System Fan Coil Unit

HVAC Guide Specifications — 42B

Size Range: 

600 to 4000 Nominal Cfm

Carrier Model Number: 

    42BHC (Horizontal Fan Coil Unit)
    42BVC (Vertical Fan Coil Unit)
Part 1 — General

1.01 SYSTEM DESCRIPTION

Horizontal and vertical, 2-pipe or 4-pipe, belt-
driven, galvanized casing model fan coil unit for
ducted installation above the ceiling or within
floor mounted cabinet, with full access to internal
components.

1.02 QUALITY ASSURANCE

A. Unit performance shall be rated in accordance with

ARI Standard 440-2005. 

B. Unit construction shall comply with ASHRAE (latest

edition) Safety Code and NEC.

C. Unit shall be constructed in accordance with ETL

and ETL, Canada standards. Factory-installed
motors and electric heaters shall be UL approved.

D. Each coil shall be factory tested for leakage

at 350-psig air pressure with coil submerged
in water. Insulation and adhesive shall meet
NFPA-90A requirements for flame spread and
smoke generation.

E. Each coil shall be factory tested for leakage at

350 psig air pressure with coil submerged in water.
Insulation and adhesive shall meet NFPA-90A
requirements for flame spread and smoke genera-
tion. Factory-installed motors shall be UL approved.

1.03 DELIVERY, STORAGE AND HANDLING

Unit shall be handled and stored in accordance with
the manufacturer’s instructions.

Part 2 — Products

2.01 EQUIPMENT

A. General:

Factory-assembled, horizontal and vertical, draw-
thru type fan coil unit for ducted installation above
the ceiling or floor mounting. Unit shall be complete
with water coils, fan(s), motor, belt drive, drain pan,
and filter.

B. Casing:

Construction shall be heavy-gage galvanized steel,
lined with one-in. thick fiberglass Tuf-Skin™ II
thermal/acoustical insulation. Knockouts shall be
provided for hanging the horizontal unit, that will
accept 

3

/

8

-in. threaded rod at the top, and bottom

of all unit corners. Supply and return duct connec-
tion shall be 1 in. long. Removable side panels shall
be provided for access to the fan/motor assembly. A
double-sloped drain pan shall be constructed of
stainless steel, extending under the full length and
width of the coil(s) with a 

3

/

4

-in. male nominal pipe

thread stainless steel drain connection and 

1

/

2

-in.

male MPT stainless secondary drain connection
(capped when not required). The outside surface of
the drain pan shall be insulated with 

1

/

8

-in. closed

cell insulation.

C. Fans:

Belt-driven, double-width fan wheels shall have
forward-curved blades and be statically and dynami-
cally balanced. Fan drive shall consist of variable-
pitch motor pulley, fixed-pitch fan pulley and V-belt.
Fans and scrolls shall be of galvanized steel.

D. Coils:

Standard unit shall be equipped with a 4-row coil for
installation in a 2-pipe system and additional rows of
coil shall be provided for installation in a 4-pipe sys-
tem as described in the Options and Accessories
section. Coils shall have 

1

/

2

-in. copper tubes, alumi-

num fins bonded to the tubes by mechanical expan-
sion and have a working pressure of 250 psig at
200 F. Each coil shall have a manual air vent and
sweat connections for copper tubes.

E. Operating Characteristics:

A single-circuit coil unit installed in a 2-pipe system
shall be capable of providing heating or cooling as
determined by the operating mode of the central
water supply system. A double-circuit coil unit
installed in a 4-pipe system shall be capable of pro-
viding sequenced heating and cooling.

F. Motor(s):

Fan motors shall be open, drip-proof, single-speed,
60 Hz, 1750 rpm 1 or 3 phase, suitable for contin-
uous duty at 104 F (40 C). Single phase motors are
capacitor start, include automatic reset thermal
overload protection and are available in 115, 208,
230, or 277 volts (60 Hz). Three-phase motors are
available in 208, 230, or 460 volts (60 Hz). Motors
are resilient base mounted (except 3 and 5 hp
motors, which are rigid base mounted).

G. Options and Accessories:

1. Factory-Installed Options:

a. Coils:

1) Unit coil(s) shall be equipped with auto-

matic air vent(s).

2) Unit shall be equipped with a high-

capacity 6-row or 8-row coil for installa-
tion in a 2-pipe system. 

3) For installation in a 4-pipe system, unit

shall be equipped with either a 4-row
cooling/1-row hot water heating split-
circuit coil, or a 4/2, 6/1, or 6/2 split-
circuit coil as required.

4) Unit shall be equipped with either a 4-

row DX (direct expansion) cooling coil
or a 6-row DX cooling coil as required.

5) Unit coil(s) shall be copper fin, copper

tube with stainless steel tube and sheets.

b. Filters:

1) A two-in. pleated filter shall be installed

in the unit (standard).

Guide specifications

Summary of Contents for AIRSTREAM 42BHC

Page 1: ...round comfort air conditioning with central station operating economy A variety of coil options reduces first cost Four 6 or 8 row cooling coils combine needed capacities with the most effi cient hea...

Page 2: ...in threaded rods are provided on the top and bottom of each corner of the unit One in duct collars on discharge and on return are fur nished standard These integral duct collars cut installation time...

Page 3: ...pprox lb per row of coil 0 240 0 240 0 324 0 324 0 420 0 492 0 768 1 020 FANS Number Size in 1 9 x 4 1 9 x 6 1 10 x 4 1 10 x 7 1 11 x 10 1 12 x 9 1 12 x 12 1 15 x 12 COPPER COIL CONN 8 ROW in Cooling...

Page 4: ...12 kW 1 or 2 stage only single phase 1 to 40 kW 1 stage only 3 phase 4 to 40 kW 1 or 2 stage only 3 phase 12 to 40 kW 1 2 or 3 stage 3 phase Heater coils are constructed of high grade resistance wire...

Page 5: ...ntrol valve 4 pipe ACO MCO automatic changeover manual changeover with on auto fan mode button one or 2 stage electric heat signal available purge cycle and temperature sensor for 2 pipe cold water ho...

Page 6: ...C D E F J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16 201...

Page 7: ...J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16 201 4 71 2 1...

Page 8: ...A B C D E F J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16...

Page 9: ...BVC DIMENSIONS in Fan Size Depth Width Height Supply Duct Return Duct A B C E F 06 9 x 4 20 281 16 361 2 71 8 109 16 33 4 241 16 167 16 08 9 x 6 20 281 16 361 2 89 16 109 16 33 4 241 16 167 16 10 10 x...

Page 10: ...pecifications are subject to change without notice 3 Right hand shown left hand opposite 4 Hanger rods which are field supplied are shown for reference only UNIT 42BVC DIMENSIONS in Fan Size Depth Wid...

Page 11: ...42BVC DIMENSIONS in Fan Size Depth Width Height Supply Duct Return Duct A B C E F 06 9 x 4 20 281 16 361 2 71 8 109 16 33 4 241 16 167 16 08 9 x 6 20 281 16 361 2 89 16 109 16 33 4 241 16 167 16 10 1...

Page 12: ...1 55 47 52 55 51 52 47 205 With Heat 50 59 59 68 59 50 68 59 236 10 No Heat 63 71 55 63 71 63 63 55 253 With Heat 62 76 68 81 76 62 81 68 287 12 No Heat 64 72 56 64 72 64 64 56 256 With Heat 63 76 68...

Page 13: ...39 29 20 10 20 46 35 23 12 30 74 55 37 18 40 98 74 49 25 NOTE Unit weights shown in pounds 10 are based on the 8 row coil and 1 Hp motor UNIT 42BVC CONFIGURATION RIGHT HAND UNITS LEFT HAND UNITS TOTA...

Page 14: ...ET RIGHT HAND SIDE VIEWS W 4 2 4 C 1 H A A B A 2 4 MIXING BOX NOTE All dimensions in inches 42BHC BVC UNIT SIZE DIMENSIONS in H W A B C 06 18 5 28 6 24 11 08 18 5 28 6 24 11 10 20 25 37 8 33 13 12 20...

Page 15: ...08 28 51 6 16 1 42BHC10 37 55 2 18 1 42BHC12 37 55 2 18 1 42BHC16 47 55 4 18 1 42BHC20 48 57 8 18 1 42BHC30 48 59 8 20 1 42BHC40 62 63 0 20 1 UNIT DIMENSIONS in W D A 42BVC06 28 35 5 16 1 42BVC08 28 3...

Page 16: ...5 20 psig 1 in 14 72 19 38 2 774 8 247 20 65 25 19 8 17 psig High Close Off Power On Power Off 2 way 1 2 in 13 29 2 285 16 09 7 41 3 5 60 psig 3 4 in 13 59 3 156 18 59 7 936 4 6 60 psig 1 in 14 97 3 3...

Page 17: ...Out 42BHC BVC UNIT SIZE HEAD STUB OUT SIZES in 8 Row Coil SO Nominal 6 Row Coil SO Nominal 4 Row Coil SO Nominal Heating 1 or 2 SO Row Coil Nominal 06 1 0 75 0 75 0 5 08 1 0 75 0 75 0 5 10 1 0 75 0 75...

Page 18: ...1 8 47 8 6 0 61 8 123 4 81 8 211 16 1 31 2 63 4 133 8 151 2 211 16 211 16 93 16 33 4 2 313 16 61 8 123 4 1513 16 31 4 31 4 101 4 47 8 8 0 61 8 123 4 101 4 211 16 10 12 4 0 73 4 143 8 515 16 211 16 1 5...

Page 19: ...d quick vent feature via knurled vent screw Application Optional replacement for manual air vent Automatically passes minute quantities of air through the fiber discs which expand upon contact with wa...

Page 20: ...flow balancing 3 0 8 9 150 200 STRAINER Y type body with 50 mesh stainless steel screen Application Used for removal of small particles from system water during normal system operation Should not be u...

Page 21: ...placed in the open position for second ary unit flushing constant water flow prior to start up etc Manual override is automatically disengaged when valve is electrically acti vated Consult factory fo...

Page 22: ...Drop for Cv Factor and Water Flow Rate table on page 33 From the Cv Factor by Coil and Unit Size table on page 32 find the Cv value for unit size 16 with four rows Cv 7 2 P GPM 0 658 x Cv 2 7 0 0 658...

Page 23: ...04 1 00 1 00 1 00 0 95 0 97 0 97 0 90 0 94 0 93 0 85 0 90 0 89 0 80 0 86 0 85 0 75 0 82 0 81 0 70 0 78 0 77 0 65 0 74 0 72 0 60 0 70 0 67 0 55 0 66 0 62 0 50 0 62 0 57 0 45 0 58 0 52 0 40 0 53 0 47 0...

Page 24: ...38 4 25 1 45 30 3 21 7 50 22 5 18 6 8 40 42 6 27 2 45 33 7 23 3 50 24 7 19 8 10 1000 4 40 40 5 27 3 45 31 6 23 7 50 23 4 20 6 6 40 52 2 33 3 45 41 7 28 7 50 31 2 24 5 8 40 57 7 36 0 45 46 4 31 0 50 34...

Page 25: ...42 4 99 4 11 3 119 2 91 1 25 9 8 122 3 92 7 8 0 99 8 83 2 6 0 75 6 75 6 11 8 147 9 102 7 9 9 124 0 93 0 8 0 100 3 84 0 14 1 175 8 112 1 12 0 150 4 102 4 10 0 125 5 93 3 DB Dry Bulb Temperature EWT Ent...

Page 26: ...165 7 117 1 10 8 135 2 103 6 8 4 104 4 90 7 16 0 199 7 129 9 13 5 168 3 116 6 10 9 136 1 103 6 18 9 236 1 142 0 16 3 203 9 128 8 13 6 170 6 116 0 28 12 2 170 8 119 3 9 9 139 0 105 2 7 6 106 9 91 7 14...

Page 27: ...2 27 6 220 5 134 1 22 2 177 4 117 0 16 9 135 1 101 5 18 13 4 120 7 96 0 9 6 86 3 82 0 6 3 56 3 56 3 18 0 162 2 112 6 13 7 122 9 96 9 9 3 84 1 84 1 23 2 208 8 129 3 18 5 166 1 112 7 13 8 124 6 97 8 DB...

Page 28: ...0 29 4 51 8 36 2 66 5 34 6 65 9 41 2 45 26 0 26 0 32 8 32 8 37 9 23 8 38 3 30 8 53 0 29 4 52 6 36 1 50 18 9 18 9 25 9 25 9 21 8 18 0 25 9 25 9 37 2 23 7 38 3 31 0 1600 40 41 9 34 1 43 7 43 7 56 7 32 3...

Page 29: ...0 37 3 68 6 44 6 84 6 42 7 83 7 49 8 45 40 4 32 9 42 2 42 2 54 6 31 2 54 6 38 6 70 6 36 9 70 1 44 2 50 27 5 27 5 34 9 34 9 38 6 24 9 40 2 33 0 54 7 30 9 55 2 38 5 1600 40 59 0 43 0 55 1 55 1 75 1 40 9...

Page 30: ...2 10 in x 7 in 1000 629 0 13 688 0 15 744 0 18 789 0 20 849 0 22 898 0 24 946 0 26 991 0 29 1035 0 31 1100 656 0 16 712 0 19 765 0 21 816 0 23 865 0 26 912 0 28 958 0 30 1002 0 33 1044 0 35 1200 686 0...

Page 31: ...1292 0 63 1326 0 66 1359 0 69 1392 0 72 1400 1124 0 55 1162 0 58 1198 0 61 1234 0 64 1269 0 67 1304 0 70 1338 0 73 1371 0 77 1404 0 80 16 11 in x 10 in 1400 985 0 42 1018 0 45 1051 0 48 1083 0 51 111...

Page 32: ...7 0 22 0 11 0 06 0 09 0 18 1100 0 08 0 29 0 44 0 58 0 03 0 07 0 14 0 20 0 27 0 14 0 08 0 11 0 22 1200 0 09 0 35 0 52 0 69 0 04 0 08 0 16 0 24 0 32 0 16 0 09 0 13 0 26 1300 0 11 0 41 0 61 0 81 0 05 0 0...

Page 33: ...4 4 15 7 18 4 21 3 24 5 27 9 31 5 4 8 0 6 0 9 1 2 1 6 2 0 2 5 3 0 3 6 4 2 4 9 5 6 6 4 7 2 8 1 9 0 10 0 11 0 12 1 13 2 14 4 16 9 19 6 22 5 25 6 28 9 5 0 0 5 0 8 1 1 1 4 1 8 2 3 2 7 3 3 3 9 4 5 5 2 5 9...

Page 34: ...34 Typical wiring schematics BASE UNIT SINGLE PHASE POWER MOTOR CONTROL DISCONNECT OPTION SINGLE PHASE POWER...

Page 35: ...35 BASE UNIT THREE PHASE POWER MOTOR CONTROL DISCONNECT OPTION THREE PHASE POWER...

Page 36: ...PERATION AND HONEYWELL THERMOSTAT 2 PIPE OR 4 PIPE HEATING COOLING WITH SINGLE SPEED FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT NOTES 1 Optional valves are field wired 2 No HW valve with electric...

Page 37: ...s that Carrier s fan coil units have been examined by UL and comply with the organization s applicable standards of U S and Canadian national product safety standard UL 1995 CSA C22 2 No 236 kW 42BHC...

Page 38: ...ric heat options and control option Interlocking disconnect switch Heater power fusing 24 v class 2 transformer 40 va 8 pole control terminal strip Auto reset temperature limit switch Manual reset bac...

Page 39: ...onnection and 1 2 in male MPT stainless secondary drain connection capped when not required The outside surface of the drain pan shall be insulated with 1 8 in closed cell insulation C Fans Belt drive...