20
Table 3 —
50VQP072-360 Electrical Data
LEGEND
NOTES:
1. HACR circuit breaker in U.S.A. only.
2.
A voltage variation of ± 10% of nameplate rating is acceptable.
Phase imbalance shall not exceed 2%.
3. See WSHP Builder for electrical data for configurations not listed
above.
50VQP UNIT SIZE
VOLTAGE
(V-Ph-Hz)
COMPRESSOR (x2)
BLOWER MOTOR
MIN CIRCUIT
AMPS
MAX FUSE/
HACR
RLA
LRA
QTY
FLA
HP
072
208/230-1-60
16.7
79.0
1
7.0
1
44.6
60
208/230-3-60
10.4
73.0
1
3.6
1
27.0
35
460-3-60
5.8
38.0
1
1.8
1
14.9
20
096
208/230-1-60
19.6
130.0
1
8.5
1
1
/
2
52.6
70
208/230-3-60
13.7
83.1
1
4.8
1
1
/
2
35.6
45
460-3-60
6.2
41.0
1
2.4
1
1
/
2
16.4
20
575-3-60
4.8
33.0
1
2.0
1
1
/
2
12.8
15
120
208/230-1-60
26.3
134.0
1
9.8
2
69.0
90
208/230-3-60
15.6
110.0
1
6.2
2
41.3
50
460-3-60
7.8
52.0
1
3.1
2
20.7
25
575-3-60
5.8
38.9
1
2.6
2
15.7
20
151
208/230-3-60
19.2
136.0
1
8.0
3
51.2
70
460-3-60
8.7
66.1
1
3.9
3
23.5
30
575-3-60
6.9
55.3
1
3.7
3
19.2
25
181
208/230-3-60
22.4
149.0
1
13.4
5
63.8
80
460-3-60
10.6
75.0
1
6.6
5
30.5
40
575-3-60
7.7
54.0
1
5.4
5
22.7
30
210
208/230-3-60
29.5
195.0
2
4.8
1
1
/
2
76.0
100
460-3-60
14.7
95.0
2
2.4
1
1
/
2
37.9
50
575-3-60
12.2
80.0
2
2.0
1
1
/
2
31.5
40
240
208/230-3-60
30.1
225.0
2
6.2
2
80.1
110
460-3-60
16.7
114.0
2
3.1
2
43.8
60
575-3-60
12.2
80.0
2
2.6
2
32.7
40
300
208/230-3-60
48.1
245.0
2
8.0
3
124.2
150
460-3-60
18.6
125.0
2
3.9
3
49.7
60
575-3-60
14.7
100.0
2
3.7
3
40.5
50
360
208/230-3-60
55.8
340.0
2
13.4
5
152.4
200
460-3-60
26.9
173.0
2
6.6
5
73.7
100
575-3-60
23.7
132.0
2
5.4
5
64.1
80
FLA
—
Full Load Amps
HACR
—
Heating, Air Conditioning, and Refrigeration
LRA
—
Locked Rotor Amps
RLA
—
Rated Load Amps
Summary of Contents for Aquazone 50HQP 072
Page 23: ...23 Fig 20 Single Phase with WSHP Open ...
Page 26: ...26 Fig 23 3 Phase with WSHP Open ...
Page 28: ...28 Fig 25 3 Phase Deluxe D Control Package with 1 Speed VFD and Hot Gas Reheat ...
Page 29: ...29 Fig 26 3 Phase with WSHP Open Hot Gas Reheat Water Economizer and SAVTM ...
Page 31: ...31 Fig 28 WSHP Open W2A Wiring Diagram ...