53
Table 3 — Electrical Data With VAV Option (cont)
LEGEND
*The VAV option is not available on 62M040 units.
†Fused disconnect only.
**Exhaust and supply fan motors are 230-3-60.
UNIT SIZE
62M*
VFD
VOLTAGE
V-Ph-Hz
ERV
WHEEL
FLA
VFD
CURRENT
INPUT
VALUE
AMP
EXHAUST AND SUPPLY
FAN MOTOR
HEATER
SIZE
(kW)
POWER SUPPLY
PRE-
HEATER
(Optional)
FLA
DISCONNECT
(Optional)
NEC - FLA
Hp
FLA
MCA
MOCP
Amps
Fuse Size†
Amps
640
208/230-3-60
1.2
26
22
7.5
—
53.61
65.10
84.64
—
100
80
8
73.72
90.24 104.74
20.11
200
100
10
78.75
96.52 109.77
25.13
100
15
91.31 112.23 122.33
37.70
110
460-3-60
12.9
11
—
26.65
32.29
41.98
—
60
40
8
36.70
44.86
52.03
10.05
50
10
39.21
48.00
54.55
12.57
80
50
15
45.50
55.85
60.83
18.85
60
575-3-60
11.5
9
—
23.62
28.71
37.33
—
60
35
8
31.66
38.76
45.37
8.04
45
10
33.67
41.28
47.38
10.05
45
15
38.70
47.56
52.40
15.08
80
50
750
208/230-3-60
2.5
26
22
—
54.91
65.10
84.64
—
100
80
10
80.05
96.52 109.77
25.13
200
100
15
92.61 112.23 122.33
37.70
110
20
105.18 127.93 134.90
50.26
125
460-3-60
1.2
12.9
11
—
27.20
32.29
41.98
—
60
40
10
39.76
48.00
54.55
12.57
80
50
15
46.05
55.85
60.83
18.85
60
20
52.33
63.71
67.11
25.13
60
575-3-60
1.4
11.5
9
—
24.50
28.71
37.33
—
60
35
10
34.55
41.28
47.38
10.05
45
15
39.58
47.56
52.40
15.08
80
50
20
44.61
53.84
57.43
20.11
50
950
208/230-3-60
2.5
34
30.8
10
—
70.86
85.00 110.50
—
200
110
10
98.65 119.74 138.29
27.79
125
15
112.55 137.11 152.19
41.69
N/A
20
126.44 154.48 166.08
55.58
N/A
460-3-60
1.2
16.5
14
—
34.28
41.15
53.49
—
80
50
10
46.85
56.85
66.06
12.57
60
15
53.13
64.71
72.34
18.85
70
20
59.41
72.56
78.62
25.13
100
70
575-3-60
1.4
14
11
—
29.63
35.12
45.66
—
60
45
10
39.68
47.69
55.71
10.05
80
50
15
44.71
53.97
60.74
15.08
60
20
49.73
60.25
65.76
20.11
60
ERV
—
Energy Recovery Ventilator
FLA
—
Full Load Amps
Hp
—
Horsepower
MCA
—
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
NEC
—
National Electric Code
N/A
—
Not Applicable
VFD
—
Variable Frequency Drive
Summary of Contents for 62MB