background image

5

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMaster

r

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor

motor at each start up.

Usage Guideline:
Required for reciprocating compressors in the

following applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the
following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of
low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.

Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Cycle Protector

The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay

after power to the compressor has been interrupted for any

reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.

6. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation

when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit

service valve. It is designed to cycle the outdoor fan motor in

order to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain

working head pressure at low--ambient temperatures down to 0

_

F

when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling operation is

used at outdoor temperatures below 55

_

F (12.8

_

C).

8. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the

saturated, condensing temperature during operation in cooling

mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C),

it maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

--12

_

C).
Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures

below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

9. Outdoor Air Temperature Sensor

Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the

outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary

heat lock out.

Usage Guideline:

Suggested for all Carrier thermostats listed in this

publication.

10. Sound Hood

Wraparound sound reducing cover for the compressor. Reduces
the sound level by about 2 dBA.

Usage Guideline:
Suggested when unit is installed closer than 15 ft to
quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft apart.

11. Support Feet

Four stick--on plastic feet that raise the unit 4 in. above the
mounting pad. This allows sand, dirt, and other debris to be

flushed from the unit base, minimizing corrosion.

Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.

12. Thermostatic Expansion Valve (TXV)

A modulating flow--control valve which meters refrigerant liquid

flow rate into the evaporator in response to the superheat of the

refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.

Hard shut off types are available.

NOTE

: When using a hard shut off TXV with single phase

reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.

Usage Guideline:

Required to achieve ARI ratings in certain equipment

combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner

long line applications.
Required for use on all zoning systems.

12. Time--Delay Relay

An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor

cycles off.

NOTE

: Most indoor unit controls include this feature. For those

that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain
combinations of indoor and outdoor units. Refer to

ARI Unitary Directory.

Accessory Description and Usage (Listed Alphabetically) (Continued)

24AB

A

3

Summary of Contents for Base 24ABA3

Page 1: ...sories available Sound S Sound level as low as 76 dBA Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete the o...

Page 2: ...ISO 9001 2000 M A N U F A C T U R E R CERTIFIED TO ARI AS C O M P L Y I N G W I T H A RI STANDARD 210 U N I T A R Y AIR CO N D I T I O N I N G EQUIPMENT STANDARD FEATURES Feature 18 24 30 36 42 48 60...

Page 3: ...0 Ft when outdoor unit is above indoor unit and up to 80 Ft when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Long Line Application G...

Page 4: ...TOR FAN BALL BEARING X KSAHS1701AAA HARD START CAP RELAY X X X X X X X KSACY0101AAA CYCLE PROTECTOR X X X X X X X KSASF0101AAA SUPPORT FEET X X X X X X X KAACS0201PTC START ASSIST PTC X X X X X X X KA...

Page 5: ...designed to control condenser fan motor speed in response to the saturated condensing temperature during operation in cooling mode only For outdoor temperatures down to 20_F 28 9_C it maintains conde...

Page 6: ...tween unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all...

Page 7: ...4 13 3 4 24ABA348 0 X 0 0 0 31 3 16 39 1 4 3 7 8 7 8 6 9 16 24 11 16 9 1 8 5 16 3 2 15 16 5 8 17 1 4 17 1 4 19 3 4 24ABA360 0 X 0 0 0 35 39 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 5 16 3 2 15 16 5 8 19 3...

Page 8: ...TDR TXV 14 00 11 70 58CV A X 090 16 CNPH 2417A 17 700 TXV 13 00 11 00 CNPH 2417A 17 500 TDR TXV 14 00 11 70 58MVB040 14 CNPH 2417A 17 500 TDR TXV 14 00 11 70 58MVB060 14 CNPH 2417A 17 600 TDR TXV 14 0...

Page 9: ...0 CNPV 3014A 22 800 TDR TXV 14 00 11 15 58CV A X 070 12 CNPV 3017A 23 000 TXV 13 00 11 00 CNPV 3017A 22 800 TDR TXV 14 00 11 70 58MVB060 14 CNPV 3017A 22 800 TDR TXV 14 00 11 70 58CV A X 090 16 CNPH 2...

Page 10: ...00 11 50 58MVB060 14 CAP 3017A 27 600 TDR TXV 14 00 11 50 58CV A X 090 16 CAP 3614A 27 000 TXV 13 00 11 00 CAP 3614A 26 600 TDR TXV 14 00 11 50 58CV A X 070 12 CAP 3617A 28 000 TXV 13 00 11 00 CAP 361...

Page 11: ...X 070 12 CAP 3617A 33 600 TDR TXV 14 00 11 50 58MVB060 14 CAP 3617A 33 600 TDR TXV 14 00 11 50 58CV A X 090 16 CAP 3621A 34 000 TXV 13 00 11 00 CAP 3621A 33 600 TDR TXV 13 50 11 20 58MVB080 14 CAP 362...

Page 12: ...21A 40 000 TDR TXV 13 50 11 20 58MVB080 14 CAP 4221A 40 500 TDR TXV 13 50 11 20 58CV A X 110 20 CAP 4224A 41 000 TXV 13 00 11 00 CAP 4224A 40 000 TDR TXV 13 50 11 20 58MVB040 14 CAP 4224A 40 500 TDR T...

Page 13: ...16 CAP 4821A 46 000 TXV 13 00 11 00 CAP 4821A 45 000 TDR TXV 13 20 11 00 58MVB080 20 CAP 4821A 45 000 TDR TXV 13 65 11 40 58MVB100 20 CAP 4821A 45 000 TDR TXV 13 50 11 20 58CV A X 110 20 CAP 4824A 46...

Page 14: ...000 TDR TXV 13 50 11 00 58CV A X 135 22 CNPV 6024A 56 500 TDR TXV 13 50 11 20 58CV A X 155 22 CNPH 6024A 57 000 TXV 13 00 11 00 CNPH 6024A 56 000 TDR TXV 13 50 11 20 58CV A X 135 22 CNPH 6024A 56 500...

Page 15: ...2 11 40 1 42 18 99 11 03 1 58 17 97 10 67 1 77 16 88 10 28 1 97 15 65 9 85 2 18 67 19 33 14 90 1 27 18 43 14 54 1 42 17 48 14 15 1 59 16 51 13 77 1 77 15 48 13 35 1 97 14 33 12 89 2 19 62 18 01 17 91...

Page 16: ...23 87 23 87 1 68 22 97 22 97 1 88 22 00 22 00 2 10 20 98 20 98 2 35 19 87 19 87 2 62 18 66 18 66 2 92 Multipliers for Determining the Performance With Other Indoor Sections Cooling Indoor Model Capaci...

Page 17: ...57 2 85 24 86 21 90 3 16 23 10 21 19 3 50 62 28 94 28 94 2 10 27 83 27 83 2 32 26 66 26 66 2 57 25 40 25 40 2 85 24 06 24 06 3 16 22 61 22 61 3 48 57 28 94 28 94 2 10 27 83 27 83 2 32 26 66 26 66 2 57...

Page 18: ...6 57 3 81 28 05 25 67 4 20 62 35 18 35 18 2 58 33 86 33 86 2 84 32 45 32 45 3 13 30 95 30 95 3 46 29 31 29 31 3 81 27 50 27 50 4 20 57 35 19 35 19 2 58 33 86 33 86 2 84 32 46 32 46 3 13 30 95 30 95 3...

Page 19: ...13 32 41 4 65 36 68 31 44 5 13 33 99 30 36 5 65 62 42 55 42 13 3 45 40 89 40 89 3 80 39 17 39 17 4 20 37 34 37 34 4 64 35 37 35 37 5 12 33 16 33 16 5 65 57 42 52 42 52 3 45 40 89 40 89 3 80 39 17 39 1...

Page 20: ...69 45 69 3 90 44 03 44 03 4 36 41 94 41 94 4 88 39 69 39 69 5 47 37 12 37 12 6 21 57 47 87 47 87 3 49 46 01 46 01 3 90 44 04 44 04 4 36 41 95 41 95 4 88 39 69 39 69 5 47 37 13 37 13 6 21 Multipliers...

Page 21: ...41 5 18 51 77 51 77 5 72 48 91 48 91 6 30 45 70 45 70 6 93 57 59 25 59 25 4 27 56 90 56 90 4 70 54 42 54 42 5 18 51 78 51 78 5 72 48 91 48 91 6 30 45 70 45 70 6 93 Multipliers for Determining the Per...

Page 22: ...ss B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel...

Reviews: