19
Fig. 17 —
VFD Input and Output Power Connections, 50HQP Units
Table 2 —
50HQP072-242 Electrical Data
50HQP UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
COMPRESSOR (x2)
BLOWER MOTOR
MIN CIRCUIT
AMPS
MAX FUSE/
HACR
RLA
LRA
QTY
FLA
HP
072
208/230-1-60
16.7
79.0
1
7.0
1
44.6
60
208/230-3-60
10.4
73.0
1
3.6
1
27.0
35
460-3-60
5.8
38.0
1
1.8
1
14.9
20
096
208/230-1-60
19.6
130.0
1
9.8
2
53.9
70
208/230-3-60
13.7
83.0
1
6.2
2
37.0
50
460-3-60
6.2
41.0
1
3.1
2
17.1
20
575-3-60
4.8
33.0
1
2.6
2
13.4
15
120
208/230-1-60
26.3
134.0
1
9.8
2
69.0
90
208/230-3-60
15.6
110.0
1
8.0
3
43.1
50
460-3-60
7.8
52.0
1
3.9
3
21.5
25
575-3-60
5.8
38.9
1
3.7
3
16.8
20
150
208/230-3-60
19.2
136.0
1
9.2
3
52.4
70
460-3-60
8.7
66.1
1
4.3
3
23.9
30
575-3-60
6.9
55.3
1
3.7
3
19.2
25
180
208/230-3-60
22.4
149.0
2
6.2
2
62.8
80
460-3-60
10.6
75.0
2
3.1
2
30.1
40
575-3-60
7.7
54.0
2
2.6
2
22.5
30
242
208/230-3-60
30.1
225.0
2
3.9
2
75.5
100
460-3-60
16.7
114.0
2
3.1
2
43.8
60
575-3-60
12.2
80.0
2
2.6
2
32.7
40
Summary of Contents for Aquazone 50HQP 072
Page 23: ...23 Fig 20 Single Phase with WSHP Open ...
Page 26: ...26 Fig 23 3 Phase with WSHP Open ...
Page 28: ...28 Fig 25 3 Phase Deluxe D Control Package with 1 Speed VFD and Hot Gas Reheat ...
Page 29: ...29 Fig 26 3 Phase with WSHP Open Hot Gas Reheat Water Economizer and SAVTM ...
Page 31: ...31 Fig 28 WSHP Open W2A Wiring Diagram ...