5
Step 7 — Make Electrical Connections —
Refer to
the unit rating plate for supply voltage, motor and heater am-
perage, and required circuit ampacities. (See Tables 2 - 4.) The
unit wiring diagram shows all factory and field wiring. Most of
the unit motors are dual voltage that are factory wired for a
specified voltage. The motors should be checked to ensure that
they are wired for the correct voltage and rotation.
Units equipped with factory-installed motor controls and
disconnect will comply with NEC requirements for disconnect,
motor controller and motor overload protection. Separate dis-
connect and motor starter are not required to comply with NEC
requirements.
All field wiring should be done in accordance with all appli-
cable local and national codes. Any factory wiring modifica-
tions without factory authorization will void all factory warran-
ties and nullify any agency listings.
The manufacturer assumes no responsibility for any dam-
age and/or injuries resulting from improperly installed or wired
components.
Install fan switches, thermostats and other accessories in
accordance with accessory manufacturer’s instructions and ap-
plicable wiring diagram.
Table 2 — 42BHE,BVE ELECTRIC HEATER DATA
AVAILABILITY
LEGEND
NOTES:
1. Stages available:
a. Single phase: 1 to 12 kW, 1 stage only
3 to 12 kW, 1 stage or 2 stage
b. Three phase: 1 to 39.9 kW, 1 stage only
4 to 39.9 kW, 1 or 2 stage
12 to 39.9 kW, 1, 2 or 3 stage
2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power = (Heater
kW x 1000)/Applied Voltage
Electric Heater Amp. for 3-phase Power = (Heater kW x 1000)/
(Applied Voltage x 1.73).
Table 3 — 42BHE,BVE ELECTRIC HEATER DATA
Table 4 — MOTOR PERFORMANCE DATA (FULL
LOAD AMPS)
NOTES:
1. Motor full load amps refer to National Electric Code (NEC)
amps; actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750
rpm rated at continuous duty, 104 F ambient with reversible
rotation.
4. 5HP motors available only on size 40 units.
SERVICE SWITCHES: — The service switch is an On/Off
switch on incoming power supply to unit. Proper amperage
load must be determined before switch can be selected. The
range of the fused or non-fused service switch is 0 to 40
amps.
Amp Load =
[Motor amps + Heater amps (if required)] x 1.20.
kW
42BHE UNIT SIZE
06
08
10
12
16
20
30
40
1.0
●
●
—
—
—
—
—
—
1.5
●
●
●
●
—
—
—
—
2.0
●
●
●
●
—
—
—
—
2.5
●
●
●
●
●
—
—
—
3.0
●
●
●
●
●
—
—
—
3.5
●
●
●
●
●
●
—
—
4.0
●
●
●
●
●
●
—
—
4.5
●
●
●
●
●
●
—
—
5.0
●
●
●
●
●
●
—
—
6.0
●
●
●
●
●
●
●
●
7.0
—
●
●
●
●
●
●
●
8.0
—
●
●
●
●
●
●
●
9.9
—
—
●
●
●
●
●
●
12.0
—
—
—
●
●
●
●
●
14.0
—
—
—
—
●
●
●
●
15.0
—
—
—
—
●
●
●
●
16.0
—
—
—
—
●
●
●
●
18.0
—
—
—
—
—
●
●
●
19.9
—
—
—
—
—
●
●
●
25.0
—
—
—
—
—
—
●
●
30.0
—
—
—
—
—
—
●
●
35.0
—
—
—
—
—
—
—
●
39.9
—
—
—
—
—
—
—
●
●
—
Standard Offering
—
—
Not Offered
kW
FULL LOAD AMPS
Single-Phase
Three-Phase
115 V
208 V
240 V
277 V
208 V
240 V
480 V
1.0
8.3
4.8
4.2
3.6
2.8
2.4
1.2
1.5
12.5
7.2
6.3
5.4
4.2
3.6
1.8
2.0
16.7
9.6
8.3
7.2
5.6
4.8
2.4
2.5
20.8
12.0
10.4
9.0
6.9
6.0
3.0
3.0
25.0
14.4
12.5
10.8
8.3
7.2
3.6
3.5
29.2
16.8
14.6
12.6
9.7
8.4
4.2
4.0
33.3
19.2
16.7
14.4
11.1
9.6
4.8
4.5
37.5
21.6
18.8
16.2
12.5
10.8
5.4
5.0
—
24.0
20.8
18.1
13.9
12.0
6.0
6.0
—
28.8
25.0
21.7
16.7
14.4
7.2
7.0
—
33.7
29.2
25.3
19.4
16.8
8.4
8.0
—
38.5
33.3
28.9
22.2
19.2
9.6
9.9
—
—
—
35.7
27.5
23.8
11.9
12.0
—
—
—
43.3
33.3
28.9
14.4
14.0
—
—
—
—
38.9
33.7
16.8
15.0
—
—
—
—
41.6
36.1
18.0
16.0
—
—
—
—
—
38.5
19.2
18.0
—
—
—
—
—
—
21.7
19.9
—
—
—
—
—
—
23.9
25.0
—
—
—
—
—
—
30.1
30.0
—
—
—
—
—
—
36.1
35.0
—
—
—
—
—
—
42.1
39.9
—
—
—
—
—
—
48.0
VOLTAGE
V-Ph-Hz
Nominal HP
1
/
4
1
/
3
1
/
2
3
/
4
1
1
1
/
2
2
3
5
115-1-60
5.2
6.0
8.6
13.3 14.4
—
—
—
—
208-1-60
3.0
3.6
4.8
6.6
7.4
9.4
11.0
—
—
230-1-60
2.5
3.0
4.2
5.1
6.0
9.0
10.9
—
—
277-1-60
2.1
2.5
3.6
5.1
5.4
8.5
8.0
—
—
208-3-60
—
—
2.4
3.6
3.8
6.0
6.5
8.2
14.0
230-3-60
—
—
2.2
3.0
3.2
4.8
6.2
8.0
13.2
460-3-60
—
—
1.1
1.5
1.9
2.8
3.1
4.0
6.6
Summary of Contents for AIRSTREAM 42BHE
Page 9: ......