Basic definitions

Unit hand — 

When facing the supply air outlet from the

front of the unit (air blowing in your face), your right hand
will be the right hand side of the unit and your left hand the
left hand side of the unit.

PIPING COMPONENTS

LEGEND

*Check all system component pressure ratings (coils, values, pumps,

etc.) with manufacturer and any applicable local or national piping
codes prior to specifying system pressure rating.

SYMBOL/SKETCH

DESCRIPTION

C

V

FACTOR

RATING*

1

/

2

3

/

4

PSI

F

MANUAL AIR VENT:

Threaded brass needle valve

with screwdriver slot for adjustment.
Application — Body brazed into high point of heat-
ing and cooling coils for bleeding air from coil. Stan-
dard item on all hydronic coils (not used on steam
or DX coils). Should not be used in lieu of main sys-
tem air vents.

N/A

N/A

400

100

AUTOMATIC AIR VENT:

Nickel plated brass valve,

fiber-disc type, with positive shut-off ballcheck and
quick vent feature via knurled vent screw.
Application — Optional replacement for manual air
vent. Automatically passes minute quantities of air
through the fiber discs which expand upon contact
with water, completely sealing the valve. As air
accumulates, the fiber discs dry and shrink, repeat-
ing the cycle. Not recommended for removing large
quantities of air encountered during initial start-up
or subsequent draining and refilling. Should not be
used in lieu of main system air vents.

N/A

N/A

125

240

SWAGE:

Copper tube end expanded to accept a

copper tube of the same size for factory or field
brazing.
Application — Used where possible for all tubing
joints for best joint integrity.

N/A

N/A

300

200

CIRCUIT SETTER:

Variable water flow balancing

valve with manual adjustment knob, pointer, per-
cent-open scale, memory stop and integral pres-
sure read-out ports.
Application — Used for close tolerance water flow
balancing. Positive shut-off ball valve feature allows
usage as combination balancing and shut-off valve.

2.12

3.9

300

250

Cv —

Coefficient of Velocity

DX —

Direct Expansion

Application data

UNIT HAND

Summary of Contents for AIRSTREAM 42BHC

Page 1: ...round comfort air conditioning with central station operating economy A variety of coil options reduces first cost Four 6 or 8 row cooling coils combine needed capacities with the most effi cient hea...

Page 2: ...in threaded rods are provided on the top and bottom of each corner of the unit One in duct collars on discharge and on return are fur nished standard These integral duct collars cut installation time...

Page 3: ...pprox lb per row of coil 0 240 0 240 0 324 0 324 0 420 0 492 0 768 1 020 FANS Number Size in 1 9 x 4 1 9 x 6 1 10 x 4 1 10 x 7 1 11 x 10 1 12 x 9 1 12 x 12 1 15 x 12 COPPER COIL CONN 8 ROW in Cooling...

Page 4: ...12 kW 1 or 2 stage only single phase 1 to 40 kW 1 stage only 3 phase 4 to 40 kW 1 or 2 stage only 3 phase 12 to 40 kW 1 2 or 3 stage 3 phase Heater coils are constructed of high grade resistance wire...

Page 5: ...ntrol valve 4 pipe ACO MCO automatic changeover manual changeover with on auto fan mode button one or 2 stage electric heat signal available purge cycle and temperature sensor for 2 pipe cold water ho...

Page 6: ...C D E F J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16 201...

Page 7: ...J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16 201 4 71 2 1...

Page 8: ...A B C D E F J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16...

Page 9: ...BVC DIMENSIONS in Fan Size Depth Width Height Supply Duct Return Duct A B C E F 06 9 x 4 20 281 16 361 2 71 8 109 16 33 4 241 16 167 16 08 9 x 6 20 281 16 361 2 89 16 109 16 33 4 241 16 167 16 10 10 x...

Page 10: ...pecifications are subject to change without notice 3 Right hand shown left hand opposite 4 Hanger rods which are field supplied are shown for reference only UNIT 42BVC DIMENSIONS in Fan Size Depth Wid...

Page 11: ...42BVC DIMENSIONS in Fan Size Depth Width Height Supply Duct Return Duct A B C E F 06 9 x 4 20 281 16 361 2 71 8 109 16 33 4 241 16 167 16 08 9 x 6 20 281 16 361 2 89 16 109 16 33 4 241 16 167 16 10 1...

Page 12: ...1 55 47 52 55 51 52 47 205 With Heat 50 59 59 68 59 50 68 59 236 10 No Heat 63 71 55 63 71 63 63 55 253 With Heat 62 76 68 81 76 62 81 68 287 12 No Heat 64 72 56 64 72 64 64 56 256 With Heat 63 76 68...

Page 13: ...39 29 20 10 20 46 35 23 12 30 74 55 37 18 40 98 74 49 25 NOTE Unit weights shown in pounds 10 are based on the 8 row coil and 1 Hp motor UNIT 42BVC CONFIGURATION RIGHT HAND UNITS LEFT HAND UNITS TOTA...

Page 14: ...ET RIGHT HAND SIDE VIEWS W 4 2 4 C 1 H A A B A 2 4 MIXING BOX NOTE All dimensions in inches 42BHC BVC UNIT SIZE DIMENSIONS in H W A B C 06 18 5 28 6 24 11 08 18 5 28 6 24 11 10 20 25 37 8 33 13 12 20...

Page 15: ...08 28 51 6 16 1 42BHC10 37 55 2 18 1 42BHC12 37 55 2 18 1 42BHC16 47 55 4 18 1 42BHC20 48 57 8 18 1 42BHC30 48 59 8 20 1 42BHC40 62 63 0 20 1 UNIT DIMENSIONS in W D A 42BVC06 28 35 5 16 1 42BVC08 28 3...

Page 16: ...5 20 psig 1 in 14 72 19 38 2 774 8 247 20 65 25 19 8 17 psig High Close Off Power On Power Off 2 way 1 2 in 13 29 2 285 16 09 7 41 3 5 60 psig 3 4 in 13 59 3 156 18 59 7 936 4 6 60 psig 1 in 14 97 3 3...

Page 17: ...Out 42BHC BVC UNIT SIZE HEAD STUB OUT SIZES in 8 Row Coil SO Nominal 6 Row Coil SO Nominal 4 Row Coil SO Nominal Heating 1 or 2 SO Row Coil Nominal 06 1 0 75 0 75 0 5 08 1 0 75 0 75 0 5 10 1 0 75 0 75...

Page 18: ...1 8 47 8 6 0 61 8 123 4 81 8 211 16 1 31 2 63 4 133 8 151 2 211 16 211 16 93 16 33 4 2 313 16 61 8 123 4 1513 16 31 4 31 4 101 4 47 8 8 0 61 8 123 4 101 4 211 16 10 12 4 0 73 4 143 8 515 16 211 16 1 5...

Page 19: ...d quick vent feature via knurled vent screw Application Optional replacement for manual air vent Automatically passes minute quantities of air through the fiber discs which expand upon contact with wa...

Page 20: ...flow balancing 3 0 8 9 150 200 STRAINER Y type body with 50 mesh stainless steel screen Application Used for removal of small particles from system water during normal system operation Should not be u...

Page 21: ...placed in the open position for second ary unit flushing constant water flow prior to start up etc Manual override is automatically disengaged when valve is electrically acti vated Consult factory fo...

Page 22: ...Drop for Cv Factor and Water Flow Rate table on page 33 From the Cv Factor by Coil and Unit Size table on page 32 find the Cv value for unit size 16 with four rows Cv 7 2 P GPM 0 658 x Cv 2 7 0 0 658...

Page 23: ...04 1 00 1 00 1 00 0 95 0 97 0 97 0 90 0 94 0 93 0 85 0 90 0 89 0 80 0 86 0 85 0 75 0 82 0 81 0 70 0 78 0 77 0 65 0 74 0 72 0 60 0 70 0 67 0 55 0 66 0 62 0 50 0 62 0 57 0 45 0 58 0 52 0 40 0 53 0 47 0...

Page 24: ...38 4 25 1 45 30 3 21 7 50 22 5 18 6 8 40 42 6 27 2 45 33 7 23 3 50 24 7 19 8 10 1000 4 40 40 5 27 3 45 31 6 23 7 50 23 4 20 6 6 40 52 2 33 3 45 41 7 28 7 50 31 2 24 5 8 40 57 7 36 0 45 46 4 31 0 50 34...

Page 25: ...42 4 99 4 11 3 119 2 91 1 25 9 8 122 3 92 7 8 0 99 8 83 2 6 0 75 6 75 6 11 8 147 9 102 7 9 9 124 0 93 0 8 0 100 3 84 0 14 1 175 8 112 1 12 0 150 4 102 4 10 0 125 5 93 3 DB Dry Bulb Temperature EWT Ent...

Page 26: ...165 7 117 1 10 8 135 2 103 6 8 4 104 4 90 7 16 0 199 7 129 9 13 5 168 3 116 6 10 9 136 1 103 6 18 9 236 1 142 0 16 3 203 9 128 8 13 6 170 6 116 0 28 12 2 170 8 119 3 9 9 139 0 105 2 7 6 106 9 91 7 14...

Page 27: ...2 27 6 220 5 134 1 22 2 177 4 117 0 16 9 135 1 101 5 18 13 4 120 7 96 0 9 6 86 3 82 0 6 3 56 3 56 3 18 0 162 2 112 6 13 7 122 9 96 9 9 3 84 1 84 1 23 2 208 8 129 3 18 5 166 1 112 7 13 8 124 6 97 8 DB...

Page 28: ...0 29 4 51 8 36 2 66 5 34 6 65 9 41 2 45 26 0 26 0 32 8 32 8 37 9 23 8 38 3 30 8 53 0 29 4 52 6 36 1 50 18 9 18 9 25 9 25 9 21 8 18 0 25 9 25 9 37 2 23 7 38 3 31 0 1600 40 41 9 34 1 43 7 43 7 56 7 32 3...

Page 29: ...0 37 3 68 6 44 6 84 6 42 7 83 7 49 8 45 40 4 32 9 42 2 42 2 54 6 31 2 54 6 38 6 70 6 36 9 70 1 44 2 50 27 5 27 5 34 9 34 9 38 6 24 9 40 2 33 0 54 7 30 9 55 2 38 5 1600 40 59 0 43 0 55 1 55 1 75 1 40 9...

Page 30: ...2 10 in x 7 in 1000 629 0 13 688 0 15 744 0 18 789 0 20 849 0 22 898 0 24 946 0 26 991 0 29 1035 0 31 1100 656 0 16 712 0 19 765 0 21 816 0 23 865 0 26 912 0 28 958 0 30 1002 0 33 1044 0 35 1200 686 0...

Page 31: ...1292 0 63 1326 0 66 1359 0 69 1392 0 72 1400 1124 0 55 1162 0 58 1198 0 61 1234 0 64 1269 0 67 1304 0 70 1338 0 73 1371 0 77 1404 0 80 16 11 in x 10 in 1400 985 0 42 1018 0 45 1051 0 48 1083 0 51 111...

Page 32: ...7 0 22 0 11 0 06 0 09 0 18 1100 0 08 0 29 0 44 0 58 0 03 0 07 0 14 0 20 0 27 0 14 0 08 0 11 0 22 1200 0 09 0 35 0 52 0 69 0 04 0 08 0 16 0 24 0 32 0 16 0 09 0 13 0 26 1300 0 11 0 41 0 61 0 81 0 05 0 0...

Page 33: ...4 4 15 7 18 4 21 3 24 5 27 9 31 5 4 8 0 6 0 9 1 2 1 6 2 0 2 5 3 0 3 6 4 2 4 9 5 6 6 4 7 2 8 1 9 0 10 0 11 0 12 1 13 2 14 4 16 9 19 6 22 5 25 6 28 9 5 0 0 5 0 8 1 1 1 4 1 8 2 3 2 7 3 3 3 9 4 5 5 2 5 9...

Page 34: ...34 Typical wiring schematics BASE UNIT SINGLE PHASE POWER MOTOR CONTROL DISCONNECT OPTION SINGLE PHASE POWER...

Page 35: ...35 BASE UNIT THREE PHASE POWER MOTOR CONTROL DISCONNECT OPTION THREE PHASE POWER...

Page 36: ...PERATION AND HONEYWELL THERMOSTAT 2 PIPE OR 4 PIPE HEATING COOLING WITH SINGLE SPEED FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT NOTES 1 Optional valves are field wired 2 No HW valve with electric...

Page 37: ...s that Carrier s fan coil units have been examined by UL and comply with the organization s applicable standards of U S and Canadian national product safety standard UL 1995 CSA C22 2 No 236 kW 42BHC...

Page 38: ...ric heat options and control option Interlocking disconnect switch Heater power fusing 24 v class 2 transformer 40 va 8 pole control terminal strip Auto reset temperature limit switch Manual reset bac...

Page 39: ...onnection and 1 2 in male MPT stainless secondary drain connection capped when not required The outside surface of the drain pan shall be insulated with 1 8 in closed cell insulation C Fans Belt drive...

Page 40: ...the event of an air failure 2 Single phase heaters shall be available in 115 208 230 or 277 volts 60 Hz Three phase electric heat shall be available in 208 230 or 460 volts 60 Hz 2 Field Installed Ac...

Reviews: