28
4.3 - Physical data 30XB with option 254 or 255 (continued)
30XB-850 to 1700 with option 254 or 255 (continued)
30XB option 254/255
850
900
1000
1100
1200
1300
1400
1550
1700
Capacity control
Touch Pilot, , Electronic Expansion Valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
10
8
Air heat exchanger
Aluminum micro-channel coils (MCHE)
Fans
FLYING-BIRD 6, axial fan with rotating impeller
Standard unit
Quantity
14
15
16
19
20
20
20
24
28
Maximum total air flow
l/s
67480 72300 77120 91580 96400 96400 96400 115680 134960
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
Unit + option 15LS
Maximum total air flow
l/s
55020 58950 62880 74670 78600 78600 78600 94320 110040
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Water heat exchanger
Flooded multi-pipe type
Water volume
l
119
130
140
164
174
180
189
240
240
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
Water connections without or with hydraulic module
Victaulic
®
type
Connections
inch
6
6
8
6
6
6
6
8/6
6
External parameter
(5)
mm
168,3
168,3
219,1
168,3
168,3
168,3
168,3
219,1/
168,3
168,3
Casing paint
Colour code RAL 7035
(5) Depends of options.
4.4 - Short-circuit stability current for all units
30XB/30XBP
250 to 500
600 to 1000
1100 to 1500
1550
1700
Short-circuit whistand current (TN system)
Circuit A+B
KA
38
50
50
50
50
Circuit C+D
kA
NA
NA
50
50
50
Unit + option 81
kA
NA
NA
50
50
NA
(1) If another current limitation protection device is used, its time-current and thermal constraint (I²t) trip characteristics must be at least equivalent to those of the recommended
protection.
Note: The short-circuit stability current values above are suitable with the TN system.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
Summary of Contents for AquaForce 30XB series