

48

109.0

19.9

1.4

26.2

10

10

76

73

40

60

134.0

26.4

1.2

34.2

8

8

91

86

50

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{

If wire is applied at ambient greater than 30

˚

C (86

˚

F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable

(NM), trade name ROMEX, shall be that of 60

˚

C (140

˚

F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60

or 75

˚

C (140 or 167

˚

C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables

of the NEC (ANSI/NFPA 70).

}

Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.

** Time---Delay fuse.

FLA

--- Full Load Amps

LRA

--- Locked Rotor Amps

MCA

--- Minimum Circuit Amps

RLA

--- Rated Load Amps

NOTE

: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.

All motors/compressors contain internal overload protection.

A--WEIGHTED SOUND POWER (DBA)

UNIT

SIZE

STANDARD

RATING

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

125

250

500

1000

2000

4000

8000

18

76

52.0

61.0

67.0

70.5

67.5

63.5

56.5

24

76

56.5

64.0

67.5

69.5

67.0

65.0

60.5

30

76

55.0

63.5

69.0

72.0

69.0

64.5

59.5

36

76

58.5

64.0

68.0

69.5

66.0

62.5

55.0

42

78

57.5

65.0

71.0

73.0

70.5

67.5

62.5

48

78

59.5

67.0

72.5

73.0

70.0

67.0

62.5

60

78

53.5

61.0

67.5

74.5

68.5

62.5

61.0

A--WEIGHTED SOUND POWER (DBA) WITH ACCESSORY SOUND HOOD

UNIT

SIZE

STANDARD

RATING

TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

125

250

500

1000

2000

4000

8000

18

74

50.0

61.5

64.5

66.5

64.0

61.0

54.5

24

75

58.0

65.5

69.0

70.5

68.0

65.0

59.0

30

76

56.5

64.0

69.5

71.5

69.0

64.5

58.0

36

76

58.5

64.5

68.5

69.5

67.0

63.5

58.5

42

77

57.5

65.0

70.5

72.0

70.0

67.0

62.0

48

77

59.5

67.0

72.0

72.0

69.5

66.5

62.0

60

77

53.0

61.0

66.5

73.0

66.0

60.5

57.5

CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)

UNIT SIZE--- VOLTAGE & SERIES

REQUIRED SUBCOOLING (

_

F)

18---30

8

24---30

13

30---30

16

36---30

16

42---30

10

48---30

17

60---30

11

24AB

A

3

24AB

A

3

Summary of Contents for Base 24ABA3

Page 1: ...sories available Sound S Sound level as low as 76 dBA Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete the o...

Page 2: ...ISO 9001 2000 M A N U F A C T U R E R CERTIFIED TO ARI AS C O M P L Y I N G W I T H A RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT STANDARD FEATURES Feature 18 24 30 36 42 48 60...

Page 3: ...0 Ft when outdoor unit is above indoor unit and up to 80 Ft when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Long Line Application G...

Page 4: ...TOR FAN BALL BEARING X KSAHS1701AAA HARD START CAP RELAY X X X X X X X KSACY0101AAA CYCLE PROTECTOR X X X X X X X KSASF0101AAA SUPPORT FEET X X X X X X X KAACS0201PTC START ASSIST PTC X X X X X X X KA...

Page 5: ...designed to control condenser fan motor speed in response to the saturated condensing temperature during operation in cooling mode only For outdoor temperatures down to 20_F 28 9_C it maintains conde...

Page 6: ...tween unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all...

Page 7: ...4 13 3 4 24ABA348 0 X 0 0 0 31 3 16 39 1 4 3 7 8 7 8 6 9 16 24 11 16 9 1 8 5 16 3 2 15 16 5 8 17 1 4 17 1 4 19 3 4 24ABA360 0 X 0 0 0 35 39 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 5 16 3 2 15 16 5 8 19 3...

Page 8: ...TDR TXV 14 00 11 70 58CV A X 090 16 CNPH 2417A 17 700 TXV 13 00 11 00 CNPH 2417A 17 500 TDR TXV 14 00 11 70 58MVB040 14 CNPH 2417A 17 500 TDR TXV 14 00 11 70 58MVB060 14 CNPH 2417A 17 600 TDR TXV 14 0...

Page 9: ...0 CNPV 3014A 22 800 TDR TXV 14 00 11 15 58CV A X 070 12 CNPV 3017A 23 000 TXV 13 00 11 00 CNPV 3017A 22 800 TDR TXV 14 00 11 70 58MVB060 14 CNPV 3017A 22 800 TDR TXV 14 00 11 70 58CV A X 090 16 CNPH 2...

Page 10: ...00 11 50 58MVB060 14 CAP 3017A 27 600 TDR TXV 14 00 11 50 58CV A X 090 16 CAP 3614A 27 000 TXV 13 00 11 00 CAP 3614A 26 600 TDR TXV 14 00 11 50 58CV A X 070 12 CAP 3617A 28 000 TXV 13 00 11 00 CAP 361...

Page 11: ...X 070 12 CAP 3617A 33 600 TDR TXV 14 00 11 50 58MVB060 14 CAP 3617A 33 600 TDR TXV 14 00 11 50 58CV A X 090 16 CAP 3621A 34 000 TXV 13 00 11 00 CAP 3621A 33 600 TDR TXV 13 50 11 20 58MVB080 14 CAP 362...

Page 12: ...21A 40 000 TDR TXV 13 50 11 20 58MVB080 14 CAP 4221A 40 500 TDR TXV 13 50 11 20 58CV A X 110 20 CAP 4224A 41 000 TXV 13 00 11 00 CAP 4224A 40 000 TDR TXV 13 50 11 20 58MVB040 14 CAP 4224A 40 500 TDR T...

Page 13: ...16 CAP 4821A 46 000 TXV 13 00 11 00 CAP 4821A 45 000 TDR TXV 13 20 11 00 58MVB080 20 CAP 4821A 45 000 TDR TXV 13 65 11 40 58MVB100 20 CAP 4821A 45 000 TDR TXV 13 50 11 20 58CV A X 110 20 CAP 4824A 46...

Page 14: ...000 TDR TXV 13 50 11 00 58CV A X 135 22 CNPV 6024A 56 500 TDR TXV 13 50 11 20 58CV A X 155 22 CNPH 6024A 57 000 TXV 13 00 11 00 CNPH 6024A 56 000 TDR TXV 13 50 11 20 58CV A X 135 22 CNPH 6024A 56 500...

Page 15: ...2 11 40 1 42 18 99 11 03 1 58 17 97 10 67 1 77 16 88 10 28 1 97 15 65 9 85 2 18 67 19 33 14 90 1 27 18 43 14 54 1 42 17 48 14 15 1 59 16 51 13 77 1 77 15 48 13 35 1 97 14 33 12 89 2 19 62 18 01 17 91...

Page 16: ...23 87 23 87 1 68 22 97 22 97 1 88 22 00 22 00 2 10 20 98 20 98 2 35 19 87 19 87 2 62 18 66 18 66 2 92 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capaci...

Page 17: ...57 2 85 24 86 21 90 3 16 23 10 21 19 3 50 62 28 94 28 94 2 10 27 83 27 83 2 32 26 66 26 66 2 57 25 40 25 40 2 85 24 06 24 06 3 16 22 61 22 61 3 48 57 28 94 28 94 2 10 27 83 27 83 2 32 26 66 26 66 2 57...

Page 18: ...6 57 3 81 28 05 25 67 4 20 62 35 18 35 18 2 58 33 86 33 86 2 84 32 45 32 45 3 13 30 95 30 95 3 46 29 31 29 31 3 81 27 50 27 50 4 20 57 35 19 35 19 2 58 33 86 33 86 2 84 32 46 32 46 3 13 30 95 30 95 3...

Page 19: ...13 32 41 4 65 36 68 31 44 5 13 33 99 30 36 5 65 62 42 55 42 13 3 45 40 89 40 89 3 80 39 17 39 17 4 20 37 34 37 34 4 64 35 37 35 37 5 12 33 16 33 16 5 65 57 42 52 42 52 3 45 40 89 40 89 3 80 39 17 39 1...

Page 20: ...69 45 69 3 90 44 03 44 03 4 36 41 94 41 94 4 88 39 69 39 69 5 47 37 12 37 12 6 21 57 47 87 47 87 3 49 46 01 46 01 3 90 44 04 44 04 4 36 41 95 41 95 4 88 39 69 39 69 5 47 37 13 37 13 6 21 Multipliers...

Page 21: ...41 5 18 51 77 51 77 5 72 48 91 48 91 6 30 45 70 45 70 6 93 57 59 25 59 25 4 27 56 90 56 90 4 70 54 42 54 42 5 18 51 78 51 78 5 72 48 91 48 91 6 30 45 70 45 70 6 93 Multipliers for Determining the Per...

Page 22: ...ss B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel...

Reviews: