11
50HQP072-150 UNITS SERVICE CLEARANCES
50HQP180-242 UNITS SERVICE CLEARANCES
50VQP072-181 UNITS SERVICE CLEARANCES
50VQP210-360 UNITS SERVICE CLEARANCES
Fig. 7 —
Service Clearances
Compressor/Refrigerant Access
36" Minimum
Electrical/Compressor Access
36" Minimum
Compressors
Blower
Motor
Blower
Air Coil
Electrical
Control
Box
Blower Access
24" Minimum (072, 096, 150)
36" Minimum (120)
Electrical/Compressor Access
36" Minimum
Blower Access
36" Minimum
Compressor/Refrigerant Access
36" Minimum
Air Coil
Compressors
Electrical
Control
Box
NOTE: The local electric codes may require 36" or more clearance at all electrical control boxes.
Blower
Motor
Blower
Motor
Blower
Blower
*Blower Motor
Sheave/Pulley/Belt Access
18" Minimum
24" Optimum
Compressor Accesss and
Electrical/Control Access
36" Minimum
*Blower Wheel/Housing
18" Minimum
24" Optimum
Blower
Compressor
Front of Unit
Electrical
Control
Box
* Blower motor and blower housing access is required on BOTH SIDES of the unit.
*Blower Wheel/Housing
18" Minimum
24" Optimum
*Blower Motor
Sheave/Pulley/Belt Access
18" Minimum
24" Optimum
*Blower Motor
Sheave/Pulley/Belt Access
18" Minimum
24" Optimum
Compressor Access and
Electrical/Control Access
36" Minimum
*Blower Wheel/Housing
18" Minimum
24" Optimum
Blower
Compressor
Compressor
Electrical
Control
Box
Front of Unit
* Blower motor and blower housing access is required on BOTH SIDES of the unit.
Blower
Blower
Motor
Blower
Motor
Summary of Contents for Aquazone 50HQP 072
Page 23: ...23 Fig 20 Single Phase with WSHP Open ...
Page 26: ...26 Fig 23 3 Phase with WSHP Open ...
Page 28: ...28 Fig 25 3 Phase Deluxe D Control Package with 1 Speed VFD and Hot Gas Reheat ...
Page 29: ...29 Fig 26 3 Phase with WSHP Open Hot Gas Reheat Water Economizer and SAVTM ...
Page 31: ...31 Fig 28 WSHP Open W2A Wiring Diagram ...