Step 8 — Make Duct Connections — 

Install all duct-

work to and from unit in accordance with all applicable codes.

Duct construction must allow unit to operate within the limits of

the unit external static pressure as shown on job submittals.

Units designed to operate with ductwork may be damaged if

operated without the intended ductwork attached. Units config-

ured to bring in outside air should have some method of low

temperature protection to prevent coil freeze-up.

Insulate all ductwork as required. Use flexible connections

to minimize duct-to-duct alignment problems and noise trans-

mission where specified. Acoustic lining of main supply and

return duct should be considered for noise control. Noise trans-

mission will be reduced when return grilles are located as far as

possible from the unit.

Install ductwork, accessory grilles, and plenums so that they

do not restrict access to filter.

NOTE: Prevent dirt, dust, and debris from settling in unit

.

Step 9 — Install Mixing Box — 

Mixing boxes are

preassembled from the factory. A linkage kit consisting of

2 crankarms, 2 swivels, and either a 25 in. (unit sizes 06-16) or

a 34 in. (unit sizes 20-40) length of 

5

/

16

 in. rod is provided for

field installation of the actuator.

To install the mixing box:

1. Assemble the mixing box base rails using the provided

hardware. The base rails are marked with identifying let-

ters. See Fig. 5.

2. Place unit on the base rails. Install mixing box and attach

to base rails using the no. 8 x 

1

/

2

 in. fasteners at the loca-

tions shown in Fig. 6.

3. Seal the connection between the mixing box and the re-

turn duct flange.
NOTE: Be careful not to tape or seal the filter access

panel.

Step 10 — Make Final Preparations

1. TURN POWER OFF. (Open unit electrical disconnect.)
2. Clean unit thoroughly. Remove dirt and debris from unit,

especially drain pan, drain line, motor and fan. Pour water

into drain pan to check that drain operates properly.

3. Rotate fan wheel by hand to be sure wheel is free and

does not rub housing. The 42BHE,BVE belt drives are

factory set at the speed required for the design specifica-

tions specified when ordered. These drives may be ad-

justed to achieve different speed by qualified personnel

during air system balancing. Refer to the Start-Up section

before energizing the unit. Check fan belt tension as de-

scribed in the Service section which follows.

4. Check that a clean air filter of proper type and size is in-

stalled in unit filter rack after commissioning. See Table 1

and Clean or Replace Air Filters section. Do NOT oper-

ate unit without filter.

5. Turn on water supply. Open all valves. Check for leaks.

Recheck pitch of suspended unit.

6. Vent all air from unit coil and related piping. If air vent is

manual, release air by turning air vent screw 1

1

/

2

 turns

counterclockwise with screwdriver. When a steady

stream of water begins to escape, close valve. If vent is

automatic, trapped air will be released automatically. Vent

releases air slowly, usually dripping water into the drain

pan in the process.

Fig. 5 — Assemble Base Rails

a42-4164

a42-4165

CAUTION

The air vent provided on the unit is not intended to replace

the main system vents and may not release air trapped in

other parts of the system. Inspect the entire system for

potential air traps and vent those areas as needed. Some

systems may require repeated venting over a period of time

to properly eliminate air from the system. Failure to do so

could result in equipment damage.

Fig. 6 — Install  Mixing Box

a42-4166

Summary of Contents for AIRSTREAM 42BHE

Page 1: ...ty or equip ment use good judgment and follow safe practices as outlined below when installing and operating this equipment INTRODUCTION The following contains general installation instructions for th...

Page 2: ...ements Refer to job drawings and product dimension drawings as re quired Instruct all trades in the appropriate part of the installa tion For unit component identification refer to Fig 1 For unit dime...

Page 3: ...side or bottom of the filter rack on horizontal unit 42BHE If side access to filter is desired the minimum clearance required is the width of the filter rack plus 6 inches 6 Protect unit from damage f...

Page 4: ...g and valves not located over drain pans or drip lips must be insulated to prevent damage from sweating Vent all coils during final preparations See Step 10 section 6 Check interior unit piping for si...

Page 5: ...3 42BHE BVE ELECTRIC HEATER DATA Table 4 MOTOR PERFORMANCE DATA FULL LOAD AMPS NOTES 1 Motor full load amps refer to National Electric Code NEC amps actual motor nameplate amps may vary 2 NEC data ext...

Page 6: ...ilter access panel Step 10 Make Final Preparations 1 TURN POWER OFF Open unit electrical disconnect 2 Clean unit thoroughly Remove dirt and debris from unit especially drain pan drain line motor and f...

Page 7: ...perating conditions specified at the time of order entry Proper belt drive alignment and tension must be maintained when adjusting the unit fan drive speed The drive belt tension should not exceed 3 1...

Page 8: ...ld be in stalled to shut off the water when the fan stops The following two practices will also help avoid condensa tion problems 1 Continuous fan operation with motorized chilled water valve controll...

Page 9: ......

Page 10: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420006 01 Printed in U S A Form 42B 3SI Pg 10 2 11 Replaces 42B 2SI Cop...

Page 11: ...valve Yes No 13 Open air vent on top of coil to vent air out of system Yes No 14 Open return ball valve Yes No 15 Engage power only long enough to verify proper blower rotation Yes No 16 Check all du...

Page 12: ...______________________________________ ________________________________________________________________________________________________________ ________________________________________________________...

Reviews: