background image

furnace blower motor BLWM on low-cooling speed
(same speed as for low-gas heat). The R to Y1-and-Y2
circuits start the outdoor unit on high-cooling speed,
and the R to G-and-Y2 circuits start furnace blower
motor BLWM on high-cooling speed.

NOTE:

Y1 is found in the outdoor unit. The furnace control CPU

controls blower motor BLWM speed by sensing only G for
low-cooling speed and Y/Y2 for high-cooling speed.

(2.) The EAC terminals EAC-1 and EAC-2 are energized

with 115v when blower motor BLWM is operating on
either cooling speed.

(3.) When thermostat is satisfied, the R to G-and-Y1 or R

to G-and-Y1-and-Y/Y2 circuits open. The outdoor
unit stops, and furnace blower continues operating on
cooling speed for an additional 90 sec.

4. Continuous Blower Mode

a. When R to G circuit is closed by thermostat, the blower

motor BLWM operates on low-gas heat speed (identical to
low-cool speed). Terminals EAC-1 and EAC-2 are ener-
gized with 115v as long as blower motor BLWM is
energized.

b. During a

call for heat,

the blower motor BLWM stops

during ignitor warm-up (17 sec), ignition (7 sec), and
blower on delay (45 sec), allowing furnace heat exchangers
to heat up quickly.

c. The blower motor BLWM reverts to continuous blower

speed after the heating cycle is completed. In high-gas heat,
the furnace control CPU holds the blower motor BLWM at
high-gas-heat speed during the selected blower off delay
period before reverting to continuous blower speed.

(1.) When thermostat

calls for low-cooling,

the blower

motor BLWM continues to operate on low-cool speed.
When thermostat is satisfied, the blower motor
BLWM continues on continuous blower speed.

(2.) When thermostat

calls for high-cooling,

the blower

motor BLWM operates on high-cool speed. When the
thermostat is satisfied, the blower motor BLWM
operates an additional 2 sec on high-cool speed before
reverting back to continuous blower speed.

(3.) When R-G circuit is opened, the blower motor BLWM

continues operating for an additional 90 sec if no other
function requires blower motor BLWM operation.

5. Heat Pump Mode

NOTE:

A dual fuel thermostat or accessory interface kit is

required with single-speed heat pumps. See dual fuel thermostat or
interface kit Installation Instructions for single-speed heat pump
thermostat and interface connections. No interface kit is needed for
2-speed heat pumps. See 2-speed heat pump Installation Instruc-
tions to determine whether a standard or dual-fuel heat pump
thermostat is required and for thermostat connections.

a. Single-Speed Heat Pump Cooling

(1.) The thermostat and interface kit close the R to

G-and-Y/Y2 circuit to start the furnace blower motor
BLWM on high-cooling speed. The Y/Y2 input to the
furnace control is necessary to provide adequate cool-
ing airflow.

(2.) The EAC terminals EAC-1 and EAC-2 are energized

with 115v when the blower motor BLWM is operat-
ing.

(3.) When thermostat is satisfied, furnace blower motor

BLWM continues operating on high-cool speed for an
additional 90 sec.

b. Two-Speed Heat Pump Cooling

(1.) The thermostat R to G circuits start the furnace blower

motor BLWM on low-cool speed. The thermostat R to
G-and-Y/Y2 circuits start the furnace blower motor
BLWM on high-cool speed.

NOTE:

The furnace control CPU controls blower motor BLWM

speed by sensing only G for low-cool speed and Y2 for high-cool
speed.

(2.) The EAC terminals EAC-1 and EAC-2 are energized

with 115v when the blower motor BLWM is operating
on either cooling speed.

(3.) When thermostat is satisfied, the furnace blower

motor BLWM continues operating on cooling speed
for an additional 90 sec.

c. Single-Speed Heat Pump Heating

(1.) The thermostat and accessory interface kit R to G-

and-Y/Y2 circuits start the furnace blower motor
BLWM on heat pump high-heat speed (identical to
high-cool speed).

(2.) The EAC terminals EAC-1 and EAC-2 are energized

with 115v when the blower motor BLWM is operat-
ing.

(3.) When thermostat is satisfied, the furnace blower motor

BLWM continues operating on heat pump high-heat
speed for an additional 90 sec.

d. Two-Speed Heat Pump Heating

(1.) The thermostat closes R-G circuit for low heat and

starts furnace blower motor BLWM on heat pump
low-heat speed (identical to low-cooling speed). Clos-
ing R-Y/Y2 circuit to furnace provides blower motor
BLWM heat pump high-heat speed.

NOTE:

The furnace control CPU controls blower motor BLWM

speed by sensing only G (for heat pump low-heat speed) and Y2
(for heat pump high-heat speed).

(2.) The EAC terminals EAC-1 and EAC-2 are energized

with 115v when the blower motor BLWM is operating
on either heating speed.

(3.) When thermostat is satisfied, the furnace blower

motor BLWM continues operating on heating speed
for an additional 90 sec.

(4.) Opening only R-Y/Y2 circuit reduces blower motor

BLWM speed to heat pump low-heat speed.

6. Defrost

a. When furnace control R to W/W1-and-Y/Y2 circuits are

closed, furnace control CPU continues blower motor
BLWM operation at heat pump heating speed until the end
of the prepurge period, then shuts off until the end of the
HSI ignitor-on period (22 sec).

b. When installed with a heat pump, the furnace control CPU

automatically holds blower off time to 22 sec during HSI
ignitor on period. After 17 sec of HSI ignitor-on period, a
trial for ignition sequence occurs as described above for
gas heating. After flame is proved and without a blower on
delay, the blower motor BLWM will operate on high-gas-
heat speed during defrost. For both single-speed and
2-speed heat pumps, defrost mode is in high-gas heat only.

c. When furnace control R-W/W1 circuit is opened, the

furnace control CPU begins the normal inducer post purge
period and the blower motor BLWM remains on for the
blower off delay period. If R-G circuit remains closed,
blower motor BLWM reverts to continuous operation.

16

Summary of Contents for 58UXT Series

Page 1: ...Conditioning Systems NFPA 90B ANSI NFPA 90B In Canada refer to the current edition of the CAN CGA B149 1 and 2 M00 National Standard of Canada Natural Gas and Propane Installation Codes NSCNGPIC Wear safety glasses and work gloves Have a fire extinguisher available during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see ...

Page 2: ...e and unit sizing Improper installation or misapplication of the furnace can require excessive servicing or cause premature component failure To aid in installation troubleshooting and service a status code label is located on the blower compartment door This label explains how to use the LED status indicator on the furnace control which is viewed through the sight glass on the door Fig 1 Dimensio...

Page 3: ...y be 0 inches For upflow furnaces bottom clearance may be 0 inches Indicates supply or return sides when furnace is in the horizontal position Line contact only permissible between lines formed by intersections of the Top and two Sides of the furnace jacket and building joists studs or framing 18 inches front clearance required for alcove For single wall vent 6 inches For Type B 1 vent 3 inches 32...

Page 4: ...ls and many other solvents commonly used in the construction process Excessive exposure to contami nated combustion air will result in safety and performance related problems Do not install furnace in a corrosive or contaminated atmo sphere Make sure all combustion and circulating air require ments are met in addition to all local codes and ordinances This furnace must be installed so the electric...

Page 5: ...tion ventilation and dilution of flue gases using 1 of the following methods See Fig 5 and Table 2 NOTE In determining free area of an opening the blocking effect of louvers grilles and screens must be considered If free area of louver or grille design is unknown assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area Screens when used must not...

Page 6: ...ir must also be handled by a duct s sealed to the furnace casing and terminating outside the space containing the furnace Secure ductwork with proper fasteners for type of ductwork used Seal supply and return duct connections to furnace with code approved tape or duct sealer Flexible connections should be used between ductwork and furnace to prevent transmission of vibration Ductwork passing throu...

Page 7: ...er or a factory specified high efficiency disposable filter see cabinet instructions If installing the filter in the furnace blower compartment deter mine location for the filter and relocate filter retaining wire if necessary After the return air duct has been connected to the furnace install the filter s inside the furnace blower compartment See Fig 7 for side return application and Fig 8 for bo...

Page 8: ...1 and Fig 11 INSTALL FURNACE 1 Position furnace in desired location 2 Connect gas supply pipe See Fig 11 for typical piping entry 3 Connect supply and return air ducts 4 Install 24 X 24 in sheet metal shield on platform in front of louvered control panel as shown in Fig 11 Step 6 Horizontal Crawlspace Installation The furnace can be installed horizontally with either LH or RH side up In a crawlspa...

Page 9: ...UDS OR FRAMING CLEARANCE TO COMBUSTIBLE MATERIALS Fig 12 Crawlspace Horizontal Installation A97600 NOTES ANGLE IRON OR EQUIVALENT ROD LOCATION USING DIMPLE LOCATORS SEE DIMENSIONAL DWG FOR LOCATIONS 3 8 IN ROD 1 A 1 In clearance minimum between top of furnace and combustible material 2 The entire length of furnace must be supported when furnace is used in horizontal position 3 8 IN HEX NUT WASHER ...

Page 10: ...tion of propane gas Install an accessible manual shutoff valve upstream of furnace gas controls and within 72 in of furnace A 1 8 in NPT plugged tapping is provided on the gas valve for test gage connection Installation of an additional 1 8 in NPT plugged tapping acces sible for test gage connection installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff...

Page 11: ...Canada Natural and Propane Installation Codes CAN CGA B149 1 and 2 M00 in Canada for proper vent sizing and installation requirements After fully assembling the vent connector to the furnace flue collar securely fasten the vent connector to the collar with 2 field supplied corrosion resistant sheet metal screws located 180 degrees apart and midway up the collar The horizontal portion of the ventin...

Page 12: ... DISCONNECT SWITCH WHEN REQUIRED JUNCTION BOX CONTROL BOX 24 V TERMINAL BLOCK TWO WIRE HEATING ONLY FIVE WIRE 1 STAGE THERMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W Y R G C GND GND GND GND GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2...

Page 13: ...ed and a 2 sec flame proving period begins If the high heat pressure switch HPS fails to close on call for high stage gas heat and the low heat pressure switch LPS closes the furnace operates at low heat gas flow rate until the high heat HPS pressure switch closes d Flame proving When burner flame is proved at flame proving sensor electrode FSE the control CPU begins blower on delay period and con...

Page 14: ...en inducer motor IDM reduces pressure sufficiently the high heat pressure switch HPS will open The low heat gas valve solenoid GV remains energized as long as low heat pressure switch LPS remains closed The blower motor BLWM switches speed for low gas heat 5 sec after R W2 circuit opens 3 Cooling Mode a Single Speed Cooling Outdoor Unit See Fig 15 for thermostat connections 1 The thermostat closes...

Page 15: ...to reset thermal overload switches 4 Blower motor speed selections are for average conditions See Installation Instructions for details on optimum speed selection 5 Replace only with a 3 AMP fuse 6 Auxiliary limit switches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RE...

Page 16: ... EAC 2 are energized with 115v when the blower motor BLWM is operat ing 3 When thermostat is satisfied furnace blower motor BLWM continues operating on high cool speed for an additional 90 sec b Two Speed Heat Pump Cooling 1 The thermostat R to G circuits start the furnace blower motor BLWM on low cool speed The thermostat R to G and Y Y2 circuits start the furnace blower motor BLWM on high cool s...

Page 17: ... for correct input a Obtain yearly heat value average at installed altitude from local gas supplier b Obtain yearly specific gravity average from local gas supplier c Verify furnace model Table 9 can only be used for model 58UXT furnaces d Find installation altitude in Table 9 NOTE For Canada altitudes of 2000 to 4500 ft use U S A altitudes of 2001 to 3000 ft in Table 9 e Find closest natural gas ...

Page 18: ... to 3000 or Canada Altitudes 2000 to 4500 775 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 43 3 8 1 6 800 44 3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 875 45 3 7 1 6 45 3 8 1 6 44 32 1 4 44 3 4 1 4 44 3 5 1 5 900 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 44 3 3 1 4 925 4...

Page 19: ...3 5 1 5 44 3 6 1 5 725 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 44 3 3 1 4 44 3 4 1 4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6 47 3 4 1 4 47 3 5 1 5 47 3 7 1 5 45 3 2 1 3 850 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 47 3 4 1 5 47 3 5 1 5 875 48 3 4 1 4 48 3 5 1 5 4...

Page 20: ...nifold Pressure High Low Orifice No Manifold Pressure High Low Orifice No Manifold Pressure High Low U S A Only 8001 to 9000 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 5 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 4 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 5 675 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 47 3 5 1 5 47 3 6 1 6 700 48 3 3 1 4 48 3 5 1 5 48 3 6 1 5 48...

Page 21: ...altitudes from 2000 to 4500 ft this furnace must be derated 10 percent by an authorized Gas Conver sion Station or Dealer To determine correct input rate for altitude see example above and use 0 82 as derate multi plier factor b Check that gas valve adjustment caps are in place for proper input to be clocked c Obtain yearly heat value average for local gas supply NOTE Be sure heating value of gas ...

Page 22: ...ry setting med low or med 5 speed blowers only Disconnect the electrical power before changing the speed tap or removing motor lead cap if used on 5 speed motors A failure to follow this warning can cause personal injury NOTE For units with 5 speed motors make sure the unused speed tap is either capped or placed on SPARE terminal on control board before power is restored d To change motor speed se...

Page 23: ...ailure 2 Check draft safeguard switch The purpose of this control is to permit the safe shutdown of the furnace during certain blocked vent conditions a Disconnect power to furnace and remove vent connector from furnace flue collar Be sure to allow time for vent pipe to cool down before removing b Restore power to furnace and set room thermostat above room temperature c After normal start up allow...

Page 24: ...e Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training Copyright 2001 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 58uxt5si Manufacturer reserves the right ...

Reviews: