Carrier AIRSTREAM 42BHE Installation, Start-Up And Service Instructions Manual Download Page 8

8

To remove filter, slide filter out of filter rack from either side

of return-air duct collar.
THROWAWAY OR PLEATED FILTER  —   Replace  filter

with a good quality filter of the size shown in Table 1. Do not

attempt to clean and reuse a disposable filter.

Recommended Maintenance

Quarterly
• Lubricate motor and blower bearings (if applicable)

• Check and adjust belt tension

• Change air filter
Annually — in addition to quarterly maintenance
• Inspect all wiring connections and tighten if necessary

• Check and tighten set screws on pulleys

• Clean coil and drain pan

• Clean blower wheel as needed

TROUBLESHOOTING

Excessive Condensation on Fan Coil Unit
Parts — 

Excessive condensation can be caused by running

chilled water through a fan coil unit with its fan off. If fan cy-

cling control is used, a water flow control valve should be in-

stalled to shut off the water when the fan stops.

The following two practices will also help avoid condensa-

tion problems:

1. Continuous fan operation with motorized chilled water

valve controlled by thermostat.

2. Continuous fan operation with thermostat control to

switch fan from high to low speed (instead of switching it

off).

Motor Overload — 

The following are causes and reme-

dies for motor trip-out on overload:

Cause:

Fan delivers too much air because external stat-

ic pressure is lower than the design pressure.

Remedy: Reduce fan speed by adjusting motor pulley or

changing fan shaft pulley to larger diameter.

Cause:

Air temperature across fan motor is too high

(heating mode).

Remedy: Check ambient temperature on motor’s name-

plate. Compare to actual air temperature at the

motor or at the fan discharge. If motor’s name-

plate lists an ambient temperature of 104 F and

the actual air temperature is higher, either low-

er the air temperature or obtain a special motor

rated for high ambient temperatures.

Summary of Contents for AIRSTREAM 42BHE

Page 1: ...ty or equip ment use good judgment and follow safe practices as outlined below when installing and operating this equipment INTRODUCTION The following contains general installation instructions for th...

Page 2: ...ements Refer to job drawings and product dimension drawings as re quired Instruct all trades in the appropriate part of the installa tion For unit component identification refer to Fig 1 For unit dime...

Page 3: ...side or bottom of the filter rack on horizontal unit 42BHE If side access to filter is desired the minimum clearance required is the width of the filter rack plus 6 inches 6 Protect unit from damage f...

Page 4: ...g and valves not located over drain pans or drip lips must be insulated to prevent damage from sweating Vent all coils during final preparations See Step 10 section 6 Check interior unit piping for si...

Page 5: ...3 42BHE BVE ELECTRIC HEATER DATA Table 4 MOTOR PERFORMANCE DATA FULL LOAD AMPS NOTES 1 Motor full load amps refer to National Electric Code NEC amps actual motor nameplate amps may vary 2 NEC data ext...

Page 6: ...ilter access panel Step 10 Make Final Preparations 1 TURN POWER OFF Open unit electrical disconnect 2 Clean unit thoroughly Remove dirt and debris from unit especially drain pan drain line motor and f...

Page 7: ...perating conditions specified at the time of order entry Proper belt drive alignment and tension must be maintained when adjusting the unit fan drive speed The drive belt tension should not exceed 3 1...

Page 8: ...ld be in stalled to shut off the water when the fan stops The following two practices will also help avoid condensa tion problems 1 Continuous fan operation with motorized chilled water valve controll...

Page 9: ......

Page 10: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420006 01 Printed in U S A Form 42B 3SI Pg 10 2 11 Replaces 42B 2SI Cop...

Page 11: ...valve Yes No 13 Open air vent on top of coil to vent air out of system Yes No 14 Open return ball valve Yes No 15 Engage power only long enough to verify proper blower rotation Yes No 16 Check all du...

Page 12: ...______________________________________ ________________________________________________________________________________________________________ ________________________________________________________...

Reviews: