background image

OPERATIONAL INFORMATION

Five-minute Compressor Timeguard

This timer prevents the compressor from starting unless it has been off for at least 5 minutes. It can be defeated for 1 cycle by simultaneously
pressing the FAN mode button and the INCREASE TEMPERATURE button.

Fifteen-minute Cycle Timer

This timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle. Its function is to assure
that equipment is not cycled more than 4 times per hour. This timer is defeated for 1 cycle when the desired temperature is manually changed.
It can also be defeated for 1 cycle by simultaneously pressing the FAN mode button and the INCREASE TEMPERATURE button.

Fifteen-minute Staging Timer

In multistage heating or cooling, this timer prevents any higher stage from turning on until the preceeding stage has been on for 15 minutes.
This timer is defeated if the temperature error is greater than 5 degrees (usually due to a large change in desired temperature).

Two-minute Minimum On Time

When a stage is turned on, it cannot be turned off until it has been on for at least 2 minutes.

Auto Changeover

When the auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until a 3 degree demand has existed for
20 minutes. If the desired temperature is changed, the 20 minute requirement is deleted, but the 3 degree requirement is preserved.

Power On Check

When AC power is first applied, all segments of the display are turned on for a few seconds. Following this, the temperature display indicates
the model/configuration via the following 2 digit code:
AC—1-speed air conditioner
HP—1-speed heat pump
A2—2-speed air conditioner
H2—2-speed heat pump
HS—1-speed heat pump with 3-stage auxiliary heat.

Error Codes

E1 - If the thermostat cannot properly read room temperature, the display will indicate E1 and all outputs (except the fan if on) will turn off.

This is to prevent operation of the equipment if the thermostat has failed.

E2 - If the AC line voltage drops below a minimum (brownout) level, all outputs are turned off and the display indicates E2. This condition

will remain for 15 seconds after proper line voltage is restored. If the AC line voltage disappears completely, the display will immediately
go blank.

Energy Savings Icon

This icon is displayed under these conditions:
1-speed HP heating without auxiliary heat.
2-speed HP on LO or HI speed heating without auxiliary heat.
2-speed HP or AC on LO speed cooling.

Smart Recovery

With Smart Recovery selected, the transition out of a heating setback begins a fixed time period before the selected recovery time and gradually
adjusts room temperature so that the desired temperature will be achieved at the selected recovery time. The fixed time period is 1 hr for
furnaces and 1.5 hrs for heat pumps.

Thermostat Troubleshooting

SYMPTOM

WHAT TO CHECK

No LCD on temperature display

Check for 24 VAC between R and C at terminal connections. Both R and C must be connected for proper opera-
tion.

E2

on temperature display

Brownout condition or too low of voltage to thermostat. Double check wiring and check for 24 VAC between R and
C. E2 will clear 15 seconds after proper voltage is restored.

E1

on temperature display

Temperature sensor reading out of range. Check sensor for damage. If recycling power does not clear display,
thermostat should be replaced.

Clean Filter

on temperature display

After 500 hours of blower operation

clean filter

will display on LCD. This is to remind the homeowner to

check

filter. Press

reset filter

button to clear display and reset timer to 0.

Trouble

on temperature display

This will indicate a problem with system equipment. 24 VAC is present on the

L

terminal connection.

--

on temperature display

If the outdoor sensor is open, not connected, or shorted

--

will be displayed.

Cooling will not come on

Select COOL mode. Set desired temperature to 10 degrees below room temperature. Simultaneously press FAN
and INCREASE TEMPERATURE buttons to defeat timers. Check for 24 VAC at Y/Y2 terminal. If present, thermo-
stat is OK and problem is with equipment or wiring. If not present, replace thermostat.

Heating will not come on

Select HEAT mode. Set desired temperature to 10 degrees above room temperature. Simultaneously press FAN
and INCREASE TEMPERATURE buttons to defeat timers. Check for 24 VAC at Y/Y2 (with HP) or W/W1 (with
AC) terminal. If present, thermostat is OK and problem is with equipment or wiring. If not present, replace thermo-
stat.

7

Summary of Contents for A94134

Page 1: ...ly HP 1 stage cool 2 stage heat for either HP or AC with 2 stage heat 2S 2 stage cool 2 stage heat for 2 speed AC systems or 2 stage cool 3 stage heat for 2 speed HP systems or 1 stage cool 4 stage heat for 1 speed HP with special 3 stage electric heat Use each only for its intended purpose See Table 1 INSTALLATION Step 1 Thermostat Location Thermostat should be mounted Approximately 5 ft 1 5m fro...

Page 2: ... wires to the correct terminals of the thermostat connector See Table 1 and Fig 2 through 14 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push excess wiring into wall Seal hole in wall to prevent drafts 10 Snap hinge back together...

Page 3: ...ed Operation 1 Press FAN button to select AUTO or ON position Fan annunciator displays current selection 2 Press MODE button to select OFF HEAT COOL AUTO Heat pumps will also have an EHEAT mode Mode annun ciator displays current selection 3 Press up or down buttons to select desired temperature 4 If daily cycles are to be programmed now refer to Homeown er s Guide for programming instructions 5 If...

Page 4: ... B L S1 S2 C Y C MODEL AC THERMOSTAT TYPICAL FAN COIL SINGLE SPEED AIR CONDITIONER See notes 3 and 7 W2 Y Y2 W3 Y1 O L E Fig 6 Single Speed Air Conditioner with Typical Fan Coil Dual Stage Heat Control A94274 24 VAC HOT FAN HEAT STAGE 1 COOL STAGE 1 HEAT STAGE 2 N A R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A N A OUTDOOR SENSOR CONNECTION C B L S1 S2 C Y C MODEL HP THERMOSTAT TYPICAL FAN COIL SIN...

Page 5: ...T TWO STAGE OR VARIABLE SPEED FURNACE TWO SPEED AIR CONDITIONER See note 5 R Y1 R G L W W1 Y Y2 W2 Fig 10 Two Speed Air Conditioner with Typical Fan Coil A94223 24 VAC HOT FAN HEAT STAGE 1 COOL STAGE 2 HEAT STAGE 2 COOL STAGE 1 R G W W1 Y Y2 O W2 Y1 W2 R G 24 VAC COMM N A TROUBLE OUTDOOR SENSOR CONNECTION C B L S1 S2 C Y2 C MODEL 2S THERMOSTAT TYPICAL FAN COIL TWO SPEED AIR CONDITIONER See notes 5...

Page 6: ...fer to furnace instructions for proper setup 2 On HP models 1 stage cool 2 stage heat O W2 can control second stage heat Refer to indoor unit instructions for proper setup 3 On AC models 1 stage cool 1 stage heat O W2 is not connected Thermostat can only control 1 stage of heat 4 Refer to outdoor unit installation instructions for latent kit requirements 5 O W2 can control second stage heat Refer ...

Page 7: ...emain for 15 seconds after proper line voltage is restored If the AC line voltage disappears completely the display will immediately go blank Energy Savings Icon This icon is displayed under these conditions 1 speed HP heating without auxiliary heat 2 speed HP on LO or HI speed heating without auxiliary heat 2 speed HP or AC on LO speed cooling Smart Recovery With Smart Recovery selected the trans...

Page 8: ...6231 49008c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab misc misc PC 101 Catalog No 92 33TS TA1C Printed in U S A Form TSTAT 1SI Pg 8 9 94 Replaces New ...

Reviews: