31
4.5 - Electrical data (continued)
30XB from 1100 to 1700 (continued)
30XB
1100
1200
1300
1400
1500
1550
1700
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A
320
366
440
470
509
740
593
Circuit 2
(a)
A
466
509
470
505
509
370
593
Option 081
A
788
877
912
977
1020
1113
Unit + option 15LS
Circuit 1
(a)
A
309
355
424
454
491
727
574
Circuit 2
(a)
A
452
491
454
489
491
357
574
Option 081
A
762
848
880
945
985
1074
Nominal start-up current
(3)
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
954
812
Circuit 2
(a)
A
629
629
629
629
629
477
812
Option 081
A
940
980
985
1015
1019
1316
Option 081 & Opt 25c
A
802
820
844
862
862
Unit + option 15LS
Circuit 1
(a)
A
576
576
613
613
611
941
793
Circuit 2
(a)
A
615
611
613
613
611
464
793
Option 081
A
914
951
953
983
984
1290
Option 081 & Opt 25c
A
776
791
812
830
826
Maximum start-up current(Un)
(2)
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
954
812
Circuit 2
(a)
A
629
629
629
629
629
477
812
Option 081
A
1046
1095
1095
1130
1134
1431
Option 081 & Opt 25c
802
820
844
862
862
Unit + option 15LS
Circuit 1
(a)
A
576
576
613
613
611
941
793
Circuit 2
(a)
A
615
611
613
613
611
464
793
Option 081
1020
1066
1063
1098
1099
1393
Option 081 & Opt 25c
A
776
791
812
830
826
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS