Carrier AIRSTREAM 42BHE Installation, Start-Up And Service Instructions Manual Download Page 3

3

Step 4 — Prepare Unit — 

Be sure that unit power re-

quirements match available power source. Refer to unit name-

plate and wiring diagram. Check all tags on unit to determine if

any shipping screws are to be removed. Remove screws as

directed.

Step 5 — Position Unit

1. The air handler has 

5

/

8

-in. knockouts in each corner of the

top and bottom panels for suspension rods to pass

through. Be sure to support the unit from underneath until

mounting is complete. 

2. Install vibration isolators as shown in Fig. 1. Field-

supplied and field-installed accessories must be indepen-

dently supported or suspended. It is recommended that a

trapeze suspension be used on 42BHE size 30 and 40

units. Size your trapeze to ensure that you do not block

bottom access for filter removal.

3. For units with mixing boxes, follow Step 9 for installation

instructions.

4. To ensure proper drainage and operation, be sure unit is

level. DO NOT mount the unit on a slope. The pitch of a

suspended unit can change after coil is filled; recheck

after filling. Drain pan has built-in slope to ensure proper

drainage.

5. Sufficient clearance must be maintained for service and

maintenance. Ensure that there is a minimum clearance of

24-in. on access side for motor, pulley and belt access.

Filter shall be removed from side or top of the filter rack

on vertical unit (42BVE) and side or bottom of the filter

rack on horizontal unit (42BHE). If side access to filter is

desired, the minimum clearance required is the width of

the filter rack plus 6 inches. 

6. Protect unit from damage from jobsite debris. Do not

allow foreign material to fall into drain pan. Prevent dust

and debris from being deposited on motor or fan.

C

A

7-7/16

TOP VIEW

2-1/16

B

4 X 4 JBOX AND MOTOR

MOUNTED SAME SIDE AS

COIL CONNECTIONS

DEPTH

1-7/16

1" SUPPLY AIR
COLLAR

SUPPL

Y AIR

BOTH SIDES
AND FRONT
PANEL WITH
CAMLOCK
ACCESS

4-3/8
ADD 2" FOR
MERV11 FILTER

HEIGHT

RETURN AIR

COIL RETURN CONN.

COIL SUPPLY CONN.

COIL DRAIN CONN.

[MALE 3/4-14 NPT]

[MALE 1/2-14 NPT SECONDARY]

SIDE VIEW

FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES AND TOP

1" RETURN AIR COLLAR

2

E

WIDTH

FRONT VIEW

F

1"

Fig. 3 — Unit Dimensions — 42BVE Units

NOTES:

1. All dimensions are in inches (±

1

/

4

 in.).

2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to

change without notice.

3. Left hand shown, right hand opposite.

UNIT

42BVE

DIMENSIONS (in.)

Fan Size

Depth

Width

Height

Supply Duct

Return Duct

A

B

C

E

F

06

9 x  4

20

28

36

1

/

2

7

1

/

8

10

1

/

2

17

1

/

4

24

16

1

/

2

08

9 x  6

20

28

36

1

/

2

8

1

/

2

10

1

/

2

15

3

/

4

24

16

1

/

2

10

10 x  4

22

37

39

3

/

8

7

1

/

8

11

9

/

16

24

1

/

2

33

18

1

/

3

12

10 x  7

22

37

39

3

/

8

9

15

/

16

11

9

/

16

21

1

/

2

33

18

1

/

3

16

11 x 10

22

47

39

3

/

8

13

3

/

8

12

3

/

4

16

3

/

4

43

18

1

/

3

20

12 x  9

24

48

45

1

/

8

12

1

/

2

13

3

/

4

17

3

/

4

44

20

3

/

4

30

12 x 12

28

48

54

3

/

16

15

7

/

8

13

3

/

4

16

44

29

40

15 x 12

28

62

57

5

/

8

16

7

/

16

16

1

/

16

22

3

/

4

58

29

a42-4259

Summary of Contents for AIRSTREAM 42BHE

Page 1: ...ty or equip ment use good judgment and follow safe practices as outlined below when installing and operating this equipment INTRODUCTION The following contains general installation instructions for th...

Page 2: ...ements Refer to job drawings and product dimension drawings as re quired Instruct all trades in the appropriate part of the installa tion For unit component identification refer to Fig 1 For unit dime...

Page 3: ...side or bottom of the filter rack on horizontal unit 42BHE If side access to filter is desired the minimum clearance required is the width of the filter rack plus 6 inches 6 Protect unit from damage f...

Page 4: ...g and valves not located over drain pans or drip lips must be insulated to prevent damage from sweating Vent all coils during final preparations See Step 10 section 6 Check interior unit piping for si...

Page 5: ...3 42BHE BVE ELECTRIC HEATER DATA Table 4 MOTOR PERFORMANCE DATA FULL LOAD AMPS NOTES 1 Motor full load amps refer to National Electric Code NEC amps actual motor nameplate amps may vary 2 NEC data ext...

Page 6: ...ilter access panel Step 10 Make Final Preparations 1 TURN POWER OFF Open unit electrical disconnect 2 Clean unit thoroughly Remove dirt and debris from unit especially drain pan drain line motor and f...

Page 7: ...perating conditions specified at the time of order entry Proper belt drive alignment and tension must be maintained when adjusting the unit fan drive speed The drive belt tension should not exceed 3 1...

Page 8: ...ld be in stalled to shut off the water when the fan stops The following two practices will also help avoid condensa tion problems 1 Continuous fan operation with motorized chilled water valve controll...

Page 9: ......

Page 10: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420006 01 Printed in U S A Form 42B 3SI Pg 10 2 11 Replaces 42B 2SI Cop...

Page 11: ...valve Yes No 13 Open air vent on top of coil to vent air out of system Yes No 14 Open return ball valve Yes No 15 Engage power only long enough to verify proper blower rotation Yes No 16 Check all du...

Page 12: ...______________________________________ ________________________________________________________________________________________________________ ________________________________________________________...