Table 6 —
50HQP,VQP Typical Unit Operating Pressures and Temperatures
LEGEND
50HQP,
50VQP
UNIT
SIZE
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
COOLING
HEATING
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water Temp
Drop
(F)
Air Temp
Rise
(F) DB
072
30
10.0
—
—
—
—
65- 80
282-344
6- 7
14-17
16.0
—
—
—
—
73- 89
294-359
3- 4
15-18
40
10.0
121-148
184-225
17-21
18-22
80- 98
299-365
7- 9
16-20
16.0
117-143
167-204
10-13
19-23
89-108
311-380
4- 5
17-21
50
10.0
123-151
222-271
17-20
17-21
95-116
315-385
9-11
19-23
16.0
119-145
202-247
10-12
18-23
105-128
329-402
5- 7
20-24
60
10.0
125-153
260-318
16-19
17-21
109-133
332-406
11-13
21-26
16.0
120-147
237-289
10-12
18-22
121-148
346-423
6- 8
22-27
70
10.0
127-155
298-365
15-19
17-20
124-151
349-427
12-15
23-28
16.0
122-149
271-331
9-11
18-21
138-168
364-444
7- 9
25-30
80
10.0
129-158
336-411
14-18
16-20
138-169
366-447
14-17
26-31
16.0
124-152
306-374
9-11
17-21
154-188
381-466
8-10
27-33
90
10.0
131-160
374-458
14-17
16-19
153-187
383-468
16-19
28-34
16.0
126-154
340-416
8-10
17-20
170-208
399-487
9-12
29-36
100
10.0
133-162
413-504
13-16
15-19
—
—
—
—
16.0
128-156
375-458
8-10
16-20
—
—
—
—
096
30
13.0
—
—
—
—
72- 87
296-361
5- 6
21-25
22.0
—
—
—
—
75- 92
301-368
3- 4
22-26
40
13.0
114-139
155-190
14-17
22-27
88-107
314-384
6- 7
24-29
22.0
108-132
147-180
10-12
23-28
92-112
321-392
4- 5
25-30
50
13.0
116-142
192-234
13-16
21-26
104-127
333-407
7- 9
27-33
22.0
111-135
182-222
9-12
22-27
109-133
340-415
5- 6
28-34
60
13.0
119-146
228-279
13-16
21-26
120-146
352-430
8-10
30-37
22.0
113-138
217-265
9-11
22-27
125-153
359-439
6- 7
32-39
70
13.0
122-149
264-323
13-15
20-25
136-166
371-453
9-12
33-41
22.0
116-142
251-307
9-11
21-26
142-174
378-462
7- 8
35-43
80
13.0
125-152
301-368
12-15
20-24
152-185
389-476
11-13
36-44
22.0
118-145
286-349
9-11
21-26
159-194
397-485
8- 9
38-47
90
13.0
127-156
337-412
12-15
19-24
168-205
408-499
12-15
39-48
22.0
121-148
320-392
9-10
20-25
176-215
416-509
8-10
41-51
100
13.0
130-159
374-457
12-14
19-23
—
—
—
—
22.0
124-151
355-434
8-10
20-24
—
—
—
—
120
30
16.0
—
—
—
—
73- 89
266-325
5- 6
15-18
32.0
—
—
—
—
77- 94
272-333
3- 4
16-19
40
16.0
117-143
189-231
14-17
18-22
86-105
279-341
6- 7
17-21
32.0
112-137
178-217
8- 9
19-24
90-110
286-350
4- 5
18-22
50
16.0
126-154
221-270
14-17
18-21
162-198
293-358
7- 8
20-24
32.0
121-148
207-253
8- 9
19-23
170-208
300-366
5- 6
21-25
60
16.0
131-160
252-308
13-16
17-21
110-134
306-374
8-10
22-27
32.0
125-153
237-290
8- 9
18-22
115-141
314-383
6- 7
23-29
70
16.0
135-165
284-347
13-16
17-20
122-150
320-391
9-11
24-30
32.0
130-158
266-326
7- 9
18-22
129-157
327-400
6- 8
26-32
80
16.0
140-171
320-391
13-16
16-20
134-164
333-407
11-13
27-33
32.0
134-164
300-367
7- 9
17-21
141-172
341-417
7- 9
28-35
90
16.0
144-176
360-440
13-16
16-19
147-179
347-424
12-14
29-36
32.0
138-169
338-414
7- 9
17-21
154-188
355-434
8-10
31-38
100
16.0
149-182
405-495
13-15
15-19
—
—
—
—
32.0
143-174
381-465
7- 9
16-20
—
—
—
—
DB
—
Dry Bulb
Summary of Contents for Aquazone 50HQP 072
Page 23: ...23 Fig 20 Single Phase with WSHP Open ...
Page 26: ...26 Fig 23 3 Phase with WSHP Open ...
Page 28: ...28 Fig 25 3 Phase Deluxe D Control Package with 1 Speed VFD and Hot Gas Reheat ...
Page 29: ...29 Fig 26 3 Phase with WSHP Open Hot Gas Reheat Water Economizer and SAVTM ...
Page 31: ...31 Fig 28 WSHP Open W2A Wiring Diagram ...