background image

7

Avoid spilling liquid refrigerant on skin or splashing it into 

the eyes. Use safety goggles and safety gloves. Wash any 

spills from the skin with soap and water. If liquid refrigerant 

enters the eyes, immediately and abundantly flush the eyes 

with water and consult a doctor.
The accidental releases of the refrigerant, due to small leaks 

or significant discharges following the rupture of a pipe or 

an  unexpected  release  from  a  safety  valve,  can  cause 

frostbites  and  burns  to  personnel  exposed.  Do  not  ignore 

such  injuries.  Installers,  owners  and  especially  service 

engineers for these units must:

 

-

Seek medical attention before treating such injuries.

 

-

Have access to a first-aid kit, especially for treating 

eye injuries.

We recommend to apply standard EN 378-3 Annex 3.
Never  apply  an  open  flame  or  live  steam  to  a  refrigerant 

container.  Dangerous  overpressure  can  result.  If  it  is 

necessary to heat refrigerant, use only warm water.

During refrigerant removal and storage operations follow applicable 
regulations. These regulations, permitting conditioning and recovery 
of halogenated hydrocarbons under optimum quality conditions 
for the products and optimum safety conditions for people, property 
and the environment are described in standard NF E29-795.

Any refrigerant transfer and recovery operations must be carried 
out using a transfer unit. A 3/8” SAE connector on the manual liquid 
line valve is supplied with all units for connection to the transfer 

station. The units must never be modified to add refrigerant and oil 

charging, removal and purging devices. All these devices are 

provided with the units. Please refer to the certified dimensional 

drawings for the units.

Do  not  re-use  disposable  (non-returnable)  cylinders  or 

attempt  to  refill  them.  It  is  dangerous  and  illegal.  When 

cylinders are empty, evacuate the remaining gas pressure, 

and  move  the  cylinders  to  a  place  designated  for  their 

recovery. Do not incinerate them.

ATTENTION: Only use refrigerant R134a, in accordance with 

700 AHRI (Air conditioning, Heating and Refrigertion Institute). 

The use of any other refrigerant may expose users and ope

-

rators to unexpected risks.
Do not attempt to remove refrigerant circuit components or 

fittings, while the machine is under pressure or while it is 

running. Be sure pressure is at 0 kPa and that the unit has 

been  shut-down  and  de-energised  before  removing 

components or opening a circuit.

Do not attempt to repair or recondition any safety devices when 

corrosion or build-up of foreign material (rust, dirt, scale, etc.) 

is found within the valve body or mechanism. If necessary, 

replace  the  device.  Do  not  install  relief  valves  in  series  or 

backwards.
ATTENTION: No part of the unit must be used as a walk-way, 

rack or support. Periodically check and repair or if necessary 

replace any component or piping that shows signs of damage.
The refrigerant lines can break under the weight and release 

refrigerant, causing personal injury.
Do not climb on a machine. Use a platform, or staging to work 

at higher levels.

Use mechanical lifting equipment (crane, hoist, winch, etc.) to 

lift or move heavy components. For lighter components, use 

lifting equipment when there is a risk of slipping or losing 

your balance.

Use  only  original  replacement  parts  for  any  repair  or 

component replacement. Consult the list of replacement parts 

that  corresponds  to  the  specification  of  the  original 

equipment.
Do  not  drain  water  circuits  containing  industrial  brines, 

without  informing  the  technical  service  department  at  the 

installation site or a competent body first.
Close the entering and leaving water shutoff valves and purge 

the  unit  water  circuit,  before  working  on  the  components 

installed on the circuit (screen filter, pump, water flow switch, 

etc.).
Do not loosen the water box bolts until the water boxes have 

been completely drained.
Periodically  inspect  all  valves,  fittings  and  pipes  of  the 

refrigerant and hydraulic circuits to ensure that they do not 

show any corrosion or any signs of leaks.
It is recommended to wear ear defenders, when working near 

the unit and the unit is in operation.

1 - INTRODUCTION

Summary of Contents for AquaForce 30XB series

Page 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Air Cooled Screw Chillers 30XB 30XBP Unit with options 15 23A Nominal cooling capacity 270 1688 kW 50Hz...

Page 2: ...UNITS 17 4 1 Physical data 30XB 17 4 2 Physical data 30XBP 21 4 3 Physical data 30XB with option 254 or 255 25 4 4 Short circuit stability current for all units 28 4 5 Electrical data 29 4 6 Compresso...

Page 3: ...rect drive twin screw compressor with variable capacity slide valve 57 11 2 Pressure vessels 57 11 3 High pressure safety switch 58 11 4 Condensers 58 11 5 Fans 58 11 6 Electronic expansion valve EXV...

Page 4: ...applies to fuse plugs and relief valves if used in the refrigerant or heat transfer medium circuits Check if the original protection plugs are still present at the valve outlets These plugs are genera...

Page 5: ...He must have been trained and be familiar with the equipment and the installation All welding operations must be carried out by qualified specialists Any manipulation opening or closing of a shut off...

Page 6: ...ect the protection devices more frequently Regularly carry out leak tests and immediately repair any leaks Ensure regularly that the vibration levels remain acceptable and close to those at the initia...

Page 7: ...ly use refrigerant R134a in accordance with 700 AHRI Air conditioning Heating and Refrigertion Institute The use of any other refrigerant may expose users and ope rators to unexpected risks Do not att...

Page 8: ...Unit leak test pressure Voltage frequency number of phases Maximum current drawn Maximum power input Unit net weight Confirm that all accessories ordered for on site installation have been supplied a...

Page 9: ...WARNING Never push or lever on any of the enclosure panels of the unit Only the base of the unit frame is designed to withstand such stresses If a unit includes a hydraulic module options 116B C F G t...

Page 10: ...tioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to...

Page 11: ...weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to walls please refer to chapter...

Page 12: ...ng points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to walls please refer...

Page 13: ...ning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to wal...

Page 14: ...ning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to wal...

Page 15: ...f the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to walls ple...

Page 16: ...er distributor to evaluate the various possible arrangements In certain situations an accessory supplied loose at the time of purchase can be added 3 14 Distance to the wall To ensure correct operatio...

Page 17: ...6 4929 5060 5358 5669 Unit option 50 3 kg 3370 3404 3425 4102 4245 4601 5551 5782 6065 6382 Compressors 06T semi hermetic screw compressor 50 r s Circuit A 1 1 1 1 1 1 1 1 1 1 Circuit B 1 1 1 1 1 1 1...

Page 18: ...r heat exchanger Flooded multi pipe type Water volume l 58 61 61 66 70 77 79 94 98 119 Max water side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000...

Page 19: ...Compressors 06T semi hermetic screw compressor 50 r s Circuit A 1 1 1 1 1 1 1 1 1 1 Circuit B 1 1 1 1 1 1 1 1 1 1 Circuit C 1 1 Circuit D 1 No of control stages Refrigerant for standard unit 4 R134a C...

Page 20: ...15 7 15 7 15 7 15 7 15 7 15 7 15 7 Unit option 15LS Maximum total air flow l s 47160 47160 55020 62880 70740 78600 78600 86460 94320 110040 Maximum rotation speed r s 11 7 11 7 11 7 11 7 11 7 11 7 11...

Page 21: ...424 5707 6018 Compressors 06T semi hermetic screw compressor 50 r s Circuit A 1 1 1 1 1 1 1 1 1 1 Circuit B 1 1 1 1 1 1 1 1 1 1 No of control stages Refrigerant for standard unit 4 R134a Circuit A kg...

Page 22: ...exchanger Flooded multi pipe type Water volume l 58 61 61 66 70 77 79 94 98 119 Max water side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Hydraul...

Page 23: ...emi hermetic screw compressor 50 r s Circuit A 1 1 1 1 1 1 1 1 Circuit B 1 1 1 1 1 1 1 1 No of control stages Refrigerant for standard unit 4 R134a Circuit A kg 72 69 75 76 76 110 116 132 teqCO2 103 0...

Page 24: ...11 7 11 7 11 7 11 7 11 7 11 7 11 7 11 7 Water heat exchanger Flooded multi pipe type Water volume l 119 130 140 164 174 180 189 189 Max water side operating pressure without hydraulic module kPa 1000...

Page 25: ...4261 4324 4776 5578 5692 6386 6675 Compressors 06T semi hermetic screw compressor 50 r s Circuit A 1 1 1 1 1 1 1 1 1 1 Circuit B 1 1 1 1 1 1 1 1 1 1 No of control stages Refrigerant for standard unit...

Page 26: ...7 11 7 11 7 11 7 Water heat exchanger Flooded multi pipe type Water volume l 58 61 61 66 70 77 79 94 98 119 Max water side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 100...

Page 27: ...06T semi hermetic screw compressor 50 r s Circuit A 1 1 1 1 1 1 1 1 1 Circuit B 1 1 1 1 1 1 1 1 1 Circuit C 1 1 Circuit D 1 No of control stages Refrigerant for standard unit 4 R134a Circuit A kg 130...

Page 28: ...ed multi pipe type Water volume l 119 130 140 164 174 180 189 240 240 Max water side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 Water connections with...

Page 29: ...operating current draw Un 1 30XBP Standard unit A 192 214 236 270 311 341 419 452 507 537 583 622 720 Unit option 15LS A 186 208 230 262 303 333 408 440 495 525 571 610 706 Maximum current Un 10 1 30...

Page 30: ...92 356 386 390 273 446 Option 081 A 616 666 697 742 780 820 Unit option 15LS Circuit 1 a A 247 263 325 340 372 530 427 Circuit 2 a A 344 374 340 370 372 260 427 Option 081 A 590 637 665 710 745 782 Ma...

Page 31: ...2 Standard unit Circuit 1 a A 587 587 629 629 629 954 812 Circuit 2 a A 629 629 629 629 629 477 812 Option 081 A 1046 1095 1095 1130 1134 1431 Option 081 Opt 25c 802 820 844 862 862 Unit option 15LS C...

Page 32: ...346 376 379 Option 081 A 600 648 677 722 758 Unit option 15LS Circuit 1 a A 244 260 321 336 368 Circuit 2 a A 335 363 330 360 361 Option 081 A 584 630 657 702 736 Maximum operating current draw Un 1...

Page 33: ...t up current Un 2 Standard unit Circuit 1 a A 580 580 619 619 618 Circuit 2 a A 620 618 619 619 618 Option 081 A 1030 1077 1075 1110 1112 Option 081 Opt 25c A 786 801 5 824 841 5 839 5 Unit option 15L...

Page 34: ...220 245 278 319 352 430 464 522 552 601 643 743 Unit option 15LS A 188 210 234 265 306 338 412 445 502 532 580 621 717 Maximum current Un 10 1 Standard unit A 198 220 245 278 319 352 430 464 522 552 6...

Page 35: ...d unit Circuit 1 a A 261 274 341 356 390 543 446 Circuit 2 a A 364 392 356 386 390 273 446 Option 081 A 625 666 697 742 780 820 Unit option 15LS Circuit 1 a A 247 265 325 340 372 530 427 Circuit 2 a A...

Page 36: ...current locked rotor current or reduced start up current of the largest compressor 3 Standardised EUROVENT conditions water cooled exchanger water inlet outlet 12 C 7 C outdoor air temperature 35 C a...

Page 37: ...st not be connected directly to the unit if necessary use a transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch...

Page 38: ...l load and nominal voltage 88 1 89 4 89 4 90 1 91 3 91 3 1 Nominal efficiency at 75 full load and nominal voltage 88 0 88 9 88 9 89 7 91 4 91 4 1 Nominal efficiency at 50 full load and nominal voltage...

Page 39: ...switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see electrical data tables The calculati...

Page 40: ...phase m Standard unit 250 2 185 1 x 95 190 XLPE Cu 2 x 95 450 PVC Cu 300 2 185 1 x 95 190 XLPE Cu 2 x 95 420 PVC Cu 350 2 185 1 x 120 197 XLPE Cu 2 x 95 390 PVC Cu 400 2 185 1 x 150 200 XLPE Cu 2 x 1...

Page 41: ...8 10 Condenser air temperature Minimum Maximun Storage 20 68 Operation standard unit 10 55 2 With winter operation option option 28 20 55 2 With Low noise option option 15LS 10 52 2 Note If the air te...

Page 42: ...below Connection to a buffer tank Bad Bad Good Good 6 6 Maximum system water volume Units with hydraulic module incorporate an expansion tank that limits the water volume The table below gives the max...

Page 43: ...6 500 7 600 Water flow rate l s Pressure drop kPa 1 3 7 4 5 2 6 10 100 10 Sizes 700 1700 Legend 1 700 2 750 3 800 4 850 5 900 6 1000 7 1100 8 1200 9 1300 10 1400 11 1500 12 1550 13 1700 Water flow ra...

Page 44: ...ge fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping could generate eletrolytic pairs and consequently corrosion Verify then the need...

Page 45: ...6 6 6 6 6 8 5 6 6 Actual outside diameter mm 141 3 141 3 168 3 168 3 168 3 168 3 168 3 168 3 219 1 141 3 168 3 168 3 Options 100C Nominal diameter in 6 6 8 Actual outside diameter mm 168 3 168 3 219...

Page 46: ...K below the lowest temperature likely to occur at the installation site If the unit is not used for an extended period it is recommended to drain it and as a safety precaution add ethylene glycol to t...

Page 47: ...XB XBP 400 5 30XB XBP 450 6 30XB XBP 500 1 30XB XBP 250 2 30XB XBP 300 3 30XB XBP 350 4 30XB XBP 400 5 30XB XBP 450 6 30XB XBP 500 Single pump low pressure 0 20 40 60 80 100 120 140 160 180 200 3 5 7...

Page 48: ...e maximum water flow is reduced When the glycol is used it s limited to 40 Available static pressure kPa Water flow rate l s Low pressure pumps options 116F 116G 252 302 350 400 450 500 0 10 20 30 40...

Page 49: ...alve 8 Free cooling expansion device EXV 9 Refrigerant pump The change over between the cooling and free cooling modes is automatically controlled it is possible to block the change over to free cooli...

Page 50: ...unit The sealing joints are in the control box The temperature sensors and the condenser flow switch are wired and fixed in the machine They must be installed as described in the chapter Condenser wat...

Page 51: ...fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to walls please r...

Page 52: ...he fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to walls please...

Page 53: ...distribution and centre of gravity coordinates please refer to the dimensional drawings If the installation includes several units or if this these is are close to walls please refer to chapters 3 11...

Page 54: ...laim at low entering water temperature 12 5 C It also ensures an optimal and controlled leaving water temperature 9 5 Operating limits for stable operation no mode changeover 9 5 1 Cooling only mode P...

Page 55: ...anges may lead to higher sound levels than the levels at stable operation Depending on the mode selected heat reclaim or cooling the logic compares the water entering temperature required with the set...

Page 56: ...has been selected the fans with available pressure are equipped with discharge connection flanges to facilitate the duct connection NOTE Each fan must be individually ducted 10 FANS WITH AVAILABLE PR...

Page 57: ...of re testing please refer to the maximum operating pressure given on the unit nameplate The reports of periodical checks by the user or operator must be included in the supervision and maintenance f...

Page 58: ...on the pressure switch and push the reset button in this location These pressure switches are located at the discharge of each compressor 11 4 Condensers 30XB coils are all aluminium micro channel co...

Page 59: ...element A difference in tempera ture between the filter inlet and outlet shows that the element is dirty 11 9 Sensors The units use thermistors to measure the temperature and pressure transducers to...

Page 60: ...1 5 1 6 1 2 1 3 1 7 1 4 1 8 2 7 2 5 2 8 2 4 2 7 2 5 2 3 2 2 2 6 2 1 2 6 30XBP 1200 30XB 1200 option 254 255 1 1 1 5 1 6 1 2 1 3 1 7 1 4 1 8 2 8 2 5 2 8 2 4 2 7 2 5 2 3 2 2 2 6 2 1 2 6 2 7 30XB XBP 130...

Page 61: ...and piping protection against impacts 30XB 30XBP 250 1700 Enclosure panels 23A Side enclosure panels at each end of the coil Improves aesthetics coil and piping protection against impacts 30XB 30XBP 2...

Page 62: ...ralian code Conformance with Australian regulations 30XB 30XBP 250 1700 Power factor correction 231 Capacitors for automatic regulation of power factor cos phi value to 0 95 Reduction of the apparent...

Page 63: ...the water connections Purge the water circuit Clean the water filter Fully clean the condensers with a low pressure jet and a bio degradable cleaner counter current cleaning see chapter 13 6 2 Level...

Page 64: ...l of harmful residue will increase the operating life of the coils and the unit The maintenance and cleaning procedures below are part of the regular maintenance and will prolong the life of the coils...

Page 65: ...he water side connections are clean and show no sign of leakage 13 8 Compressor maintenance 13 8 1 Oil separator Check the correct operation of the heaters and check that they are well attached to the...

Page 66: ...tact block Connection of the contactor or current transformer 1 2 2 1 Power supply bus bar with riveted contact block 2 Contactor or current transformer connection zone 13 10 Check of power factor cor...

Page 67: ...onnected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is connected properly All air has been v...

Page 68: ...l corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for...

Page 69: ......

Page 70: ...No 10224 11 2017 Supersedes order No 10224 09 2017 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: