2. Non-Adaptive Heating Mode—Two-Stage Thermostat and
2-Stage Heating
(See Fig. 16 for thermostat connections).
NOTE:
In response to thermostat call for heat R to W/W1 and
with HIGH HEAT ONLY switch SW1 set to OFF, the control
selects low-stage heating only with LOW HEAT switch SW2 set
to ON, or the control selects adaptive heating mode with LOW
HEAT switch SW2 set to ON. The control selects high-stage
heating only with HIGH-HEAT ONLY switch SW1 set to ON. In
response to thermostat call for high-stage heat R to W1 and W2,
the control selects high-stage heating regardless of switch SW1
and SW2 settings. See Fig. 15 for description of switch settings or
Fig. 16 for control circuit diagram.
The start-up and shutdown functions and delays described in item
1. apply to the 2-stage heating mode as well, except for switching
from low- to high-stage and vice versa.
a. When the wall thermostat
″
calls for heat
″
, R-W/W1 circuit
closes for low-stage or R to W1-and-W2 circuits close for
high-stage. The furnace control performs a self check,
verifies low-heat and high-heat pressure switch contacts
LPS and HPS are open, and starts inducer motor IDM in
low speed or high speed as appropriate.
b. Switching from low- to high-gas heat—If thermostat
R-W/W1 circuit for low-gas heat is closed and R-W2
circuit for high-gas- heat closes, the control CPU switches
the inducer motor IDM speed from low to high. The
high-heat pressure switch relay HPSR closes. When in-
ducer motor IDM provides sufficient pressure to close
high-heat pressure switch HPS, the high-heat gas valve
solenoid GV is energized. The blower motor BLWM
switches speed for high-gas heat 5 sec after R-W2 circuit
closes.
c. Switching from high- to low-gas heat—If thermostat R-W2
circuit for high-gas heat opens and R to W/W1 circuit for
low-gas heat remains closed, the control CPU will switch
inducer motor IDM speed from high to low. The high-heat
pressure switch relay HPSR will open to de-energize
high-heat gas valve solenoid GV. When inducer motor
IDM reduces pressure sufficiently, the high-heat pressure
switch HPS will open. The low-heat gas valve solenoid GV
remains energized as long as low-heat pressure switch LPS
remains closed. The blower motor BLWM switches speed
for low-gas heat 5 sec after R-W2 circuit opens.
3. Cooling Mode
a. Single-Speed Cooling Outdoor Unit
(See Fig. 15 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y circuits. The R-Y
circuit starts the outdoor unit, and R to G-and-Y
circuits start the furnace blower motor BLWM on
high-cool speed.
(2.) The EAC terminals EAC-1 and EAC-2 are energized
with 115v when blower motor BLWM is operating.
(3.) When thermostat is satisfied, the R to G-and-Y circuits
are opened. The outdoor unit stops, and furnace
blower motor BLWM continues operating on high-
cool speed for an additional 90 sec.
b. Two-Speed Cooling Outdoor Unit
(See Fig. 16 for thermostat connections.)
(1.) The thermostat closes R to G-and-Y1 circuits for low
cooling or closes R to G-and-Y1-and-Y/Y2 circuits for
high cooling. The R to Y1 circuits start the outdoor
unit on low-cooling speed, and the R-G circuit starts
Table 6—Setup Switch Description
SETUP
SWITCH NO.
NORMAL
POSITION
DESCRIPTION
OF USE
SW-1
High Heat Only
OFF (Staged Gas Heat)
Turn switch on to obtain only high-gas-heat operation on
any call for heat regardless of whether R-W/W1, or
R-W/W1, -W2 is closed. SW-1 overrides SW-2.
SW-2
Low Heat (Adaptive Algorithm)
OFF (Single-Stage Thermostat)
Turn switch off for installations with single-stage thermo-
stats; control selects low-gas-heat or high-gas-heat opera-
tion based on previous cycles. Turn switch on for installa-
tions with 2-stage thermostats to permit only low-gas-heat
operation in response to closing R-W/W1. High-gas heat is
supplied only when R to W/W1 and W2 are closed.
SW-3 and SW4
ON, OFF
Switches control gas heating mode blower-off delay. (See
Table 7.)
Table 7—Blower-Off Delay Setup
Switch (SW) Position
DESIRED HEATING
MODE BLOWER-OFF
DELAY (SEC)
SETUP SWITCH
SW-3
SW-4
90
OFF
OFF
135
OFF
ON
180
ON
OFF
225
ON
ON
Fig. 18—Setup Switches on Control Center
(Factory Settings)
A96402
BLOWER-
OFF
DELAY
LOW
HEAT
(ADAPTIVE
ALGORITHM)
HIGH
HEAT
ONLY
4
3
2
OFF
ON
1
14