background image

40

SINGLE STAGE ELECTRIC AUXILIARY HEAT
The control can operate a single stage of electric heat connected to

a coil on the discharge side of the unit in order to maintain the de

-

sired heating setpoint should the compressor capacity be insuffi

-

cient or a compressor failure occurs. Unless the compressor fails,

the heat stage will only operate to supplement the heat provided by

the compressor if the space temperature falls two degrees or more

below the desired heating setpoint. The heat stage will be con

-

trolled so the SAT will not exceed the Maximum Heating SAT

limit and subject to a two minute minimum OFF time to prevent

excessive cycling. 
AUTOMATIC FAN SPEED CONTROL
The control is capable of controlling up to 3 fan speeds. The motor

will operate at the lowest speed possible to provide quiet and effi

-

cient fan operation. The motor will increase speed if additional

cooling or heating is required to maintain the desired space tem

-

perature setpoint. The control increases the motor's speed by one

step for each 2°F above the cooling or below the heating setpoint.

Also, the  control will increase the fan speed as  the Supply Air

Temperature  approaches the  configured minimum or  maximum

limits. Fan speed for PSC motors is controlled by energizing and

de-energizing low, medium and high speed relays. Fan speed for

ECMs is controlled by first energizing the low speed tap. If a high

-

er speed is required, the low speed tap remains energized while the

medium speed tap is also energized. If high motor speed is re

-

quired, all 3 speed taps are energized. If more than one speed tap is

energized for an ECM, the ECM will default to the higher speed.
FAN SPEED CONTROL - DURING HEATING
Whenever  heat  is  required and  active,  the  control  continuously

monitors the supply air temperature to verify it does not rise above

the configured Maximum Heating SAT Limit (110°F Default). As

the SAT approaches this value, the control will increase the fan

speed as required to insure the SAT will remain within the limit.

This feature provides the most quiet and efficient operation by op

-

erating the fan at the lowest speed possible. 
FAN SPEED CONTROL - DURING COOLING
Whenever mechanical cooling is required and active, the control

continuously monitors the supply air temperature to verify it does

not fall below the configured Minimum Cooling SAT Limit (50°F

Default). As the SAT approaches this value, the control will in

-

crease the fan speed as required to insure the SAT  will remain

within the limit. 
MODULATING WATER ECONOMIZER CONTROL
The control has the capability to modulate a water valve to control

condenser water flowing through a coil on the entering air side of

the unit. 

COOLING

The purpose is to provide an economizer cooling function by us

-

ing the water loop when the entering water loop temperature is

suitable (at least 5°F below space temperature). If the water loop

conditions are suitable, then the valve will modulate open as re

-

quired to maintain a Supply Air Temperature that meets the load

conditions. Should the economizer coil capacity be insufficient for

a period greater than 5 minutes, or should a high humidity condi

-

tion occur, then the compressor will be started to satisfy the load.

As  the  SAT  approaches  the  Minimum  Cooling  SAT  limit,  the

economizer  valve  will  modulate  closed  during  compressor

operation. 

HEATING

Additionally, the control will modulate the water valve should the

entering water loop temperature be suitable for heating (at least

5°F above space temperature) and heat is required. The valve will

be controlled in a similar manner except to satisfy the heating re

-

quirement. Should the coil capacity be insufficient to satisfy the

space load conditions for more than 5 minutes, then the compres

-

sor will be started to satisfy the load. As the SAT approaches the

Maximum Heating SAT limit, the economizer valve will modulate

closed during compressor operation. 
TWO-POSITION WATER ECONOMIZER CONTROL
The control has the capability to open a NO or NC, two-position,

water valve to control condenser water flow through a coil on the

entering air side of the unit. 

COOLING

The purpose is to provide a cooling economizer function directly

from the condenser water loop when the entering water loop tem

-

perature is suitable (at least 5°F below space temperature). If the

optional coil is provided and the water loop conditions are suit

-

able, then the valve will open to provide cooling to the space when

required. Should the capacity be insufficient for a period greater

than 5 minutes, or should a high humidity condition occur, then

the compressor will be started to satisfy the load. Should the SAT

reach the Minimum Cooling SAT limit, the economizer valve will

close during compressor operation. 

HEATING

Additionally,  the  economizer  control  will  open  the  water  valve

should the entering water loop temperature be suitable for heating

(at least 5°F above space temperature) and heat is required. The

valve will be controlled in a similar manner except to satisfy the

heating requirement. Should  the coil capacity  be  insufficient to

satisfy the space load for more than 5 minutes, then the compres

-

sor will be started to satisfy the load. Should the SAT reach the

Maximum  Heating  SAT  limit,  the  economizer  valve  will  close

during compressor operation. 
POWER FAIL RESTART DELAY
The control provides a delay when recovering from a power fail

-

ure in order to insure stable utility power and to prevent excessive

demand when many units start simultaneously. Each unit can be

user configured for a unique delay between 0 and 600 seconds.

The factory programmed default delay is 60 seconds. (Note that

the onboard control will not start the compressor on any call for

heating, cooling or dehumidification until 5 minutes has elapsed

from the power restoration. If a lower restart time delay is config

-

ured, only the fan start will be affected as the internal logic boards

will prevent compressor operation for more than 300 seconds). 
SUPPLY  AIR  TEMPERATURE  MONITORING/CONTROL/

ALARM
The control has 2 configurable control limits for supply air tem

-

perature.  The  control  will  monitor  the  supply  air  temperature

(SAT) and verify it is within limits. During cooling, the control

will increase fan speed and reduce compressor stages should the

SAT approach the Maximum Cooling SAT limit. Likewise, during

heating,  should  the  SAT  approach  the  Maximum  Heating  SAT

limit, the fan speed will be increased, followed by reducing com

-

pressor stages. Auxiliary heating coils are controlled so as not to

exceed the Maximum Heating SAT limit. Additionally, a separate

High SAT Alarm Limit and Low SAT Alarm Limit are provided

so that an alarm can be generated to indicate an abnormal SAT

condition should the SAT exceeds the alarm limit for more than

1 minute.

Summary of Contents for Aquazone 50HQP 072

Page 1: ...gure Unit Control Components 32 UNIT PROTECTION MODULE UPM FREEZE SENSOR UPM DIP SWITCH SETTINGS PRE START UP 33 System Checkout 33 AIR COIL FIELD SELECTABLE INPUTS 34 START UP 34 Operating Limits 34 ENVIRONMENT POWER SUPPLY UNIT STARTING CONDITIONS Start Up System 34 Scroll Compressor Rotation 34 Flow Regulation 37 Flushing 37 Antifreeze 38 Cooling Tower Boiler Systems 38 Ground Coupled Closed Lo...

Page 2: ...nstructions literature is for Aquazone water source heat pump systems Water source heat pumps WSHPs are single package vertically or horizontally mounted units with a reversible refrigeration cycle for year round cooling and heating IMPORTANT Read the entire instruction manual before start ing installation WARNING Electrical shock can cause personal injury or death Before installing or servicing s...

Page 3: ...ping conduit etc to block filter access 7 Provide sufficient access to allow maintenance and servic ing of the blower and blower motor compressor and coils Removal of the entire unit from the installation area should not be necessary 8 Provide an unobstructed path to the unit within the closet or mechanical room Space should be sufficient to allow return air to freely enter the space 9 Provide rea...

Page 4: ...ill be available 10 50HQP Only Locate the hanging bracket kit located in the compressor compartment 11 50HQP Only For units with the SAVTM or single speed VFD option locate the VFD ships in control box section or on the pallet with the unit See Fig 1 for VFD shipping box location If VFD is not found contact your Carrier sales representative Fig 1 Field Installed VFD Shipping Location 50HQP Units A...

Page 5: ...4 NA 3 4 NA Unit Ship Weight Vert Horiz lb 715 715 752 752 980 980 NA 1150 1140 NA NA 1620 Unit Operating Weight Vert Horiz lb 670 670 702 702 935 935 NA 1060 1050 NA NA 1530 50HQP VQP UNIT SIZE 181 210 240 242 300 360 Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Quantity 2 2 2 2 2 2 Total Refrigerant Charge lb 15 25 16 25 18 13 18 13 18 13 36 00 Air Coil Dimensions in H x L Qty 24 x ...

Page 6: ...3 38 28 00 16 75 1 25 12 50 13 50 5 25 150 25 50 42 00 82 00 2 00 20 50 18 50 24 00 2 75 24 00 17 75 1 50 18 50 16 00 14 00 24 x 34 x 1 2 per unit 1 00 MOUNTING HOLES 5 8 IN DIAMETER 3 00 4 50 2 00 1 50 J J L 5 50 K H G E F CONDENSER WATER IN CONDENSER WATER OUT RETURN AIR BLOWER MOTOR ORIENTATION CONDENSATE DRAIN 2 120 LEFT RETURN RIGHT DISCHARGE RETURN AIR CONDENSATE DRAIN 2 BLOWER MOTOR ORIENTA...

Page 7: ...MINAL A B C E F G H DIAMETER FPT J K L M 180 25 25 60 25 106 50 2 00 24 00 22 00 22 00 6 25 22 00 16 00 1 5 27 75 17 25 5 00 4 00 24 x 34 x 1 2 per unit 242 36 00 60 25 106 50 2 00 34 75 32 75 24 50 7 25 24 50 19 62 2 0 23 75 19 75 7 75 9 75 171 4 x 341 2 x 1 4 per unit MOUNTING HOLES 1 IN DIAMETER 1 50 4 00 1 00 3 00 3 00 7 00 MOUNTING BRACKET SECTION VIEW B C A 67 00 DEPTH HEIGHT WIDTH CONDENSAT...

Page 8: ...2 00 42 00 32 00 14 75 8 50 2 75 1 120 62 00 42 00 32 00 15 00 9 00 3 00 1 25 E C B A HEIGHT CONDENSER WATER OUT CONDENSATE DRAIN CONDENSER WATER IN D 42 00 32 00 ELECTRICAL CONNECTIONS 24 00 20 00 9 00 6 00 34 00 22 00 34 00 28 00 7 00 2 00 17 50 22 00 BLOWER MOTOR ORIENTATION TOP SUPPLY TOP SUPPLY REAR SUPPLY TOP SUPPLY 24 00 6 00 9 00 20 00 C B A HEIGHT CONDENSER WATER OUT CONDENSATE DRAIN COND...

Page 9: ... 00 24 x 24 x 1 4 per unit 181 70 00 52 50 32 00 17 00 10 50 3 00 11 2 5 00 17 50 20 00 24 00 70 00 52 50 32 00 50 00 CONDENSER WATER OUT CONDENSATE DRAIN CONDENSER WATER IN C B A ELECTRICAL CONNECTIONS 44 25 22 00 22 00 44 25 12 12 28 00 2 00 17 50 BLOWER MOTOR ORIENTATION OPTIONAL BLOWER ORIENTATION STANDARD BLOWER ORIENTATION 5 00 17 50 20 00 24 00 70 00 CONDENSER WATER OUT CONDENSATE DRAIN CON...

Page 10: ...00 32 00 18 00 8 75 2 75 2 40 00 38 00 300 66 50 80 00 32 00 18 00 8 75 2 75 2 40 00 38 00 360 86 50 80 00 32 00 17 00 9 00 3 50 2 60 00 58 00 30 x 341 2 x 1 4 per unit size 360 only HEIGHT 7 00 28 00 10 00 34 00 34 00 4 50 28 00 2 00 17 50 C B A 80 00 32 00 BLOWER MOTOR ORIENTATION CONDENSER WATER OUT CONDENSATE DRAIN CONDENSER WATER IN ELECTRICAL CONNECTIONS D E 6 0 9 0 20 0 24 0 14 0 22 0 34 00...

Page 11: ...lectrical control boxes Blower Motor Blower Motor Blower Blower BlowerMotor Sheave Pulley Belt Access 18 Minimum 24 Optimum Compressor Accesss and Electrical Control Access 36 Minimum BlowerWheel Housing 18 Minimum 24 Optimum Blower Compressor Front of Unit Electrical Control Box Blower motor and blower housing access is required on BOTH SIDES of the unit Blower Wheel Housing 18 Minimum 24 Optimum...

Page 12: ...s The rods are usually attached to the unit corners by hanger bracket kits See Fig 9 The rods must be se curely anchored to the ceiling Refer to the hanging bracket as sembly and installation instructions Included with the unit for details All 50HQP units include an integral angle iron frame with mounting holes present See unit horizontal detail drawing Hor izontal units installed above the ceilin...

Page 13: ...as the capacity to handle the air required for the unit application If the duct system is too small larger ductwork must be installed Be certain to check for existing leaks and repair The duct system and all diffusers should be sized to handle the de signed airflow quietly To maximize sound attenuation of the unit blower the supply and return air plenums should be insulated There should be no dire...

Page 14: ...all valves should be installed in the supply and return lines for unit isolation and unit water flow balancing Pressure temperature ports are recommended in both the supply and return lines for system flow balancing The water flow can be accurately set by measuring the water to refrigerant heat exchang ers water side pressure drop See the unit specification sheets for the water flow and pressure d...

Page 15: ...EWT MIN 1 LINE VOLTAGE DISCONNECT 2 FLEX DUCT CONNECTION 3 LOW VOLTAGE CONTROL CONNECTION 4 LINE VOLTAGE CONNECTION 5 VIBRATION PAD 6 P T PORTS 7 HOSE KITS Optional 8 BALL VALVES 9 SOLENOID VALVE SLOW CLOSING 10 CONDENSATE DRAIN CONNECTION 11 PRESSURE TANK Optional ...

Page 16: ...ween the unit and the open cooling tower may also be used It is imperative that all air is eliminated from the closed loop side of the heat exchanger to prevent condenser fouling In the heating mode heat is absorbed from the water loop to the unit Aboiler can be utilized to maintain the loop within the proper temperature range No unit should be connected to the supply or return piping until the wa...

Page 17: ... without unit mounted disconnect switches except units with dual power supply power is connected to the line L side of the compressor contactor and the ground lug in the unit electrical box CONTROL TRANSFORMER SETTING FOR 208V UNITS As factory built all 208 230 v units are wired for 230 v operation For job sites with a 208 v power supply the primary leads on the unit transformer will need to be ch...

Page 18: ... 15 Earth Coupled Applications Fig 16 Electrical Control Box Location 50HQP Units ELECTRICAL CONNECTIONS CONDENSATE DRAIN ELECTRICAL BOX CONTROLS COMPRESSORS ACCESS COMPRESSORS REFRIGERATION COMPONENTS ACCESS ...

Page 19: ... 7 83 0 1 6 2 2 37 0 50 460 3 60 6 2 41 0 1 3 1 2 17 1 20 575 3 60 4 8 33 0 1 2 6 2 13 4 15 120 208 230 1 60 26 3 134 0 1 9 8 2 69 0 90 208 230 3 60 15 6 110 0 1 8 0 3 43 1 50 460 3 60 7 8 52 0 1 3 9 3 21 5 25 575 3 60 5 8 38 9 1 3 7 3 16 8 20 150 208 230 3 60 19 2 136 0 1 9 2 3 52 4 70 460 3 60 8 7 66 1 1 4 3 3 23 9 30 575 3 60 6 9 55 3 1 3 7 3 19 2 25 180 208 230 3 60 22 4 149 0 2 6 2 2 62 8 80 ...

Page 20: ... 15 6 110 0 1 6 2 2 41 3 50 460 3 60 7 8 52 0 1 3 1 2 20 7 25 575 3 60 5 8 38 9 1 2 6 2 15 7 20 151 208 230 3 60 19 2 136 0 1 8 0 3 51 2 70 460 3 60 8 7 66 1 1 3 9 3 23 5 30 575 3 60 6 9 55 3 1 3 7 3 19 2 25 181 208 230 3 60 22 4 149 0 1 13 4 5 63 8 80 460 3 60 10 6 75 0 1 6 6 5 30 5 40 575 3 60 7 7 54 0 1 5 4 5 22 7 30 210 208 230 3 60 29 5 195 0 2 4 8 11 2 76 0 100 460 3 60 14 7 95 0 2 2 4 11 2 ...

Page 21: ... Single Phase Complete C Control Package DEFAULT SETTINGS FOR COMPLETE C BOARD FROM FACTORY SHOWN COMPLETE C INCLUDES BUILT IN 270 300 SECOND RANDOM START 300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS ...

Page 22: ... 19 Single Phase Deluxe D Control Package DEFAULT SETTINGS FOR DELUXE D BOARD FROM FACTORY SHOWN DELUXE D INCLUDES BUILT IN 270 300 SECOND RANDOM START 300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS ...

Page 23: ...23 Fig 20 Single Phase with WSHP Open ...

Page 24: ...21 3 Phase Complete C Control Package COMPLETE C INCLUDES BUILT IN 270 300 SECOND RANDOM START 300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS DEFAULT SETTINGS FOR COMPLETE C BOARD FROM FACTORY SHOWN ...

Page 25: ...ig 22 3 Phase Deluxe D Control Package DEFAULT SETTINGS FOR DELUXE D BOARD FROM FACTORY SHOWN DELUXE D INCLUDES BUILT IN 270 300 SECOND RANDOM START 300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS ...

Page 26: ...26 Fig 23 3 Phase with WSHP Open ...

Page 27: ... Complete C Control Package with Hot Gas Reheat DEFAULT SETTINGS FOR COMPLETE C BOARD FROM FACTORY SHOWN COMPLETE C INCLUDES BUILT IN 270 300 SECOND RANDOM START 300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS ...

Page 28: ...28 Fig 25 3 Phase Deluxe D Control Package with 1 Speed VFD and Hot Gas Reheat ...

Page 29: ...29 Fig 26 3 Phase with WSHP Open Hot Gas Reheat Water Economizer and SAVTM ...

Page 30: ...hase Complete C Board with Water Economizer DEFAULT SETTINGS FOR COMPLETE C BOARD FROM FACTORY SHOWN COMPLETE C INCLUDES BUILT IN 270 300 SECOND RANDOM START 300 SECOND DELAY ON BREAK 120 SECOND LOW PRESSURE BYPASS ...

Page 31: ...31 Fig 28 WSHP Open W2A Wiring Diagram ...

Page 32: ...opera tion when a 24V signal is removed from the relay Removing the 24V signal causes the relay to open which cuts 24V power to the unit control circuit All unit components will be disabled at when the EMS is deactivated See Fig 19 BOILERLESS HEAT CONTROL DELUXE D ONLY All units with Deluxe D control include a boilerless heat relay that can be field wired to enable an external heat source when the...

Page 33: ...ete 5 Air is purged from closed loop system 6 System is balanced as required Monitor if necessary 7 Isolation valves are open 8 Water control valves or loop pumps are wired 9 Condensate lines are open and correctly pitched 10 Transformer switched to lower voltage tap 208V if necessary 11 Blower rotates freely shipping support is removed 12 Blower speed is on correct setting 13 Air filter is clean ...

Page 34: ...ver any of these factors are at a minimum or maximum level the other two factors must be at a normal level to ensure proper unit operation See Table 5 Table 5 50HQP VQP Unit Operating Limits LEGEND With antifreeze optional extended range insulation and low temperature cutout jumper clipped for antifreeze Scroll Compressor Rotation It is important to be certain compressor is rotating in the proper ...

Page 35: ...21 392 4 5 25 30 50 13 0 116 142 192 234 13 16 21 26 104 127 333 407 7 9 27 33 22 0 111 135 182 222 9 12 22 27 109 133 340 415 5 6 28 34 60 13 0 119 146 228 279 13 16 21 26 120 146 352 430 8 10 30 37 22 0 113 138 217 265 9 11 22 27 125 153 359 439 6 7 32 39 70 13 0 122 149 264 323 13 15 20 25 136 166 371 453 9 12 33 41 22 0 116 142 251 307 9 11 21 26 142 174 378 462 7 8 35 43 80 13 0 125 152 301 3...

Page 36: ... 45 0 125 153 291 356 10 12 18 22 123 151 319 390 8 10 29 35 90 25 0 134 164 349 426 17 20 17 20 128 157 324 396 13 16 29 36 45 0 129 158 328 401 9 12 18 22 135 165 332 406 9 11 31 38 100 25 0 139 170 392 480 16 20 16 20 45 0 133 163 369 451 9 11 17 21 210 30 28 0 71 87 277 339 6 7 15 19 52 0 75 92 284 347 4 5 16 20 40 28 0 118 144 194 237 21 25 19 23 84 102 291 356 7 9 18 22 52 0 113 138 182 223 ...

Page 37: ...when it is added in the process it can be wasted Refer to the Antifreeze section for more detail Loop static pressure will fluctuate with the seasons Pressures will be higher in the winter months than during the warmer months This fluctuation is normal and should be considered when charging the system initially Run the unit in either heating or cool ing for several minutes to condition the loop to...

Page 38: ...TANDBY Y and W terminals are not active in Standby mode However the O and G terminals may be active depending on the application The compressor will be off COOLING Yand O terminals are active in Cooling mode After power up the first call to the compressor will initiate a 270 to 300 second ran dom start delay and a 5 minute anti short cycle protection time de lay After both delays are complete the ...

Page 39: ...TING The control will operate 1 or 2 stages of compression to maintain the desired heating setpoint To reduce noise the control operates the fan at the lowest speed possible If the heating is active and should the SAT approach the maximum SAT limit the fan will be indexed to the next higher speed Should this be insufficient then if the SAT rises further and reaches the Maximum Heating SAT limit th...

Page 40: ...e will modulate closed during compressor operation HEATING Additionally the control will modulate the water valve should the entering water loop temperature be suitable for heating at least 5 F above space temperature and heat is required The valve will be controlled in a similar manner except to satisfy the heating re quirement Should the coil capacity be insufficient to satisfy the space load co...

Page 41: ...time hours exceed the configurable limit an alarm is generated To reset the alarm timer after the alarm has been generated a Reset FilterAlarm input is provided The filter alarm can be disabled by setting the Filter Alarm Timer Delay to zero factory default COMPRESSOR FAULT LOCKOUT ALARM The control will monitor a discrete input to determine the com pressor state Should the input state not match t...

Page 42: ...42 Fig 32 WSHP Open Controls with UPM Board ...

Page 43: ... treatment can minimize tube fouling and pitting If such conditions are anticipated water treatment analysis is recom mended Refer to the Carrier System Design Manual Part 5 for general water conditioning information Clean condensers with an inhibited hydrochloric acid solution The acid can stain hands and clothing damage concrete and without inhibitor damage steel Cover surroundings to guard agai...

Page 44: ...rging NOTE Do not vent or depressurize unit refrigerant to atmosphere Remove and recover refrigerant following accepted practices Air Coil Fan Motor Removal Motor power wires need to be disconnected from motor termi nals before motor is removed from unit 1 Shut off unit main power supply 2 Loosen bolts on mounting bracket so that fan belt can be removed 3 Loosen and remove the 2 motor mounting bra...

Page 45: ...ant Recover refrigerant evacuate and recharge with factory recommended charge High pressure Check for defective or improperly calibrated high pressure switch UNIT OFF ON LOW PRESSURE CONTROL Suction pressure too low In COOLING mode Lack of or inadequate air flow Entering air temperature too cold Blower inoperative clogged filter or restrictions in ductwork In HEATING mode Lack of or inadequate wat...

Page 46: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500286 01 Printed in U S A Form 50HQP VQP 4SI Pg 46 10 2020 Replaces 50HQP VQP 2SI 2020 Carrier ...

Page 47: ...N HAS CONDENSATE CONNECTION BEEN MADE AND IS ATRAP INSTALLED Y N ISANAIR FILTER INSTALLED Y N III START UP IS FAN OPERATING WHEN COMPRESSOR OPERATES Y N IF 3 PHASE SCROLL COMPRESSOR IS PRESENT VERIFY PROPER ROTATION PER INSTRUCTIONS Y N UNIT VOLTAGE COOLING OPERATION PHASE AB VOLTS PHASE BC VOLTS PHASE CAVOLTS if 3 phase if 3 phase PHASE ABAMPS PHASE BC AMPS PHASE CAAMPS if 3 phase if 3 phase CONT...

Page 48: ...CLE ANALYSIS HEAT OF EXTRACTION ABSORPTION OR HEAT OF REJECTION FLOW RATE GPM x TEMP DIFF DEG F x FLUID FACTOR BTU HR SUPERHEAT SUCTION TEMPERATURE SUCTION SATURATION TEMPERATURE DEG F SUBCOOLING DISCHARGE SATURATION TEMPERATURE LIQUID LINE TEMPERATURE _____ DEG F Use 500 for water 485 for antifreeze SUCTION COMPRESSOR DISCHARGE COAX EXPANSION VALVE F F AIR COIL F PSI WATER OUT WATER IN F PSI F LI...

Reviews: