Carrier 58UXT Series Operating Instructions Manual Download Page 10

Step 7—Gas Piping

Emissions control devices located at heat exchanger inlets
MUST be removed for propane installations. (Refer to gas
conversion kit for instructions.)

Gas piping must be installed in accordance with national and local
codes. Refer to the NFGC. Canadian installations must be installed
in accordance with NSCNGPIC and all authorities having juris-
diction.

The gas supply line should be a separate line running directly from
gas meter to furnace, if possible. Refer to Table 4 for recom-
mended gas pipe size. Risers must be used to connect furnace to
gas meter.

If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
gas valve and extend a minimum of 2 in. outside the furnace
casing.

Piping should be pressure tested in accordance with local and
national plumbing and gas codes before furnace has been attached.
If test pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe
must be disconnected from the furnace and capped before pressure
test. If test pressure is equal to or less than 0.5 psig (14-in. wc),
turn OFF electric shutoff switch before test. (See Fig. 14.) It is
recommended that the ground joint union be loosened before
pressure testing. After all connections have been made, purge lines
and check for leakage with regulated gas supply pressure.

Install a sediment trap in riser leading to furnace. The trap can be
installed by connecting a tee to riser leading from the furnace.
Connect a capped nipple into lower end of the tee. The capped
nipple should extend below level of gas controls. (See Fig. 14.)

Apply joint compound (pipe dope) sparingly and only to male
threads of each joint. The compound must be resistant to action of
propane gas.

Install an accessible manual shutoff valve upstream of furnace gas
controls and within 72 in. of furnace. A 1/8-in. NPT plugged
tapping is provided on the gas valve for test gage connection.
Installation of an additional 1/8-in. NPT plugged tapping, acces-
sible for test gage connection, installed immediately upstream of
gas supply connection to furnace and downstream of manual
shutoff valve, is not required. Place ground joint union between
gas control manifold and manual shutoff valve.

Use the proper length of pipes to avoid stress on the gas
control manifold. A failure to follow this warning can cause
a gas leak resulting in a fire, explosion, personal injury, or
death.

Use a backup wrench at the furnace gas control when
connecting the gas pipe to the furnace to avoid damaging gas
controls or manifold.

Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition for the
purpose of checking leakage. Use a soap-and-water solution
to check for leakage. A failure to follow this warning can
cause a fire, explosion, personal injury, or death.

Step 8—Electrical Connections

115-V WIRING

Refer to the unit rating plate or Table 5 for equipment electrical
requirements. The control system requires an earth ground for
proper operation.

Fig. 13—Horizontal Application Using Blocks

A95235

Table 4—Maximum Capacity of Gas Pipe*

NOMINAL

IRON PIPE

SIZE (IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE (FT)

10

20

30

40

50

1/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1-1/4

1.380

1400

950

770

660

580

1-1/2

1.610

2100

1460

1180

990

900

* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
supply line pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas).
Ref: Table 10-2, NFPA 54–1999.

Fig. 14—Typical Gas Pipe Arrangement

A89417

GAS

SUPPLY

MANUAL
SHUTOFF
VALVE
(REQUIRED)

SEDIMENT
TRAP

UNION

10

Summary of Contents for 58UXT Series

Page 1: ...Conditioning Systems NFPA 90B ANSI NFPA 90B In Canada refer to the current edition of the CAN CGA B149 1 and 2 M00 National Standard of Canada Natural Gas and Propane Installation Codes NSCNGPIC Wear safety glasses and work gloves Have a fire extinguisher available during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see ...

Page 2: ...e and unit sizing Improper installation or misapplication of the furnace can require excessive servicing or cause premature component failure To aid in installation troubleshooting and service a status code label is located on the blower compartment door This label explains how to use the LED status indicator on the furnace control which is viewed through the sight glass on the door Fig 1 Dimensio...

Page 3: ...y be 0 inches For upflow furnaces bottom clearance may be 0 inches Indicates supply or return sides when furnace is in the horizontal position Line contact only permissible between lines formed by intersections of the Top and two Sides of the furnace jacket and building joists studs or framing 18 inches front clearance required for alcove For single wall vent 6 inches For Type B 1 vent 3 inches 32...

Page 4: ...ls and many other solvents commonly used in the construction process Excessive exposure to contami nated combustion air will result in safety and performance related problems Do not install furnace in a corrosive or contaminated atmo sphere Make sure all combustion and circulating air require ments are met in addition to all local codes and ordinances This furnace must be installed so the electric...

Page 5: ...tion ventilation and dilution of flue gases using 1 of the following methods See Fig 5 and Table 2 NOTE In determining free area of an opening the blocking effect of louvers grilles and screens must be considered If free area of louver or grille design is unknown assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area Screens when used must not...

Page 6: ...ir must also be handled by a duct s sealed to the furnace casing and terminating outside the space containing the furnace Secure ductwork with proper fasteners for type of ductwork used Seal supply and return duct connections to furnace with code approved tape or duct sealer Flexible connections should be used between ductwork and furnace to prevent transmission of vibration Ductwork passing throu...

Page 7: ...er or a factory specified high efficiency disposable filter see cabinet instructions If installing the filter in the furnace blower compartment deter mine location for the filter and relocate filter retaining wire if necessary After the return air duct has been connected to the furnace install the filter s inside the furnace blower compartment See Fig 7 for side return application and Fig 8 for bo...

Page 8: ...1 and Fig 11 INSTALL FURNACE 1 Position furnace in desired location 2 Connect gas supply pipe See Fig 11 for typical piping entry 3 Connect supply and return air ducts 4 Install 24 X 24 in sheet metal shield on platform in front of louvered control panel as shown in Fig 11 Step 6 Horizontal Crawlspace Installation The furnace can be installed horizontally with either LH or RH side up In a crawlspa...

Page 9: ...UDS OR FRAMING CLEARANCE TO COMBUSTIBLE MATERIALS Fig 12 Crawlspace Horizontal Installation A97600 NOTES ANGLE IRON OR EQUIVALENT ROD LOCATION USING DIMPLE LOCATORS SEE DIMENSIONAL DWG FOR LOCATIONS 3 8 IN ROD 1 A 1 In clearance minimum between top of furnace and combustible material 2 The entire length of furnace must be supported when furnace is used in horizontal position 3 8 IN HEX NUT WASHER ...

Page 10: ...tion of propane gas Install an accessible manual shutoff valve upstream of furnace gas controls and within 72 in of furnace A 1 8 in NPT plugged tapping is provided on the gas valve for test gage connection Installation of an additional 1 8 in NPT plugged tapping acces sible for test gage connection installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff...

Page 11: ...Canada Natural and Propane Installation Codes CAN CGA B149 1 and 2 M00 in Canada for proper vent sizing and installation requirements After fully assembling the vent connector to the furnace flue collar securely fasten the vent connector to the collar with 2 field supplied corrosion resistant sheet metal screws located 180 degrees apart and midway up the collar The horizontal portion of the ventin...

Page 12: ... DISCONNECT SWITCH WHEN REQUIRED JUNCTION BOX CONTROL BOX 24 V TERMINAL BLOCK TWO WIRE HEATING ONLY FIVE WIRE 1 STAGE THERMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W Y R G C GND GND GND GND GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2...

Page 13: ...ed and a 2 sec flame proving period begins If the high heat pressure switch HPS fails to close on call for high stage gas heat and the low heat pressure switch LPS closes the furnace operates at low heat gas flow rate until the high heat HPS pressure switch closes d Flame proving When burner flame is proved at flame proving sensor electrode FSE the control CPU begins blower on delay period and con...

Page 14: ...en inducer motor IDM reduces pressure sufficiently the high heat pressure switch HPS will open The low heat gas valve solenoid GV remains energized as long as low heat pressure switch LPS remains closed The blower motor BLWM switches speed for low gas heat 5 sec after R W2 circuit opens 3 Cooling Mode a Single Speed Cooling Outdoor Unit See Fig 15 for thermostat connections 1 The thermostat closes...

Page 15: ...to reset thermal overload switches 4 Blower motor speed selections are for average conditions See Installation Instructions for details on optimum speed selection 5 Replace only with a 3 AMP fuse 6 Auxiliary limit switches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RE...

Page 16: ... EAC 2 are energized with 115v when the blower motor BLWM is operat ing 3 When thermostat is satisfied furnace blower motor BLWM continues operating on high cool speed for an additional 90 sec b Two Speed Heat Pump Cooling 1 The thermostat R to G circuits start the furnace blower motor BLWM on low cool speed The thermostat R to G and Y Y2 circuits start the furnace blower motor BLWM on high cool s...

Page 17: ... for correct input a Obtain yearly heat value average at installed altitude from local gas supplier b Obtain yearly specific gravity average from local gas supplier c Verify furnace model Table 9 can only be used for model 58UXT furnaces d Find installation altitude in Table 9 NOTE For Canada altitudes of 2000 to 4500 ft use U S A altitudes of 2001 to 3000 ft in Table 9 e Find closest natural gas ...

Page 18: ... to 3000 or Canada Altitudes 2000 to 4500 775 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 43 3 8 1 6 800 44 3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 875 45 3 7 1 6 45 3 8 1 6 44 32 1 4 44 3 4 1 4 44 3 5 1 5 900 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 44 3 3 1 4 925 4...

Page 19: ...3 5 1 5 44 3 6 1 5 725 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 44 3 3 1 4 44 3 4 1 4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6 47 3 4 1 4 47 3 5 1 5 47 3 7 1 5 45 3 2 1 3 850 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 47 3 4 1 5 47 3 5 1 5 875 48 3 4 1 4 48 3 5 1 5 4...

Page 20: ...nifold Pressure High Low Orifice No Manifold Pressure High Low Orifice No Manifold Pressure High Low U S A Only 8001 to 9000 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 5 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 4 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 5 675 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 47 3 5 1 5 47 3 6 1 6 700 48 3 3 1 4 48 3 5 1 5 48 3 6 1 5 48...

Page 21: ...altitudes from 2000 to 4500 ft this furnace must be derated 10 percent by an authorized Gas Conver sion Station or Dealer To determine correct input rate for altitude see example above and use 0 82 as derate multi plier factor b Check that gas valve adjustment caps are in place for proper input to be clocked c Obtain yearly heat value average for local gas supply NOTE Be sure heating value of gas ...

Page 22: ...ry setting med low or med 5 speed blowers only Disconnect the electrical power before changing the speed tap or removing motor lead cap if used on 5 speed motors A failure to follow this warning can cause personal injury NOTE For units with 5 speed motors make sure the unused speed tap is either capped or placed on SPARE terminal on control board before power is restored d To change motor speed se...

Page 23: ...ailure 2 Check draft safeguard switch The purpose of this control is to permit the safe shutdown of the furnace during certain blocked vent conditions a Disconnect power to furnace and remove vent connector from furnace flue collar Be sure to allow time for vent pipe to cool down before removing b Restore power to furnace and set room thermostat above room temperature c After normal start up allow...

Page 24: ...e Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training Copyright 2001 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 58uxt5si Manufacturer reserves the right ...

Reviews: